Eaton 9170
+
Battery Charger Module User's Guide
S
164201399 Rev E
www.eaton.com/powerquality
5
Chapter 2
Installation
The Battery Charger Module can be plugged into any UPS cabinet slot
above the battery modules. Battery Charger Modules may be installed in
any of the top three slots of the ASY-0739 12-slot external battery
cabinet.
NOTE
Do not block the cabinet's ventilation holes on the sides or the back.
Cabinet Preparation
Follow the procedures in the UPS user's guide for:
S
Equipment clearances
S
Installing the UPS cabinet and optional external battery cabinets
If additional external battery cabinets are to be used for Battery Charger
Modules, install input power wiring to each additional cabinet (see
Figure 3). Table 2 shows required wire sizes based upon the number of
Battery Charger Modules.
For each 12-slot external battery cabinet, stabilizer brackets must be
installed. If required, also install a floor anchor kit as described in the
UPS user's guide.
NOTE
The ASY-0739 12-slot external battery cabinet must be wired for input power from the
utility AC power supply.
(b) Universal Power Modules
(2-wire plus ground input)
200, 208, 220, 230, and 240 Vac
(a) Split-Phase Power Modules
(3-wire plus ground input) (2 PEN)
100/200, 110/220, 120/208, 120/240, 127/220 Vac
3
2
1
3
2
1
L2
L1
N
GND
L1
L2/N
GND
Figure 3. Input Power Wiring to ASY-0739 External Battery Cabinet
Содержание 9170+ ASY-0652
Страница 1: ...Powerware Series Eaton 9170 Battery Charger Module Models ASY 0652 and ASY 0675 User s Guide ...
Страница 14: ...OPERATION Eaton 9170 Battery Charger Module User s Guide S 164201399 Rev E www eaton com powerquality 10 ...
Страница 24: ...SPECIFICATIONS Eaton 9170 Battery Charger Module User s Guide S 164201399 Rev E www eaton com powerquality 20 ...
Страница 28: ...TROUBLESHOOTING Eaton 9170 Battery Charger Module User s Guide S 164201399 Rev E www eaton com powerquality 24 ...
Страница 29: ......
Страница 30: ......
Страница 31: ......
Страница 32: ... 164201399E 164201399 E ...