SPECIFICATIONS

Eaton 9170

+

 Battery Charger Module User's Guide  

S

  164201399 Rev E

 www.eaton.com/powerquality

12

Table 4. Model Specifications for Universal Power Modules (ASY-0528 and ASY-0674) (continued)

Nine- and Twelve-Slot Cabinet

CAUTION

  Do NOT install more than seven power and/or battery charger modules in a 9- or 12-slot cabinet.

Heat

Dissipation

Recommended

Input Service

Output Current for

200/208/220/230/240V

Input Current for

200/208/220/230/240V

UPS

kVA/Watts

Optional

Chargers

2

3/2100

46/45.5/45/44.5/44A

15/14.5/14/13/12.5A

60A

860W

(2.93 kBTU/hr)

3

3/2100

62/61.5/61/60.5/60A

15/14.5/14/13/12.5A

80A

1145W

(3.90 kBTU/hr)

4

3/2100

78/77.5/77/76.5/76A

15/14.5/14/13/12.5A

100A

1430W

(4.88 kBTU/hr)

5

3/2100

94/93.5/93/92.5/92A

15/14.5/14/13/12.5A

125A

1720W

(5.85 kBTU/hr)

0

6/4200

28/27/26/25/24A

30/29/28/26/25A

40A

570W

(1.95 kBTU/hr)

1

6/4200

44/43/42/41/40A

30/29/28/26/25A

60A

860W

(2.93 kBTU/hr)

2

6/4200

60/59/58/57/56A

30/29/28/26/25A

80A

1145W

(3.90 kBTU/hr)

3

6/4200

76/75/74/73/72A

30/29/28/26/25A

100A

1430W

(4.88 kBTU/hr)

4

6/4200

92/91/90/89/88A

30/29/28/26/25A

125A

1720W

(5.85 kBTU/hr)

5

6/4200

102A*

30/29/28/26/25A

125A

1995W

(6.75 kBTU/hr)

0

9/6300

42/40.5/39/37.5/36A

45/43.5/42/39/37.5A

60A

860W

(2.93 kBTU/hr)

1

9/6300

58/56.5/55/53.5/52A

45/43.5/42/39/37.5A

80A

1145W

(3.90 kBTU/hr)

2

9/6300

74/72.5/71/69.5/68A

45/43.5/42/39/37.5A

100A

1430W

(4.88 kBTU/hr)

3

9/6300

90/88.5/87/85.5/84A

45/43.5/42/39/37.5A

125A

1720W

(5.85 kBTU/hr)

4

9/6300

102A*

45/43.5/42/39/37.5A

125A

1995W

(6.75 kBTU/hr)

* Maximum current rating for the cabinet size. If an additional charger is desired, it must be installed in external battery
cabinet ASY-0739.

Содержание 9170+ ASY-0652

Страница 1: ...Powerware Series Eaton 9170 Battery Charger Module Models ASY 0652 and ASY 0675 User s Guide ...

Страница 2: ...sealed lead acid batteries and must be disposed of properly For more information contact your local recycling reuse or hazardous waste center This symbol indicates that you should not discard waste electrical or electronic equipment WEEE in the trash For proper disposal contact your local recycling reuse or hazardous waste center Eaton and Powerware are registered trademarks of Eaton Corporation o...

Страница 3: ...ng Between Cabinets 6 Setting DIP Switches 6 Output Current Limit 6 Periodic Float Charge 7 Reserved Switch 7 Battery Charger Module Installation 8 3 Operation 9 UPS Cabinet Operation 9 External Battery Cabinet Operation 9 Output Foldback 9 4 Specifications 11 5 Troubleshooting 21 Alarm Messages 21 Audible Alarms and UPS Conditions 21 Battery Charger Module Replacement 22 Service and Support 23 ...

Страница 4: ...TABLE OF CONTENTS Eaton 9170 Battery Charger Module User s Guide S 164201399 Rev E www eaton com powerquality ii ...

Страница 5: ... The Battery Charger Module is capable of providing up to 20 amperes of current for optimum charging based upon the condition and number of batteries in the system Examples of improved system recharge times are shown in Table 1 Note that larger systems require at least one or more Battery Charger Modules to be able to recharge the larger number of battery modules Table 1 Recharge Times Using Batte...

Страница 6: ...module may be installed in either the UPS cabinet 6 9 and 12 slot sizes or a special 12 slot external battery cabinet On Off On DIP Switch Detail Factory default setting 1 2 3 4 Current Limit 1 2 5A Off Off 10A Off Off 15A On On 20A On Figure 1 Battery Charger Module Rear View The external battery cabinet may have input power hardwired through rigid or flexible conduit as shown in Figure 2 or inpu...

Страница 7: ...er Module User s Guide S 164201399 Rev E www eaton com powerquality 3 To UPS or Previous External Battery Cabinet AC Line In To Next External Battery Cabinet DC Disconnect Switch Button Figure 2 External Battery Cabinet for Charger Modules ...

Страница 8: ...INTRODUCTION Eaton 9170 Battery Charger Module User s Guide S 164201399 Rev E www eaton com powerquality 4 ...

Страница 9: ...al external battery cabinets are to be used for Battery Charger Modules install input power wiring to each additional cabinet see Figure 3 Table 2 shows required wire sizes based upon the number of Battery Charger Modules For each 12 slot external battery cabinet stabilizer brackets must be installed If required also install a floor anchor kit as described in the UPS user s guide NOTE The ASY 0739...

Страница 10: ...n Setting DIP Switches The DIP switches on the rear panel of the Battery Charger Module are functional only when the module is installed in an external battery cabinet The DIP switches control two functions the output current limit and a periodic float charging to equalize all battery capacities NOTE Set the DIP switches ONLY if the Battery Charger Module is placed in the ASY 0739 12 slot external...

Страница 11: ... 15A 6 battery strings 21 6 Ah Off On 20A 8 battery strings 28 8 Ah On On NOTE A battery string is made up of two battery modules Factory default setting Off On 1 2 3 4 Figure 4 DIP Switches Periodic Float Charge To enable automatic float or equalize charging of the battery modules every 30 days set DIP switch 3 to ON NOTE Enable only one Battery Charger Module in external battery cabinets Reserve...

Страница 12: ... in place NOTE Place Battery Charger Modules above the battery modules in the UPS cabinet or in any of the top three slots of the ASY 0739 12 slot external battery cabinet 2 Insert the Battery Charger Modules into the cabinet To insert a Battery Charger Module Lower the front slightly and lift the rear edge over the safety stop on the center support rail Keep the module handle extended until the m...

Страница 13: ...ry Charger Module are logged and announced by the UPS system refer to the UPS user s guide Normal output voltage is 133 Vdc External Battery Cabinet Operation When the Battery Charger Module is installed in an external battery cabinet it has no communication path with the UPS power modules Therefore it controls its own operation independent of any system information within the power modules The mo...

Страница 14: ...OPERATION Eaton 9170 Battery Charger Module User s Guide S 164201399 Rev E www eaton com powerquality 10 ...

Страница 15: ... 14 5 14 13 12 5A 25A 285W 0 98 kBTU hr 1 3 2100 30 29 5 29 28 5 28A 15 14 5 14 13 12 5A 40A 570W 1 95 kBTU hr 2 3 2100 46 45 5 45 44 5 44A 15 14 5 14 13 12 5A 60A 860W 2 93 kBTU hr 0 6 4200 28 27 26 25 24A 30 29 28 26 25A 40A 570W 1 95 kBTU hr 1 6 4200 44 43 42 41 40A 30 29 28 26 25A 60A 860W 2 93 kBTU hr 0 9 6300 42 40 5 39 37 5 36A 45 43 5 42 39 37 5A 60A 860W 2 93 kBTU hr Nine and Twelve Slot ...

Страница 16: ...5 93 92 5 92A 15 14 5 14 13 12 5A 125A 1720W 5 85 kBTU hr 0 6 4200 28 27 26 25 24A 30 29 28 26 25A 40A 570W 1 95 kBTU hr 1 6 4200 44 43 42 41 40A 30 29 28 26 25A 60A 860W 2 93 kBTU hr 2 6 4200 60 59 58 57 56A 30 29 28 26 25A 80A 1145W 3 90 kBTU hr 3 6 4200 76 75 74 73 72A 30 29 28 26 25A 100A 1430W 4 88 kBTU hr 4 6 4200 92 91 90 89 88A 30 29 28 26 25A 125A 1720W 5 85 kBTU hr 5 6 4200 102A 30 29 28...

Страница 17: ...0A 80A 1145W 3 90 kBTU hr 1 12 8400 72 70 68 66 64A 60 58 56 52 50A 100A 1430W 4 88 kBTU hr 2 12 8400 88 86 84 82 80A 60 58 56 52 50A 125A 1720W 5 85 kBTU hr 3 12 8400 102 102 100 98 96A 60 58 56 52 50A 125A 1995W 6 75 kBTU hr 0 15 10500 70 67 5 65 62 5 60A 75 72 5 70 65 62 5A 100A 1430W 4 88 kBTU hr 1 15 10500 86 83 5 81 78 5 76A 75 72 5 70 65 62 5A 125A 1720W 5 85 kBTU hr 2 15 10500 102 99 5 97 ...

Страница 18: ...A 285W 0 98 kBTU hr 1 3 2500 32A 15A 14A 12 5A 40A 570W 1 95 kBTU hr 2 3 2500 48A 15A 14A 12 5A 60A 860W 2 93 kBTU hr 0 6 5000 32A 30A 28A 25A 40A 570W 1 95 kBTU hr 1 6 5000 48A 30A 28A 25A 60A 860W 2 93 kBTU hr 0 9 7500 48A 45A 42A 37 5A 60A 860W 2 93 kBTU hr Nine and Twelve Slot Cabinet CAUTION Do NOT install more than seven power and or battery charger modules in a 9 or 12 slot cabinet Optional...

Страница 19: ...A 30A 28A 25A 40A 570W 1 95 kBTU hr 1 6 5000 48A 30A 28A 25A 60A 860W 2 93 kBTU hr 2 6 5000 64A 30A 28A 25A 80A 1145W 3 90 kBTU hr 3 6 5000 80A 30A 28A 25A 100A 1430W 4 88 kBTU hr 4 6 5000 96A 30A 28A 25A 125A 1720W 5 85 kBTU hr 5 6 5000 102A 30A 28A 25A 125A 1995W 6 75 kBTU hr 0 9 7500 48A 45A 42A 37 5A 60A 860W 2 93 kBTU hr 1 9 7500 64A 45A 42A 37 5A 80A 1145W 3 90 kBTU hr 2 9 7500 80A 45A 42A 3...

Страница 20: ...8 15000 96A 90A 84A 75A 125A 1720W 5 85 kBTU hr 1 18 15000 102A 90A 84A 75A 125A 1995W 6 75 kBTU hr Maximum current rating for the cabinet size If an additional charger is desired it must be installed in external battery cabinet ASY 0739 Table 6 Model Specifications for Split Phase Power Modules ASY 0567 Three Slot Cabinet Optional Chargers UPS kVA Watts Input Current 200V Output Current 200V 220V...

Страница 21: ... 44A 45A 42A 37 5A 60A 860W 2 93 kBTU hr Nine and Twelve Slot Cabinet CAUTION Do NOT install more than seven power and or battery charger modules in a 9 or 12 slot cabinet Optional Chargers UPS kVA Watts Input Current 200V Output Current 200V 220V 240V Recommended Input Service Heat Dissipation 0 3 2100 14A 15A 14A 12 5A 25A 285W 0 98 kBTU hr 1 3 2100 30A 15A 14A 12 5A 40A 570W 1 95 kBTU hr 2 3 21...

Страница 22: ...125A 1720W 5 85 kBTU hr 5 6 4200 102A 30A 28A 25A 125A 1995W 6 75 kBTU hr 0 9 6300 42A 45A 42A 37 5A 60A 860W 2 93 kBTU hr 1 9 6300 58A 45A 42A 37 5A 80A 1145W 3 90 kBTU hr 2 9 6300 74A 45A 42A 37 5A 100A 1430W 4 88 kBTU hr 3 9 6300 90A 45A 42A 37 5A 125A 1720W 5 85 kBTU hr 4 9 6300 102A 45A 42A 37 5A 125A 1995W 6 75 kBTU hr 0 12 8400 56A 60A 56A 50A 80A 1145W 3 90 kBTU hr 1 12 8400 72A 60A 56A 50...

Страница 23: ...r battery charger modules in a 9 or 12 slot cabinet Heat Dissipation Recommended Input Service Output Current 200V 220V 240V Input Current 200V UPS kVA Watts Optional Chargers 2 15 10500 102A 75A 70A 62A 125A 1995W 6 75 kBTU hr 0 18 12600 84A 90A 84A 75A 125A 1720W 5 85 kBTU hr 1 18 12600 100A 90A 84A 75A 125A 1995W 6 75 kBTU hr Maximum current rating for the cabinet size If an additional charger ...

Страница 24: ...SPECIFICATIONS Eaton 9170 Battery Charger Module User s Guide S 164201399 Rev E www eaton com powerquality 20 ...

Страница 25: ...ry Charger Module uses an audible alarm feature to alert you of potential power problems When the alarm is activated the Battery Charger Module beeps in different intervals according to a particular condition Use Table 7 to determine and resolve the alarms and conditions Table 7 Battery Charger Module Audible Alarms Audible Alarm Condition Action 1 short 0 5 sec Startup Nothing Module is operating...

Страница 26: ...cabinet 3 Use two hands to support the module When the module is fully extended lower the front slightly and lift the rear edge over the safety stop on the center support rail 4 Treat the original and replacement modules with care to avoid damaging connectors or internal circuitry Label the original module with masking tape or some other identifier Record the serial number of the replacement modul...

Страница 27: ...ative Please have the following information ready when you call the Help Desk S Model number S Serial number S Version number if available S Date of failure or problem S Symptoms of failure or problem S Customer return address and contact information If repair is required you will be given a Returned Material Authorization RMA Number This number must appear on the outside of the package and on the...

Страница 28: ...TROUBLESHOOTING Eaton 9170 Battery Charger Module User s Guide S 164201399 Rev E www eaton com powerquality 24 ...

Страница 29: ......

Страница 30: ......

Страница 31: ......

Страница 32: ... 164201399E 164201399 E ...

Отзывы: