manualshive.com logo in svg
background image

10

Instruction Booklet 

IB0191002EN

Effective November 2019

EAFR-101C arc point sensor relay  

user manual 

  

EATON

 www.eaton.com

7.1.2 Binary output BO1, and BO2

Two binary outputs are available (+ 24 Vdc) .  BO1 is the light signal 

output to connected EAFR-110PLV relays .  This output activates 

when light is received on one of the light sensor inputs .  BO2 is the 

Block Out signal .  This output activates when either of the connected 

circuit breakers opens .  This sends the blocking signal to all other 

connected EAFR-110C relays .  For more information on the blocking 

signal, see Section 7 .2 .2 Circuit breaker binary inputs BI1,BI2, BI3, 

and BI4 .

ote: 

N

The binary output is polarity sensitive (see IB0191003EN) .

7.1.3 System failure (SF) relay

The SF relay is a form C type (NO/NC) and is energized in the 

healthy condition .  Whenever the EAFR-101C detects a system error 

or disconnection of the auxiliary power supply, the contact changes 

its state .  The state of the SF relay remains the same until the EAFR-

101C returns to a healthy condition and SF relay is again energized .

7.2 Inputs

7.2.1 Arc sensor channels S1, S2, S3, and S4

The EAFR-101C has four arc point sensor channels .  A maximum of 

three arc point sensors (type EAFR-01) may be connected to each 

channel .
For details on sensors refer to Section 4: Arc sensors .

7.2.2 Circuit breaker binary inputs BI1, BI2, BI3, and BI4

The EAFR-101C contains six binary inputs .  The inputs are activated 

by connecting a dc signal exceeding the specified nominal threshold 

level of the corresponding input .  The nominal threshold level is  

24 Vdc .  The actual activation of the binary input occurs at 80% of 

the specified nominal threshold value (i .e . 16 Vdc) .
BI1 and BI2 are reserved for the breaker open/close status informa-

tion .  When an air-insulated circuit breaker interrupts a fault, high 

current is present, as is light from the arc chutes on the circuit 

breaker, and the EAFR system may operate as if this event were an 

arc flash .  If the CB has outputs that give indication of an opening 

operation before the primary contacts part, these outputs can be 

connected to BI1 + BI2 or BI3 + BI4 .  If an input is received on 

either of these two input pairs, the EAFR-101C restrains sending 

any light information out on BO1 for 50 ms .  This gives the circuit 

breaker long enough time to clear the fault .  Also at the time of 

input, the EAFR-101C outputs a blocking signal on BO2 to all other 

connected EAFR-101C relays .  This communicates to the other 

relays in the system to also restrain passing light information out 

for 50 ms .  After 50 ms, if any light is still present, the EAFR-101C 

will then give a light out signal on BO1 .  This blocking operation only 

occurs when a connected circuit breaker opens .  A normally open 

(Form a) and normally closed (Form b) output is required from each 

connected circuit .  This is for signal redundancy and error checking .  

If the input is the same on BI1 and BI2, or on BI3 and BI4, the self-

supervision relay is released and the ERROR LED is illuminated .  The 

corresponding LED’s for the circuit breaker input will blink synchro-

nously on the front of the EAFR-101C .  
If a circuit breaker will be taken out of service for an extended 

period, it is advisable that the input for that circuit breaker be 

disabled .  This is done via the dipswitches on the rear of the 

EAFR-101C .  For details on dipswitch settings, refer to Section 3 .5 

Dipswitch settings .

7.2.3 Binary inputs BI5 and BI6

BI5 is the Master Trip/Current input .  If set to Master Trip, upon 

receipt of this input the EAFR-101C will trip without other conditions 

being present .  If set to Current, this input is permissive to tripping if 

any light signal is received on light sensor channels set to Light and 

Current (see section 3 .5 Dipswitch settings) .
BI6 is the Block In input .  If a signal is received on this input, the 

EAFR-101C will restrain any light signal received for 50 ms .  This 

input should be connected to the Block Out BO2 from all other 

connected EAFR-101C relays (refer to IB0191003EN) .

7.3 Auxiliary voltage

The  auxiliary  power  supply  voltage is (110-220) Vac/(125-250) Vdc .  

After powering up the relay, protection is active and operational 

within 50 ms .
An optional 18-72 Vdc power  supply is also available .

Содержание 65C2010G18

Страница 1: ...on 2 2 General 2 3 Operation and configuration 4 4 Arc sensors 7 5 System self supervision 8 6 Application examples 9 7 Connections 9 8 Dimensions and installation 11 9 Testing 12 10 Troubleshooting g...

Страница 2: ...m the point sensor and acting to trip the circuit breaker sourcing the fault current The EAFR 101C complete system self supervision function provides the highest level of dependability by continuously...

Страница 3: ...7 6 13 BI2 X2 12 15 BI1 14 LATCH EN SW6 11 T1 10 LATCH EN SW6 9 T2 8 SF 5 4 3 2 Uaux 1 125 250 Vdc 24 Vdc 24 Vdc 110 220 Vac dc 24 Vdc 12 Vdc 12 Vdc 5 Vdc uP 12 BI4 11 15 BI3 14 10 BI5 9 8 BI6 7 6 BO1...

Страница 4: ...al Verify system condition See Sections 11 Troubleshooting guide and 5 System self supervision T1 and T3 Red Normal status Trip relays T1 and T3 activated N A Check the reason for trip Clear the fault...

Страница 5: ...indications and latched trip relays are reset by pressing the SET button for one second Otherwise the latched trip relays will remain activated until auxiliary power is disconnected All LED indi cati...

Страница 6: ...channel S3 S4 trip criteria Trip on light only L Trip on light and over current L C Both signals are required simultaneously to trip 6 Latch or non latch for trip relays T1 and T2 T1 and T2 operate as...

Страница 7: ...rees Other point sensors are available with different Lux sensitivities EAFR 01 B at 25 000 Lux and EAFR 01 C at 50 000 Lux Figure 4 EAFR 01 arc light point sensor 4 1 1 EAFR 01 installation and wirin...

Страница 8: ...ealthy condition the POWER LED is on and the System Failure SF relay is energized If the self supervision function detects a faulty condition or the power supply fails the self supervision relay is re...

Страница 9: ...ow voltage switchgear 7 Connections Figure 6 EAFR 101C terminals at the rear plate 7 1 Outputs 7 1 1Trip relaysT1 T2 andT3 The EAFR 101C relay has integrated trip relays T1 and T2 for tripping of the...

Страница 10: ...opening operation before the primary contacts part these outputs can be connected to BI1 BI2 or BI3 BI4 If an input is received on either of these two input pairs the EAFR 101C restrains sending any l...

Страница 11: ...ser manual EATON www eaton com 8 Dimensions and installation The EAFR 101C is either door mounted or panel mounted in stan dard 19 in 482 6 mm rack height of 4U and 1 8 of a unit wide Figure 7 EAFR 10...

Страница 12: ...al is utilized verify the BO1 signal activation by the status change of the relevant input where the binary output signal is connected or by measur ing the signal output voltage ote N The BO1 signal i...

Страница 13: ...ns Light only Light current Remarks Sensor channels 1 and 2 setting Sensor channels 3 and 4 setting Object activated LED indication T1 T2 and T3 active BO1 active BO2 active Sensor channel 1 Sensor 1...

Страница 14: ...y for 0 5 s 30 A Make and carry for 3 s 16 A Breaking capacity DC when time constant L R 40 ms 40 W 0 36 A at 110 Vdc Contact material AgNi 90 10 11 4 Binary output BO1 and BO2 Rated voltage 24 Vdc Ra...

Страница 15: ...ulse test voltage Acc to IEC 60255 5 5 kV 1 2 50 us 0 5 J 11 8 Mechanical tests Vibration test 10 to 150 Hz 0 07 mm 003 in 0 5 gn 60 to 150 Hz 10 to 150 Hz 1 gn 10 to 150 Hz Shock bump test acc to IEC...

Страница 16: ...fiber sensor 30 m 93 43 ft EAFR 06 35 65C2013G06 Arc light plastic fiber sensor 35 m 114 83 ft EAFR 06 40 65C2013G07 Arc light plastic fiber sensor 40 m 131 23 ft EAFR 07 10 65C2014G01 Arc light glass...

Страница 17: ...17 Instruction Booklet IB0191002EN Effective November 2019 EAFR 101C arc point sensor relay user manual EATON www eaton com Notes...

Страница 18: ...t between Eaton and the purchaser THERE ARE NO UNDERSTANDINGS AGREEMENTS WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SP...

Отзывы: