9. Testing
It is recommended that the EAFR-110PLV arc protection relay is
tested prior to the equipment being energized. Testing is carried out
by simulating arc light to each sensor and verifying the tripping and
LED indication. For the arc light simulation, use a superior camera
flash type: Canon Speedlite® 430EX or equivalent. For testing of
non-latched signals and CBFP function, use a Mini Maglite® 2 Cell
AAA or equivalent type of flashlight. Check that camera flash or
flashlight has fully charged battery(ies) when testing.
9.1 Carrying out testing in the light only mode
1. Check that the dipswitch setting positions are in accordance to
your application.
2. Activate the camera flash within 20 cm (8 in.) of the EAFR-01
sensor in use.
3. Verify that the corresponding sensor channel indication LED
status is changed to ON.
4. Verify the relay output(s) activation(s) by checking the circuit
breaker status or by monitoring the trip contact status. The
circuit breaker should open or contacts operate.
ote:
N
A best practice is to operate the circuit breaker during testing.
5. Verify that the corresponding relay output(s) LED(s) indication
status is changed to ON.
6. If the binary output (BO1) or high speed output (HSO) signal
is utilized, verify the BO1 or HSO signal activation by status
change of relevant input where the output signal is connected
or by measuring the signal output voltage. Note that the BO1
signal is a non-latched type.
7. If the BO1 or HSO signal is utilized, verify that the BO1 LED or
relevant HSO LED is illuminated.
8. Press the SET push-button to reset all indications and latches.
9. If a binary input (BI2) is utilized as master trip to activate the
corresponding binary input, verify that the trip has occurred by
repeating Steps 4 and 5.
10. Press the SET push-button to reset all indications and latches.
11. Repeat the testing procedure for all sensors.
51 (2.01)
159 (6.26)
168 (6.61)
84 (3.31)
16.5 (0.65)
M4