background image

Page 18

614-07977-00_EN

5. Maintenance

5.1 Troubleshooting

Operation status 

Possible cause

Action

Batteries disconnected

The UPS does not recognise  

the internal batteries

If the condition persists, contact 

your service representative

The batteries are disconnected

Verify that all batteries are properly 

connected. If the condition persists, 

contact your service representative.

Overload

Power requirements exceeds the 

UPS capacity (greater than 105 %  

of nominal)

Remove some of the equipment 

from the UPS. The UPS continues  

to operate, but may shutdown if the 

load increases. The alarm resets 

when the condition becomes  

inactive.

End of battery life 

The end of the battery life is 

reached.

Contact your service representative 

for battery replacement.

Event 

An UPS event occurs

Example: 

Remote Power OFF, the RPO  

contact has been activated to  

shutdown the UPS and now  

prevents restart.

Set the contact back to its normal 

position and press   button  

to restart.

UPS fault

An internal failure occured with the 

UPS

The UPS does not protect the  

equipment anymore. 

Note.

 the alarm message and  

the UPS Serial Number, then contact 

your service representative.

Troubleshooting a UPS equipped with the HotSwap MBP module

Indication

Diagnostic

Correction

1

The load is no longer supplied 

when the rotary switch 

(55)

 on 

the 

HotSwap MBP

 module is 

set to Bypass position.

l  

The protected devices 

are connected to the UPS 

output instead of to the 

HotSwap MBP 

module.

l  

The AC-power cord is  

connected to the UPS input 

instead of to the 

HotSwap 

MBP

 module.

Check the wiring between  

the UPS and the 

HotSwap MBP 

module (see section 3.6).

2

The load is no longer supplied 

when the rotary switch 

(55)

 on 

the 

HotSwap MBP 

module is 

set to Normal position.

The UPS is shut down.

l  

The wiring between the 

UPS and the 

HotSwap MBP

 

module is incorrect.

Start the UPS.

l  

Check the wiring between 

the UPS and the 

HotSwap 

MBP 

module  

(see section 3.6).

3

The load is no longer supplied 

after AC-power fails.

l  

The rotary switch 

(55)

 on 

the 

HotSwap MBP

 module 

is set to Bypass position.

l  

The wiring between the 

UPS and the 

HotSwap MBP

 

module is incorrect.

l  

Set the rotary switch 

(55)

 

on the 

HotSwap MBP

  

module to Normal position.

l  

Check the wiring between 

the UPS and the 

HotSwap 

MBP

 module  

(see section 3.6).

Содержание 5PX 1500i RT2U

Страница 1: ...PX 2200i RT2U 5PX 3000i RT2U 5PX 3000i RT3U 5PX EBM 48V RT2U 5PX EBM 72V RT2U 5PX EBM 72V RT3U Installation and user manual Copyright 2010 EATON All rights reserved Service and support Call your local...

Страница 2: ...waste center This symbol indicates that you should not discard waste electrical or electronic equipment WEEE in the trash For proper disposal contact your local recycling reuse or hazardous waste cen...

Страница 3: ...onnection with a FlexPDU Power Distribution Unit module optional 14 3 6 Connection with a HotSwap MBP module optional 14 3 7 UPS connection without a FlexPDU or HotSwap MBP module 15 4 Operation 16 4...

Страница 4: ...recycled cardboard p p Sacks and bags are made of polyethylene p p Packing materials are recyclable and bear the appropriate identification symbol p p 01 PET Materials Abbreviations Number in the sym...

Страница 5: ...1 2 x 86 2 20 6 x 17 4 x 3 4 5PX 2000i RT2U 28 50 62 80 5PX 2200i RT2U 28 50 62 80 5PX 3000i RT2U 38 08 84 00 647 x 441 2 x 86 2 25 5 x 17 4 x 3 4 5PX 3000i RT3U 37 33 82 30 497 x 441 2 x 130 7 19 6 x...

Страница 6: ...al battery modules 7 16 A outlet for connection of equipment Primary group 8 Two groups of 2 programmable outlets for connection of equipment Group 1 and 2 9 Groups of 4 outlets for connection of equi...

Страница 7: ...yellow Alarm Indicator red Normal mode 100 17min 1EBM 100 2 7kW 3kVA Efficiency 98 Escape Up Down Enter On Off button The following table shows the indicator status and description Indicator Status D...

Страница 8: ...essed Normal mode The UPS is operating normally The UPS is powering and protecting the equipment In AVR mode Load protected LED is ON No beep The UPS is operating normally but the utility voltage is o...

Страница 9: ...address 2 6 User settings The following table displays the options that can be changed by the user Description Available settings Default settings Local settings Language English Fran ais Deutsch Ital...

Страница 10: ...detected on the output Disable Sleep mode Disable Enable If disable LCD and communication will turn OFF immediately after UPS is OFF If enable LCD and communication stays ON 1h30 min after UPS is OFF...

Страница 11: ...Safety instructions 39 Quick start 40 Mounting kit for 19 inch enclosures Elements supplied depending on the version or optional 41 2 supports for tower position RT 2U version only 42 FlexPDU module...

Страница 12: ...in tower position Note The two supports for the tower position are used on the RT 2U version only 3 3 Installation in rack position Follow steps 1 to 4 for module mounting on the rails 1 1 3 4 4 3 2...

Страница 13: ...tion cards optional standard on the Netpack versions It is not necessary to shutdown the UPS before installing a communication card 1 Remove the slot cover 4 secured by screws 2 Insert the communicati...

Страница 14: ...with a HotSwap MBP module optional The HotSwap MBP module makes it possible to service or even replace the UPS without affecting the connected loads HotSwap function 5PX HotSwap MBP 46 51 52 55 54 53...

Страница 15: ...ce and the true electrical consumption of the total load 10 32 35 9 7 31 8 1 5PX 1500i 2000i connect the UPS input socket 10 to the AC power source using the cable of the protected equipment 5PX 2200i...

Страница 16: ...Cold start setting in ON OFF Settings on page 10 To start the UPS on battery 1 Press the button on the UPS front panel until the UPS front panel display illuminates and shows a status of UPS starting...

Страница 17: ...shut down the UPS These functions are obtained by opening a contact connected between the appropriate pins of connector 5 on the rear panel of the UPS see figures below 5 Remote control connection and...

Страница 18: ...the equipment anymore Note the alarm message and the UPS Serial Number then contact your service representative Troubleshooting a UPS equipped with the HotSwap MBP module Indication Diagnostic Correct...

Страница 19: ...elets and all other metal objects from the hands and arms p p use tools with an insulated handle p p Battery tray removal E D C A B A Remove the middle part B Remove the left hand side of the front pa...

Страница 20: ...o Bypass position The red LED on the HotSwap MBP module goes ON indicating that the load is supplied directly with AC input source power 2 Stop the UPS by pressing the button on the UPS control panel...

Страница 21: ...mperature range l Storage temperature range l Relative humidity l Noise level 0 to 40 C 15 to 50 C 20 to 90 without condensation 45 dBA 50 dBA 1 The high and low thresholds can be adjusted using UPS s...

Страница 22: ...connected to the UPS output Low battery warning This is a battery voltage level indicating that battery power is low and that the user must take action in light of the imminent break in the supply of...

Отзывы: