Instruction Book    

IB182217EN   October 2018   www.eaton.com

50 / 75 / 150 DHP [Cable or Hard Bus Application]

Ground and Test Device

SECTION 6:  INSPECTION AND 
MAINTENANCE

6.1 INTRODUCTION

m

 WARNING

DO NOT WORK ON A GROUND AND TEST DEVICE IN THE “CONNECTED” 

POSITION.

DO NOT DEFEAT ANY SAFETY INTERLOCKS.

FAILURE TO FOLLOW ANY OF THESE INSTRUCTIONS MAY CAUSE DEATH, 

SERIOUS BODILY INJURY, OR PROPERTY DAMAGE. SEE SECTION 2 - 

SAFE PRACTICES FOR MORE INFORMATION.

6.2 FREQUENCY OF 

INSPECTION

6.2 FREQUENCY OF INSPECTION

Inspect the ground and test device at least once a year or before 

each use, especially in a severe service condition.

6.3 INSPECTION AND MAINTENANCE PROCEDURES

Insulation

Visually inspect all insulating barriers. Ensure that there is not 

dirt visible on the surface of any of the barriers. If dirt is found, 

clean with a lint-free cloth. If a solvent is required to cut dirt, used 

Stoddard’s Solvent (Eaton part number 55812CA) or commercial 

equivalent.

Hardware

Visually inspect all hardware. Replace any damaged or missing 

hardware with parts equivalent to those provided with the ground 

and test device.

Power Frequency Withstand Test

Individually energize each terminal (without cables, but with 

insulating barriers) with the frame and device ground connection 

system and all other terminals grounded. See Section 6-4 for 

procedure.

6.4 INSULATION INTEGRITY CHECK

A sinusoidal AC voltage shall have a crest value of no less than 1.414 

times the rated power frequency withstand voltage value specified, 

and shall be applied to each terminal as specified in Section 6.3. The 

frequency shall be /- 20% of the rated power frequency. For 

5kV, the test voltage shall be gradually increased from zero to 15 kV 

rms and held for 1 minute without flashover. For 7.5kV and 15kV, the 

test voltage shall be gradually increased from zero to 27kV rms and 

held for 1 minute without flashover.

Содержание 50 DHP

Страница 1: ...182217EN 50 75 150 DHP Cable or Hard Bus Application Ground and Test Device Supersedes May 2016 Effective October 2018 150 DHP Ground and Test Device Hard Bus Type Device 150 DHP Ground and Test Devic...

Страница 2: ...es office should be consulted Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between...

Страница 3: ...PLATES 17 4 6 CELL POSITION DESCRIPTION 17 4 7 INSTALLATION OF GROUNDING BUS BARS 18 4 8 DEVICE AMPERAGE CONVERSION PROCEDURE 18 4 9 UNIVERSAL 1200A 2000A G T CONFIGURATION OPTIONAL 19 4 7 1 Changing...

Страница 4: ...ng out tests m CAUTION BECAUSE OF THE UNIQUE APPLICATION AND VAST VARIETY OF SYSTEM USER REQUIREMENTS SPECIFIC SAFE OPERATING PROCEDURES FOR THE USE OF THIS DEVICE MUST BE DEVELOPED BY THE USER m WARN...

Страница 5: ...aker Rated Continuous Current at 60 Hz Amps A B C D E F G H 50DHP 250 Dual 1200 2000 20 50 7 00 36 13 2 94 15 12 6 81 16 50 8 50 50DHP 350 Dual a 1200 2000 20 30 7 00 36 73 2 94 15 12 11 24 16 50 8 50...

Страница 6: ...Bus Application Ground and Test Device Table 4 DHP Ground and Test Device Dimensions Hard Bus Application Design Breaker Type Existing Breaker Rated Continuous Current at 60 Hz Amps A B C D E F G H 50...

Страница 7: ...us Application Ground and Test Device Table 5 DHP Ground and Test Device Dimensions Hard Bus Application Design Breaker Type Existing Breaker Rated Continuous Current at 60 Hz Amps A B C D E F G H 150...

Страница 8: ...st device from the enclosure before performing any maintenance Failure to do so could result in electrical shock leading to death severe personnel injury or property damage Do not leave the ground and...

Страница 9: ...the original DHP air circuit breakers Use the racking handle originally provided to engage the racking shaft of the G T racking mechanism to move the device into and out of the circuit breaker compar...

Страница 10: ...evice while lifting and moving Figure 3 2 a Front External View of 50DHP G T Device Figure 3 2 b Front External View of 150DHP G T Device 3 3 STORAGE If the ground and test device is to be placed in s...

Страница 11: ...ton com 50 75 150 DHP Cable or Hard Bus Application Ground and Test Device Front External View 50DHP G T Shown 1 Kirk Key Interlocks 3 Ground Bus 5 Rail Latch 2 Door Latch 4 Levering Shaft Figure 3 3...

Страница 12: ...150 DHP Cable or Hard Bus Application Ground and Test Device Figure 3 3 b Rear External View of DHP G T Device 1 1 2 6 5 4 3 Front External View 50DHP G T Shown 1 Primary Disconnects 3 Snubber Bolt 5...

Страница 13: ...50 75 150 DHP Cable or Hard Bus Application Ground and Test Device 1 5 4 2 3 Figure 3 3 c Front External View of 50DHP 350 G T 3000A Device Front External View 150DHP G T Shown 1 Lifting Points 3 Grou...

Страница 14: ...75 150 DHP Cable or Hard Bus Application Ground and Test Device 1 1 2 5 4 3 Figure 3 3 d Rear External View of 50DHP 350 G T 3000A Device Back External View 150DHP G T Shown 1 Primary Disconnects 3 Sn...

Страница 15: ...ation Ground and Test Device Figure 3 3 e Front External View of 150DHP GT 500 1200A 2000A Device Front External View 1 Padlock Provision 3 Lifting Points 5 Levering Shaft 2 G T Storage Compartment 4...

Страница 16: ...75 150 DHP Cable or Hard Bus Application Ground and Test Device Figure 3 3 f Rear External View of 150DHP GT 500 1200A 2000A Device Back External View 1 Primary Disconnect 3 Grounding Contact 5 Ground...

Страница 17: ...ate door and turn the key This will lock the door and the key will now be able to be removed and inserted into the other lock This feature is not applicable for single terminal ground and test m NOTIC...

Страница 18: ...nd and test device consists of cycloaliphatic bushings with silver plated copper conductor knobs Primary disconnecting contacts are attached to the knobs these primary disconnects are configured to en...

Страница 19: ...tab ampere rating prior to inserting the G T device If the incorrect finger cluster is mounted on the G T device remove it and install the proper finger cluster 4 7 1 Changing 1200A Finger Clusters to...

Страница 20: ...re 4 14 Figure 4 11 Finger Cluster Hardware Figure 4 13 Fitting 2000A Universal G T Finger Cluster Figure 4 14 2000A Universal G T Finger Cluster Removal Figure 4 12 Finger Cluster Hardware Thread the...

Страница 21: ...THE SURFACE OF THE INSULATION OR WITHIN THE CELL BOTTLES FAILURE TO HEAD THIS WARNING CAN CAUSE DEATH SERIOUS PERSONNEL INJURY AND OR PROPERTY DAMAGE Orient the finger cluster with the stainless stee...

Страница 22: ...in line with the location of the snubber bolts on each side of the ground and test device Figure 5 1 Step 2 Adjust the height of the top of the snubber bolt to be between 0 0 and 0 031 0 0 and 1 32 in...

Страница 23: ...sh Continue cranking until the crank turns freely and the G T device stops moving The G T device should now be in the OPERATING or ENGAGED position 5 5 REMOVAL PROCEDURE To remove the G T device from...

Страница 24: ...If a solvent is required to cut dirt used Stoddard s Solvent Eaton part number 55812CA or commercial equivalent Hardware Visually inspect all hardware Replace any damaged or missing hardware with par...

Страница 25: ...to customer depending upon the service severity and continuity requirements Each customer should develop his own level based on operating experience 7 1 1 ORDERING INSTRUCTIONS 1 Always specify the gr...

Страница 26: ...evard Cleveland OH 44122 United States Eaton com 2018 Eaton All Rights Reserved Printed in USA Publication No IB182217EN October 2018 Eaton is a registered trademark All trademarks are property of the...

Отзывы: