21
Instruction Book
IB182217EN October 2018 www.eaton.com
50 / 75 / 150 DHP [Cable or Hard Bus Application]
Ground and Test Device
Figure 4.15. Waxing 1200A DHP Finger Cluster
Figure 4.16. 1200A DHP Finger Cluster Orientation
m
WARNING
DO NOT USE GREASE OF ANY KIND. GREASING OF THE FINGER CLUSTERS
OR PRIMARY CONDUCTORS WILL VOID THE WARRANTY AND OVER TIME
CAN CAUSE A BUILDUP OF CONTAMINANTS THAT CAUSE TRACKING
OVER THE SURFACE OF THE INSULATION OR WITHIN THE CELL BOTTLES.
FAILURE TO HEAD THIS WARNING CAN CAUSE DEATH, SERIOUS
PERSONNEL INJURY, AND / OR PROPERTY DAMAGE.
•
Orient the finger cluster with the stainless steel retaining ring and
spring marking as shown (Figure 4.7).
•
Place the large retaining washer inside the finger cluster cavity.
•
Push the 1200A finger cluster onto the primary conductor stem.
•
Thread the shorter hex head bolt and lock washer into the primary
conductor stem and tighten until the flat washer is collapsed. Do
not over tighten.
•
Repeat the process until all finger clusters are changed to the
proper rating.