Operating instructions

Loadmake operation

• 

Area must be clear of obstructions or contaminations 

that would interfere with the operation of the loadbreak 

elbow.

• 

Securely fasten a clampstick to the pulling eye of the 

elbow.

• 

Place the loadbreak elbow over the bushing, inserting 

the white arc follower of the probe into the bushing 

approximately 2” until a slight resistance is felt. This will 

align and stabilize the elbow.

• 

Turn your back to the bushing and grasp the clampstick 

securely and obtain good footing. Slam the elbow onto 

the bushing with one quick and continuous motion.

• 

Turn around and apply a force to the clampstick to push 

the elbow onto the bushing. A popping or snapping 

sound is often heard when this operation is performed.

• 

To check that the elbow is properly latched apply a gentle 

pull force to the clampstick. When latched properly the 

elbow will not slide back off of the bushing.

• 

As a last operation, push on the clampstick to seat the 

elbow all the way onto the bushing again. This insures 

that the elbow is latched and was not dislodged during 

the latching check in previous step above.

Loadbreak operation

• 

Area must be clear of obstructions or contaminants that 

would interfere with this operation.

• 

Use clampstick to secure standoff insulator or portable 

feedthru in bracket. Ground devices to system ground 

per appropriate Installation Instructions. All associated 

apparatus must also be grounded.

• 

Secure elbow eye firmly onto clampstick and lock.

• 

Twist clampstick clockwise until the elbow rotates slightly 

on bushing–about 1/4” (7 mm). This action will break any 

surface friction between outer surface of bushing and 

inner surface of elbow.

• 

Withdraw elbow from bushing with a fast, firm, straight 

motion. Minimum amount of travel of elbow to break load 

is 9” (229 mm).

• 

Use clampstick to place elbow on lubricated standoff 

insulator or portable feedthru. (Follow loadmake 

instructions.)

• 

Place an insulated protective cap with ground wire 

attached to system ground on any exposed energized 

bushing using clampstick. Follow the same operating 

procedures as for the elbow as outlined above under 

Loadmake Operation.

 CAUTION 

The operator should always use personal protective 

equipment (insulated gloves, clampstick and eye 

protection) whenever operating the elbow. The operator 

should always be in the best possible operating 

position, providing firm footing and enabling a secure 

grasp of the clampstick, while maintaining positive 

control of the elbow before, during and immediately 

after operation. If there is any question regarding the 

operator’s operating position, de-energize the elbow 

before operation. The operator should not be looking 

directly at the connector during the moment of circuit 

interruption or connection.

5

200 A 35 KV CLASS “LE” SERIES ELBOW INSTALLATION INSTRUCTIONS

   MN650010EN   May 2015   

Содержание 200 A 25 kV class

Страница 1: ...200 A 35 kV class LE series elbow installation instructions COOPER POWER SERIES Loadbreak Apparatus Connectors MN650010EN Effective May 2015 Supersedes S500 41 1 March 2011...

Страница 2: ...NY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES In no...

Страница 3: ...dling and Storage 1 Quality Standards 1 INSTALLATION INSTRUCTIONS Installation Instructions 2 Preparation of Concentric Neutral Cable 3 Elbow and Loadbreak Probe Installation 4 OPERATING PROCEDURES Lo...

Страница 4: ...afety information DANGER Hazardous voltage Contact with hazardous voltage will cause death or severe personal injury Follow all locally approved safety procedures when working around high and low volt...

Страница 5: ...IONAL LOCKING RING THREE PHASE PROBE INSULATED CUFF ARC FOLLOWER PULLING EYE TEST POINT CAP DRAIN WIRE TAB LOADBREAK BAND PEROXIDE CURED SEMI CONDUCTING SHIELD INSULATION ENCAPSULATED CONDUCTIVE INSER...

Страница 6: ...Cable Cutters Clampstick Personal Protection Equipment For detailed instructions please see pages 3 4 Table 1 Crimp Chart Connector Size AWG or kcmil Catalog Number Nominal Barrel Diameter Burndy Kear...

Страница 7: ...the compression connector prior to crimping to ensure proper thread engagement Place the coppertop bimetal connector on the conductor Make sure the threaded hole in connector faces the apparatus bush...

Страница 8: ...elbow Step 7 By hand thread loadbreak probe into threaded eye of coppertop connector When tight use the provided installation tool to properly torque the loadbreak probe Proper torque is applied when...

Страница 9: ...vices to system ground per appropriate Installation Instructions All associated apparatus must also be grounded Secure elbow eye firmly onto clampstick and lock Twist clampstick clockwise until the el...

Страница 10: ...This page intentionally left blank 6 200 A 35 KV CLASS LE SERIES ELBOW INSTALLATION INSTRUCTIONS MN650010EN May 2015...

Страница 11: ...This page intentionally left blank 7 200 A 35 KV CLASS LE SERIES ELBOW INSTALLATION INSTRUCTIONS MN650010EN May 2015...

Страница 12: ...wer and Kearney are valuable trademarks of Eaton in the U S and other countries You are not permitted to use the trademarks without the prior written consent of Eaton Burndy is a registered trademark...

Отзывы: