Refer to Tables 3-3 to 3-5 and the appropriate Power Xpert 9395, 9395P, or 9395C UPS Installation and
Operation manual for external wiring requirements, including the minimum AWG size of external wiring, The
power wiring connections for this equipment are rated at 90°C. If wire is run in an ambient temperature greater
than 30°C, higher temperature wire and/or larger size wire may be necessary.
Table 3-3. External Power Wiring Requirements for Power Xpert 9395 Model 1085/1085HR Battery Cabinet to UPS or to Common Disconnect
UPS Model
Power Xpert 9395
kVA/kW
Minimum
Number of
Cabinets
per UPS
Battery
Terminal
Minimum
Conductor Size
(AWG) 90° C Copper
Number
per Pole
Wires/Conduit
Conduit (EMT)
Trade Size
275/225
1
(
+
) (–)
500
1
2+GND
2.5
275/250
2
(
+
) (–)
500
1
2+GND
2.5
275/275
2
(
+
) (–)
500
1
2+GND
2.5
300/300
3
(
+
) (–)
500
1
2+GND
2.5
550/400
3
(
+
) (–)
500
1
2+GND
2.5
550/450
3
(
+
) (–)
500
1
2+GND
2.5
550/500
4
(
+
) (–)
500
1
2+GND
2.5
550/550
4
(
+
) (–)
500
1
2+GND
2.5
825/600
5
(
+
) (–)
500
1
2+GND
2.5
825/650
5
(
+
) (–)
500
1
2+GND
2.5
825/750
6
(
+
) (–)
500
1
2+GND
2.5
825/825
6
(
+
) (–)
500
1
2+GND
2.5
1100/900
7
(
+
) (–)
500
1
2+GND
2.5
1100/1000
7
(
+
) (–)
500
1
2+GND
2.5
1100/1100
7
(
+
) (–)
500
1
2+GND
2.5
All
All
Ground
3
1
2+GND
2.5
NOTE
This table is not to be used for wire sizing from common disconnect to UPS. For that refer to the UPS manual.
Table 3-4. External Power Wiring Requirements for Power Xpert 9395P Model 1085/1085HR Battery Cabinet to UPS or to Common
Disconnect
UPS Model
Power Xpert 9395P
kVA/kW
Minimum
Number of
Cabinets
per UPS
Battery
Terminal
Minimum
Conductor Size
(AWG) 90° C Copper
Number
per Pole
Wires/Conduit
Conduit (EMT)
Trade Size
300/200
1
(
+
) (–)
500
1
2+GND
2.5
300/225
1
(
+
) (–)
500
1
2+GND
2.5
300/250
2
(
+
) (–)
500
1
2+GND
2.5
300/275
2
(
+
) (–)
500
1
2+GND
2.5
300/300
3
(
+
) (–)
500
1
2+GND
2.5
600/400
3
(
+
) (–)
500
1
2+GND
2.5
600/450
3
(
+
) (–)
500
1
2+GND
2.5
600/500
4
(
+
) (–)
500
1
2+GND
2.5
600/550
4
(
+
) (–)
500
1
2+GND
2.5
600/600
5
(
+
) (–)
500
1
2+GND
2.5
900/675
5
(
+
) (–)
500
1
2+GND
2.5
900/750
6
(
+
) (–)
500
1
2+GND
2.5
900/825
6
(
+
) (–)
500
1
2+GND
2.5