![Eaton-Williams ICUS30 Скачать руководство пользователя страница 12](http://html1.mh-extra.com/html/eaton-williams/icus30/icus30_installation-manual_3687125012.webp)
ICUS CONDENSING UNIT INSTALLATION MANUAL
Jan 09:F\Qualitair Eng\Icu\Manuals\0412118S
12
Fitting
Pipe Size
3/8”
½”
5/8”
¾”
45° Bend
0.12
0.15
0.18
0.21
90° Bend Short Radius
0.37
0.43
0.49
0.55
90° Bend Long Radius
0.24
0.27
0.30
0.37
180° Bend Short Radius
0.73
0.91
1.10
1.28
180° Bend Long Radius
0.46
0.55
0.64
0.76
90° Elbow
0.67
0.85
1.04
1.25