EasyIO SH-TSX Скачать руководство пользователя страница 8

 

 

SH-TSX Product Manual - © EasyIO / www.easyio.eu

 

Typical Thermostat Home Screens 

 
The images below illustrate the typical home screens on the thermostats. The screen is touch 
sensitive and shows the current status of the thermostat. Inside the red/blue/white ring the thermostat 
shows the current target temperature. The intensity of the red/blue ring changes based on the 
temperature differing from the target temperature. 
 
The colour of the blue red/blue ring can be set over the network. As default the ring’s intensity 
changes based on the target value differing from the sensor 3 (built-in sensor) measurement. 

 

The small action circle indicates the current measurements / network values in rotation. 

 

 

 

 

Touchscreen 

 
The room thermostat home screen has four touch sensitive areas that allow the thermostat settings to 
be 

altered. All parameter values are available as Modbus/BACnet network variables. 

 

  UP and DOWN arrows; to alter the current target (temperature / % value). 

 

  SMALL ACTION CIRCLE (that contains current main zone temperature etc.); allows access to 

FURTHER SETTINGS AND INFORMATION screen. 

 

  FUNCTION BASED ICON; in PARTY mode shows the PARTY icon; in OFF mode shows the 

OFF icon. Pressing the icon the mode can be cancelled. 

 

  FAN SPEED ICON; when FAN display is enabled, the fan ICON can be used to control the fan 

speed (up to 7 steps, AUTO-0-1-2-3-4-5-6) 

 

  ECO ICON; when set the ECO mode icon is displayed below the fan speed 

 

  A/C ICON; when AC is enabled the AC can be enabled/disabled from this icon 

 

  LIGHTS ICON; when LIGHTS are enabled, the lights can be enabled/disabled from this icon 

 

SCREEN

LOCKED

CLEANING 

MODE

COMMS 

MESSAGE

RED 

RING

LIGHTS 

ON
AIR/CON 

ON

SH-TS WITH RED DISPLAY

ICON 

DESCRIPTION

BLUE

RING

OFF

MODE

ERROR

21

.5

°C

Room

20

TARGET IN PERCENTAGE, WHITE 

.1

°C

Zone 2

20

.8

°C

Zone 3

10

.5

°C

TRANSITIONS BETWEEN

ROOM - ZONE2  - ZONE3 - 

RH IF FITTED / ENABLED

IN AUTO MODE INTENSITY 

OF THE RED AND BLUE  

CHANGES DEPENDING 

ON DIFFERENCE 

BETWEEN TARGET AND 

ZONE1 MEASUREMENT

STATUS INFORMATION 

BANNER

21

.5

°C

Room

23

.8

°C

WHITE

RING

A/C AND LIGHTS STATUS 

AND SWITCH ON/OFF

THE SMALL INFO CIRCLE ACTS 

ALSO AS AN ACTION AREA FOR 

FURTHER SETTINGS

Humidity

45

%

MAINTENANCE 

MODE
PARTY

MODE
ECO 

MODE
FROST 

ICON

FUNCTION BASED ICON 

AREA (PARTY MODE / 

ON-OFF/ECO ICON) 

PRESS UP AND 

DOWN ARROWS 

TO ADJUST 

TARGET VALUE 

SMALL ACTION CIRCLE

50

.0

%

Room

20

.1

°C

SH-TS WITH ON/BLUE DISPLAY

SH-TS WITH FAN SPEED

21

.5

°C

Room

20

.1

°C

A

CONTROL MODE ( AUTO/HEATING 

/ COOLING / FAN VENTILATION

FAN

Содержание SH-TSX

Страница 1: ...SH TSX Product Manual EasyIO www easyio eu 1 Touchscreen Modbus BACnet thermostat with Fan speed control product manual v2 2 SH TSX...

Страница 2: ...110 and BI4 these show if the fan speed has been set to Manual or Auto by user firmware version 3 06 4th Jul 2019 V2 2 Added Setpoint Mode None where no Setpoint is displayed System Setting Screen Ref...

Страница 3: ...formation 10 Fan Speed Display and Manual Override 11 Operating Mode Icon 13 ECO Mode Icon 13 OFF Mode Icon 14 Night Mode Digital Input Override 15 Party Mode Boost 15 Frost Icon 16 Cleaning Mode 16 A...

Страница 4: ...Manual EasyIO www easyio eu 4 Parameter Storage 23 Modbus Registers 23 BACnet Interoperability Building Blocks Supported Annex K 27 BACnet Standard Object Types Supported 28 Device Object Properties 2...

Страница 5: ...conditioning interface for system network devices Features 24VAC DC Power Supply 3 5 Inch Backlit Touchscreen Display BACnet and Modbus Communication Models Fan speed control and display Operating mo...

Страница 6: ...nication BACnet MS TP RS485 maximum 63 devices 0 127 via Touchscreen Default 651000 MAC Address Adjustable 9k6 19k2 38k4 57k6 76k8 Baud Parity None Even Odd 1 or 2 Stop Bits adjustable through Touchsc...

Страница 7: ...0VDC 7A Relay Contact 24V 24Vac dc Supply 0V 0V Supply RI1 Remote NTC10 Temperature Sensor Input 1 RI2 Remote NTC10 Temperature Sensor Input 2 DI1 Volt Free Digital Input Contact A Modbus BACnet MS TP...

Страница 8: ...the PARTY icon in OFF mode shows the OFF icon Pressing the icon the mode can be cancelled FAN SPEED ICON when FAN display is enabled the fan ICON can be used to control the fan speed up to 7 steps AUT...

Страница 9: ...ture or temperature can be set over the network if Sensor2 Source has been set to network The description for the temperature can be changed via Sensor2 Text parameter in the configuration pages By se...

Страница 10: ...the screen This option is particularly useful in hospitality applications where the client base is expected to be international Further Settings and Information The FURTHER SETTINGS shows additional u...

Страница 11: ...A next to the line bar if Auto option selected When the device is manually overridden then the A symbol changes to M indicating manual operation only if Auto option has been selected for Manual Contr...

Страница 12: ...over the network 6 STEP AUTO fan speed rotates between OFF M 1 2 3 4 5 6 segments M and Auto A When auto is selected the display returns to show the speed set over the network ADVANCED advanced fan s...

Страница 13: ...een Auto Heating Cooling Circulation Fan AUTO HTG FAN rotates between Auto Heating Circulation Fan AUTO CLG FAN rotates between Auto Cooling Circulation Fan ECO Mode Icon The SH TSX can be switched to...

Страница 14: ...overridden to OFF mode via the network or a digital input transition the user can cancel the OFF mode by pressing the OFF icon Similarly a networked interface driven to OFF mode by the user can be ov...

Страница 15: ...has a PARTY MODE button When the PARTY MODE BOOST TIME has been set and the PARTY MODE icon is pressed the PARTY MODE is activated icon turns red In the PARTY MODE the device activates the interface...

Страница 16: ...leaning of the interface A C and Lights Buttons It is possible to enable A C and LIGHTS buttons The buttons and their current status is displayed on the front screen When touching the buttons the Ligh...

Страница 17: ...INFORMATION screen by selecting the LOCK icon it is possible to lock the thermostat Now by entering the LOCK CODE default 0000 the thermostat lock state can be activated The lock mode can be configur...

Страница 18: ...volt free contact can be used to override the interface to ECO and OFF FROST modes or for just monitoring purposed The configuration options are Close for ECO Mode Open for ECO Mode Close for OFF Mod...

Страница 19: ...he all four edges of the screen and then press OK to accept the new settings Language Selection The SH TSX user pages can be displayed in different languages by selecting the language from the System...

Страница 20: ...to Hardware reads the internal temperature sensor status monitoring over the network is always active 0 Hardware Built In Sensor Default 1 Network Digital Input Mode Digital Input Operation status mon...

Страница 21: ...abled Ring Mode Set the Main Ring Colour 0 White 1 Red 2 Blue 3 Green 4 Orange 5 Yellow 6 Magenta 7 Cyan 8 Sensor 1 9 Sensor 2 10 Sensor 3 Default Display Parameter name Description Range Brightness B...

Страница 22: ...s the unit of the target parameter 0 Temperature default 1 Percentage 2 None no setpoint displayed Disable ECO Button Disables the user cancel of the ECO mode 0 Enabled default 1 Disabled System Param...

Страница 23: ...9600 bps 8 data bits Parity None and 1 Stop Bit The default Modbus Slave address is 1 The device Parity can be changed between Odd None and Even The baud rate is selectable between 9600 19200 38400 5...

Страница 24: ...5 DI2 N A Bit 6 Time Lost 64 107 Discrete Input Registers Bit 0 DI1 Bit1 Relay Bit 2 Holiday etc Unsigned 16 0 65 535 N A 108 N A 109 N A 110 N A 111 Current Fan Speed Unsigned 16 0 6 0 6 112 Mode Ico...

Страница 25: ...oured Bar Fan 5 Coloured Bar 111 Fan Speed Override Unsigned 16 0 6 0 6 112 Enable Mode Icon Unsigned 16 0 6 0 Disabled default 1 Htg Clg 2 Htg Clg Fan 3 Auto Htg Clg 4 Auto Htg Clg Fan 5 Auto Htg Fan...

Страница 26: ...signed 16 0 9999 0000 9999 129 Maintenance Mode Password Unsigned 16 0 9999 0000 9999 130 Override A C Note To release override set to None otherwise the user cannot set unset Unsigned 16 0 2 0 None D...

Страница 27: ...122 0 C F Default 0 0 159 Disable ECO Button User Cancel Signed 16 0 1 0 Enabled Default 1 Disabled 300 Modbus Address Unsigned 16 0 247 0 247 Default 1 301 Modbus Baud Rate Unsigned 16 0 4 0 9600 Def...

Страница 28: ...V 2 Sensor 2 Temp AV 3 Sensor 3 Temp AV 4 Brightness AV 5 Y1 Output AV 6 Y2 Output AV 7 Y3 Output Binary Input 5 BI 0 Digital Input DI1 BI 1 Boost Party Mode Status BI 2 NA BI 3 NA BI 4 Auto Fan Statu...

Страница 29: ...s are set to null Note 3 Set to 5 none to allow users to change the Mode through the screen Note 4 The maximum number depends on the selected Fan Speed Mode E g if 3 speed is selected then the range i...

Страница 30: ...SH TSX Product Manual EasyIO www easyio eu 30 Dimensions...