24 

110 

Auto Fan Status (fan in auto 
mode) 

 

0..1 

Off - On 

 

 

 

 

 

 

FUNCTION CODE 04 - READ INPUT REGISTERS (Add 30,000 for Modicon 
Addressing) 

100 

Built-In Temperature 
Measurement  

Signed 16  

-400...3020 

-40.0...150.0°C  
(-40.0..302.0°F)  

101 

Resistive Input 1 Measurement

 

Signed 16  

-400...3020 

-40.0...150.0°C  
(-40.0..302.0°F)  

102 

Resistive Input 2 Measurement

 

Signed 16  

-400...3020 

-40.0...150.0°C  
(-40.0..302.0°F)  

103 

Current Calculated Setpoint (°C)  
 

Signed 16  

-400...3020 

-40.0...150.0°C  
(-40.0..302.0°F)  

104 

Interface Current Mode  

Unsigned 16   0..3 

0 = Comfort  
1 = OFF  
2 = Party (Boost) Mode  

105 

Relative Humidity Measurement 
(with RH option)  

Unsigned 16   0..1000  

0..100.0 %rH  

106 

Alarm State  
 

Unsigned 16   0..256  

Bit 0 = Internal NTC (1)  
Bit 1 = RI1 (2)  
Bit 2 = RI2 (4)  
Bit 3 = Humidity sensor 
(8)  
Bit 4 = DI1 (16)  
Bit 5 = DI2 (N/A)  
Bit 6 = Time Lost (64)  

107 

Discrete Input Registers (Bit 0 = 
DI1, Bit1 = Relay, Bit 2 = Holiday 
etc.)  

Unsigned 16   0..65,535  

N/A  

108 

N/A 

 

 

 

109 

N/A 

 

 

 

110 

N/A 

 

 

 

111 

Current Fan Speed 

Unsigned 16 

0..6 

0..6 

112 

Mode Icon Status 

Unsigned 16 

0..3 

0 = Auto 
1 = Heating 
2 = Cooling 
3 = Ventilation Fan 

200 

Firmware Version 

Unsigned 16   N/A  

N/A  

 

 

 

FUNCTION CODE 03 - READ HOLDING REGISTERS (For Modicon Addressing Add 
40,000) 
FUNCTION CODE 06 - WRITE SINGLE HOLDING REGISTER  
FUNCTION CODE 16 - WRITE MULTIPLE HOLDING REGISTERS

  

100 

Nominal Setpoint  

Unsigned 16 

 

0...990  

0...999.0 (Default 21.0) 
(°C/°F/%)  

101 

Setpoint Unit 

Unsigned 16 

 

0..1 

 

0 = Temperature 
(Default) 
1 = Percentage 

102 

Sensor 3 Source  

Unsigned 16 

 

0..1 

 

0 = Built-In Sensor 
(Default) 
1 = Network Sensor 

 

103 

Sensor 3 Network Temperature 

Signed 16 

 

-580...1220 

 

-58.0…122.0°C/°F 
(Default 0.0)

 

104 

Minimum Setpoint  

Unsigned 16 

 

0...990 

 

0.0...99.9°C/°F/% 
(Default 14°C)  

105 

Maximum Setpoint  

Unsigned 16 

 

0...990 

 

0.0...99.9°C/°F/% 
(Default 30°C)  

106 

Colour Ring Mode 

Unsigned 16 

 

0..10

 

0 = White 
1 = Red 
2 = Blue 

Содержание SH-TSX

Страница 1: ...SH TSX Product Manual EasyIO www easyio eu 1 Touchscreen Modbus BACnet thermostat with Fan speed control product manual v2 2 SH TSX...

Страница 2: ...110 and BI4 these show if the fan speed has been set to Manual or Auto by user firmware version 3 06 4th Jul 2019 V2 2 Added Setpoint Mode None where no Setpoint is displayed System Setting Screen Ref...

Страница 3: ...formation 10 Fan Speed Display and Manual Override 11 Operating Mode Icon 13 ECO Mode Icon 13 OFF Mode Icon 14 Night Mode Digital Input Override 15 Party Mode Boost 15 Frost Icon 16 Cleaning Mode 16 A...

Страница 4: ...Manual EasyIO www easyio eu 4 Parameter Storage 23 Modbus Registers 23 BACnet Interoperability Building Blocks Supported Annex K 27 BACnet Standard Object Types Supported 28 Device Object Properties 2...

Страница 5: ...conditioning interface for system network devices Features 24VAC DC Power Supply 3 5 Inch Backlit Touchscreen Display BACnet and Modbus Communication Models Fan speed control and display Operating mo...

Страница 6: ...nication BACnet MS TP RS485 maximum 63 devices 0 127 via Touchscreen Default 651000 MAC Address Adjustable 9k6 19k2 38k4 57k6 76k8 Baud Parity None Even Odd 1 or 2 Stop Bits adjustable through Touchsc...

Страница 7: ...0VDC 7A Relay Contact 24V 24Vac dc Supply 0V 0V Supply RI1 Remote NTC10 Temperature Sensor Input 1 RI2 Remote NTC10 Temperature Sensor Input 2 DI1 Volt Free Digital Input Contact A Modbus BACnet MS TP...

Страница 8: ...the PARTY icon in OFF mode shows the OFF icon Pressing the icon the mode can be cancelled FAN SPEED ICON when FAN display is enabled the fan ICON can be used to control the fan speed up to 7 steps AUT...

Страница 9: ...ture or temperature can be set over the network if Sensor2 Source has been set to network The description for the temperature can be changed via Sensor2 Text parameter in the configuration pages By se...

Страница 10: ...the screen This option is particularly useful in hospitality applications where the client base is expected to be international Further Settings and Information The FURTHER SETTINGS shows additional u...

Страница 11: ...A next to the line bar if Auto option selected When the device is manually overridden then the A symbol changes to M indicating manual operation only if Auto option has been selected for Manual Contr...

Страница 12: ...over the network 6 STEP AUTO fan speed rotates between OFF M 1 2 3 4 5 6 segments M and Auto A When auto is selected the display returns to show the speed set over the network ADVANCED advanced fan s...

Страница 13: ...een Auto Heating Cooling Circulation Fan AUTO HTG FAN rotates between Auto Heating Circulation Fan AUTO CLG FAN rotates between Auto Cooling Circulation Fan ECO Mode Icon The SH TSX can be switched to...

Страница 14: ...overridden to OFF mode via the network or a digital input transition the user can cancel the OFF mode by pressing the OFF icon Similarly a networked interface driven to OFF mode by the user can be ov...

Страница 15: ...has a PARTY MODE button When the PARTY MODE BOOST TIME has been set and the PARTY MODE icon is pressed the PARTY MODE is activated icon turns red In the PARTY MODE the device activates the interface...

Страница 16: ...leaning of the interface A C and Lights Buttons It is possible to enable A C and LIGHTS buttons The buttons and their current status is displayed on the front screen When touching the buttons the Ligh...

Страница 17: ...INFORMATION screen by selecting the LOCK icon it is possible to lock the thermostat Now by entering the LOCK CODE default 0000 the thermostat lock state can be activated The lock mode can be configur...

Страница 18: ...volt free contact can be used to override the interface to ECO and OFF FROST modes or for just monitoring purposed The configuration options are Close for ECO Mode Open for ECO Mode Close for OFF Mod...

Страница 19: ...he all four edges of the screen and then press OK to accept the new settings Language Selection The SH TSX user pages can be displayed in different languages by selecting the language from the System...

Страница 20: ...to Hardware reads the internal temperature sensor status monitoring over the network is always active 0 Hardware Built In Sensor Default 1 Network Digital Input Mode Digital Input Operation status mon...

Страница 21: ...abled Ring Mode Set the Main Ring Colour 0 White 1 Red 2 Blue 3 Green 4 Orange 5 Yellow 6 Magenta 7 Cyan 8 Sensor 1 9 Sensor 2 10 Sensor 3 Default Display Parameter name Description Range Brightness B...

Страница 22: ...s the unit of the target parameter 0 Temperature default 1 Percentage 2 None no setpoint displayed Disable ECO Button Disables the user cancel of the ECO mode 0 Enabled default 1 Disabled System Param...

Страница 23: ...9600 bps 8 data bits Parity None and 1 Stop Bit The default Modbus Slave address is 1 The device Parity can be changed between Odd None and Even The baud rate is selectable between 9600 19200 38400 5...

Страница 24: ...5 DI2 N A Bit 6 Time Lost 64 107 Discrete Input Registers Bit 0 DI1 Bit1 Relay Bit 2 Holiday etc Unsigned 16 0 65 535 N A 108 N A 109 N A 110 N A 111 Current Fan Speed Unsigned 16 0 6 0 6 112 Mode Ico...

Страница 25: ...oured Bar Fan 5 Coloured Bar 111 Fan Speed Override Unsigned 16 0 6 0 6 112 Enable Mode Icon Unsigned 16 0 6 0 Disabled default 1 Htg Clg 2 Htg Clg Fan 3 Auto Htg Clg 4 Auto Htg Clg Fan 5 Auto Htg Fan...

Страница 26: ...signed 16 0 9999 0000 9999 129 Maintenance Mode Password Unsigned 16 0 9999 0000 9999 130 Override A C Note To release override set to None otherwise the user cannot set unset Unsigned 16 0 2 0 None D...

Страница 27: ...122 0 C F Default 0 0 159 Disable ECO Button User Cancel Signed 16 0 1 0 Enabled Default 1 Disabled 300 Modbus Address Unsigned 16 0 247 0 247 Default 1 301 Modbus Baud Rate Unsigned 16 0 4 0 9600 Def...

Страница 28: ...V 2 Sensor 2 Temp AV 3 Sensor 3 Temp AV 4 Brightness AV 5 Y1 Output AV 6 Y2 Output AV 7 Y3 Output Binary Input 5 BI 0 Digital Input DI1 BI 1 Boost Party Mode Status BI 2 NA BI 3 NA BI 4 Auto Fan Statu...

Страница 29: ...s are set to null Note 3 Set to 5 none to allow users to change the Mode through the screen Note 4 The maximum number depends on the selected Fan Speed Mode E g if 3 speed is selected then the range i...

Страница 30: ...SH TSX Product Manual EasyIO www easyio eu 30 Dimensions...

Отзывы: