FW Series – firmware upgrade guide v2.0 

 

 
The firmware upgrade procedure will take approximately 

10 to 12

 minutes.  

Wi-Fi connection will be disconnect during this period.  
Do not attempt to connect to the controller during this period.  
 

**DO NOT LOSE POWER TO THE CONTROLLER DURING THIS PERIOD

.** 

 
It is important to wait and allow the flashing/reboot process to complete.  
Wait for the RED LED (ERR)  to turn off for before powering off or perform any connection. 
 
Failure  to  follow  this  precautionary  instruction  may  damage  the  controller  requiring  it  to  be  returned 
back to factory for repairs or replacement.  
 

**  IMPORTANT:  DO  NOT  LOSE  POWER  DURING  THIS  PERIOD.  POWER  LOST  DURING  FIRMWARE 
UPGRADING PROCEDURE WILL RESULT IN PERMANENT DAMAGE TO THE CONTROLLER.** 

 

Step 11 

Once the controller firmware upgrade procedure is completed, the “Error” LED (ERR) will go turn OFF and 
the controller will boot up normally.  
 

 
Step 12 

Verify controller firmware upgrade is successful, connect to the controller using CPT tool and look at the 
“platform” (

plat

) in the service folder or login to the web browser and go to the firmware upgrade page 

to verify the firmware and MCU version.  

**V1 FW Series will has a version number of V1.0bxx** 
**V2 FW Series will has a version number of V2.0bxx** 
 

 
 

 

 

Version property slot shows the version number.  

The Version noted in the platform object should match the Version downloaded.   

 
 
 
 
 
 
 
 
 

Содержание FW Series

Страница 1: ...FW Series firmware upgrade guide v2 0 1 EasyIO FW Series Firmware Upgrade guide...

Страница 2: ...W Series firmware upgrade guide v2 0 2 Document Change Log 12th August 2017 Document created 17 th Dec 2018 Updated disclaimer and support channel emails addresses 23rd May 2019 Update to include FW 2...

Страница 3: ...tice EasyIO logo are registered trademarks of EasyIO Holdings Pte Ltd CPT Tool is by Online Tools Inc BACnet and ASHRAE are registered trademarks of American Society of Heating Refrigerating and Air C...

Страница 4: ...firmware upgrade guide v2 0 4 Table of Contents Introduction 5 Login Details for Web Browser 5 Precaution 5 Prerequisites 6 Firmware Upgrade Procedure 6 Kits version VS Firmware version 11 Technical S...

Страница 5: ...wser By default the EasyIO FW Series controller s login details are as below Applies for both V1 and V2 FW series Primary Network Main Wifi SSID and Ethernet Default IP address 192 168 10 30 Default S...

Страница 6: ...r SSID1 or SSID2 can perform the firmware upgrade procedure For detail user guide about wifi network please refer to EasyIO FW Series User Reference By default the EasyIO FW controller SSID is FW xxxx...

Страница 7: ...ick expand icon at the bottom left to view the sidebar Then select Utility menu Step 7 Once you are in the utility page select Firmware Upgrade option Step 8 Locate the firmware file in your computer...

Страница 8: ...ruption is allowed Any power interruption will damage the controller and if this occurs the controller cannot be recovered and controller is required to shipped back to EasyIO for recovery process Ens...

Страница 9: ...r replacement IMPORTANT DO NOT LOSE POWER DURING THIS PERIOD POWER LOST DURING FIRMWARE UPGRADING PROCEDURE WILL RESULT IN PERMANENT DAMAGE TO THE CONTROLLER Step 11 Once the controller firmware upgra...

Страница 10: ...FW Series firmware upgrade guide v2 0 10 Image above is a V1 FW series controller Image above is a V2 FW series controller...

Страница 11: ...1 0 45 12 28 Segment 1 Segment 2 Segment 3 Segment 4 Segment 5 easyioFW BACnet 1 0 45 12 6 Segment 1 easyioFW identifies that the kit is for FG Series Controller use only Segment 2 BACnet identifies...

Страница 12: ...de guide v2 0 12 Technical Support For technical support issues please contact technical support person as below Worldwide Support support easyio com North America Support support easyio pro Europe Su...

Отзывы: