FW Series – firmware upgrade guide v2.0
5
Introduction
All products in the FW Series are equipped with a built-in “boot -loader”. This feature is designed save
time and effort when updating the controller firmware.
Firmware upgrade process for FW series is done through web browser.
Any web browser is compatible.
Model
Firmware Version Numbering
Remarks
EasyIO FW – V1
(FW-14 , FW-08 and FW-08V)
V1.0b
xx
, where
xx
is the build
number.
V1.0 is referring to the FW
hardware version.
V1.0 is referring to FM-02
module
EasyIO FW - V2
(2
nd
Generation)
(FW-28)
V2.0b
xx
, where
xx
is the build
number.
V2.0 is referring to the FW
hardware version.
V2.0 is referring to FM-06
module which is larger module.
Login Details for Web Browser
By default the EasyIO FW Series controller’s login details are as below.
Applies for both V1 and V2 FW series.
Primary Network (Main Wifi SSID and Ethernet)
Default IP address
: 192.168.10.30
Default Subnet
: 255.255.255.0
Default Gateway
: 0.0.0.0
Secondary Network (Conf Wifi SSID)
Default IP address
: 192.168.14.1
Default Subnet
: 255.255.255.0
Default Gateway
: 0.0.0.0
Precaution
Tech Tip: -**Please ensure you backup the controller Sedona App before running the
firmware upgrade as the Sedona App in the controller will be erased during the flashing
procedure**
Tech Tip: -**during firmware flashing, no power interruption is allowed. Any power
interruption will damage the controller and if this occurs the controller cannot be
recovered and controller is required to shipped back to EasyIO for recovery process.
Ensure the controller is supplied with a constant 24Vac or 24Vdc supply during the flashing
procedure
**