EasyIO FS32 – User Reference v1.4 

12 

 

Universal Output Connection

 

 

EasyIO  FS  series  has  Universal  Output  connections.  Each  Universal  Output  can  be  configured  to  drive 
voltage or current output or digital output via hardware jumper setting and internal register settings.

 

 

The operating range for voltage mode is 0 – 10V and for current mode either 0 – 20mA or 4 – 20mA.  
 

**We DO NOT recommend you to drive a relay directly from UO 0-10V mode as it is not design for it 
and will damaged the UO. ** 
 

For current transmitter, the circuit able to drive load impedance up to 800 ohm which is  ideal for long 
wire connection (up to 500 meter wire length).

 

 

For UO as digital output it can only support up to 24VDC and max load is 200mA each UO channel. AC 
power source is not allowed. It will damage the controller.

 

 
 

 

Universal Output

 

8 Channels (FS-32) 

 

 

 

 

 

Type

 

Current: 0 - 20mA, 4 - 20mA , max load impedance

 800 Ohm

 

 

    

Voltage: 0 – 10VDC , min load impedance 

2,000 Ohm

 

 

    

Digital Mode, Max Sinking Current Rating:

 0.2A Max each channel

 

 

    

 

 

    

 

 

Universal Output Connection for Voltage and Current 

 

 

Содержание FS Series

Страница 1: ...EasyIO FS32 User Reference v1 4 1 EasyIO FS Series User Reference...

Страница 2: ...EasyIO FS32 User Reference v1 4 2 Document Change Log 12 th March 2019 Remove RS485 built in jumper note FS Series DO NOT have EOL jumper 12 th December 2019 Added IP changing option...

Страница 3: ...mark Notice EasyIO logo are registered trademarks of EasyIO Holdings Pte Ltd BACnet and ASHRAE are registered trademarks of American Society of Heating Refrigerating and Air Conditioning Engineers All...

Страница 4: ...on 5 RS485 Specification 6 Jumpers Setting 7 Wiring diagram 8 Digital Output Wiring Connection 9 Universal Input Connection 10 Universal Output Connection 12 Buttons and Indications 14 Login Details 1...

Страница 5: ...onnection use individual power supply for each controller If a single power supply is used make sure controller power supplies are connected with the same polarity Electrical Power Supply 24V AC 5 or...

Страница 6: ...d keep it as short as possible and never connect more than one device to the wire branch it is not recommended Be careful if single power supply is used for all connected RS485 device make sure all de...

Страница 7: ...EasyIO FS32 User Reference v1 4 7 Jumpers Setting Below image shows the jumper setting for Universal Input Universal Output Watchdog...

Страница 8: ...EasyIO FS32 User Reference v1 4 8 Wiring diagram...

Страница 9: ...tal output is for general purpose isolated digital output connections relay output 24 VAC 2 0A 24 VDC 2 0A Digital Output 8 Channels FS 32 2 Channels FS 20 Type Relay Contacts SPST NO 48VA at 24VAC It...

Страница 10: ...10K 5 Ohm 0 1 5K 1 Ohm Thermistor 10K 10K Shunt 1K Balco 1K Platinum All 0 01 Deg C UI as Digital Input Voltage Free Contact a Resistance The working range of resistance is 500Ohm 500KOhms The commonl...

Страница 11: ...EasyIO FS32 User Reference v1 4 11 Universal Input as Pulse Input specifications Max 20Hz...

Страница 12: ...0 10V mode as it is not design for it and will damaged the UO For current transmitter the circuit able to drive load impedance up to 800 ohm which is ideal for long wire connection up to 500 meter wi...

Страница 13: ...er source it will damage the controller Max DC power source is 24VDC Max load for Universal Output as Digital Output is 200mA Refer below table for software configurations of UO as DO A Digital Output...

Страница 14: ...is pressed whenever manual restart is required The Service button is used to activate the built in boot loader program for software upgrade Each digital output has a correspondence LED to indicate it...

Страница 15: ...rform graphics deployment Username webuser Password 123456 FTP client Firmware Upgrade Login This login allows user to upgrade firmware Username easyio Password 123456 Default IP address 192 168 10 12...

Страница 16: ...S32 via Sedona workbench Locate the object IP under the Service folder Step 2 Click IP object and view properties at the side bar At the newIpAddress newSubnetMask and newGateway property enter your n...

Страница 17: ...1 Login to the FS32 browser Locate the plug in tab and select Network Manager Step 2 At the network manager page configure the new IP address and hit SAVE Controller will reboot and a manual reconnect...

Страница 18: ...ication backup and save a copy into your computer if you have connection to the EasyIO FS Controller Step 2 Cycle power or toggle the reset button Within 5 seconds press and HOLD down the service butt...

Отзывы: