EasyIO 30P – Frequently Asked Questions

                                                             

7  

 

Frequent Ask Questions – DDC: Main Plant Control, AHU 

Control and Unitary control 

Related to EasyIO-30P series, EasyIO-DEM-5 and EasyIO-LT-D5 

General 

1)

 

What is the power consumption for EasyIO products? 

 

Power Supply Rating 

EasyIO-30P 

24VDC: 320mA 

EasyIO-DEM-5 

24VAC/VDC: 150mA 

 

All EasyIO products’ power consumption is stated in all of our catalogues. For further details, 
please refer to our products catalogue.  

 

2)

 

Can EasyIO-30P share 24VAc transformer with non EasyIO products? 

It is not advisable to share transformer with EasyIO products, as our power supply are half wave 
power supply.  

 

3)

 

Can EasyIO-30P share transformer with EasyIO-DEM-5? 

Yes. Please mind the polarity. Make sure the 24G and 24H are correct.  

 

4)

 

How many EasyIO-30P can be connected to a 2A transformer? 

As per our power rating, a 2A transformer can power up to 6 EasyIO 30P. Each EasyIO30P’s peak 
power consumption with full load is at 320mA @ 24VAC. 

 

5)

 

What protocol does EasyIO-30P support? 

EasyIO-30P supports BACnet, Modbus and Sedona. 

 

Getting Started – Hardware  

1)

 

What input type does a Universal Input (UI) support? 

EasyIO 30P supports Voltage Free Contact as digital input 

Содержание 30P

Страница 1: ...EasyIO 30P Frequently Asked Questions 1 EasyIO 30P Frequently Asked Questions ...

Страница 2: ...EasyIO 30P Frequently Asked Questions 2 Document Change Log 31th January 2011 Document created 07th March 2012 Remove Non Sedona content Update documents name ...

Страница 3: ...EasyIO 30P Frequently Asked Questions 3 Disclaimer EasyIO 30P is a product by EasyIO Holdings Pte Ltd The EasyIO 30P was built on the Sedona Framework Sedona Framework is a trademark of Tridium Inc ...

Страница 4: ...ss EasyIO 30P support 11 10 If EasyIO 30P RS485 port is damaged is the Ethernet port still able to communicate 11 11 How to connect EasyIO DEM 5 to EasyIO 30P s Universal Input 12 12 How many does a DEM5 does a EasyIO30P support 12 Getting Started Software General 12 1 What is the default login name and password for EasyIO 30P 13 2 What is the default IP address for EasyIO 30P 13 3 How to change t...

Страница 5: ... 1 What is the minimum requirement in order to connect a Sedona Controller 20 2 How to program EasyIO 30P SF It is same with EasyIO BACnet or EasyIO Modbus 20 3 EasyIO 30P SF supports what protocols 20 4 What is the default login credentials for Sedona Web Browser 20 5 How to change add edit Sedona Web Browser login credential 20 6 What is the default login credentials for Sedona Web Browser 20 7 ...

Страница 6: ...EasyIO 30P Frequently Asked Questions 6 18 How to archive history that is stored in the Sedona Controller into Niagara Fox 26 19 What is the max memory allocated for history in a Sedona Controller 26 ...

Страница 7: ...mer with non EasyIO products It is not advisable to share transformer with EasyIO products as our power supply are half wave power supply 3 Can EasyIO 30P share transformer with EasyIO DEM 5 Yes Please mind the polarity Make sure the 24G and 24H are correct 4 How many EasyIO 30P can be connected to a 2A transformer As per our power rating a 2A transformer can power up to 6 EasyIO 30P Each EasyIO30...

Страница 8: ... voltage analogue output AO 3 Can EasyIO 30P directly drive 240V equipment No Although EasyIO does come 240VAC 5A relays we do not recommend to directly driving a 240VAC equipment It may cause backfire to the controller and causes damage damages 4 What are the jumper settings on EasyIO 30P board For jumpers settings please refer to our online Information Help Go to Information Jumper Setting ...

Страница 9: ... many EasyIO 30P can be connected in a single RS485 bus Modbus RTU 31nos BACnet MS TP 31nos 6 How to use EasyIO 30P digital outputs As a triac output or a relay contact output EasyIO 30P digital output is a contact output It is not a triac output ...

Страница 10: ...formation Help Go to Information Jumper Setting Serial addressing is using the binary code Please note that the LSB is on the right and MSB is on the left 8 How to confirm the serial address that was set User can confirm or double check on the serial addressing via web browser Go to Setting General tab ...

Страница 11: ...orts up to 254 addressing Address 0 and 255 should not be used 10 If EasyIO 30P RS485 port is damaged is the Ethernet port still able to communicate Yes The damaged RS 485 comm port will not affect the Ethernet port in the EasyIO 30P if there is no other component burned during the RS 485 comm port surge ...

Страница 12: ...O 30P s Universal Input An EasyIO DEM5 only can be connected any one of the 8 Universal Inputs An EasyIO DEM5 needs power in order for it to work 12 How many does a DEM5 does a EasyIO30P support One EasyIO 30P can support up to 8 nos of EasyIO DEM5 Getting Started Software General ...

Страница 13: ...P Default IP address and subnet mask is as below IP address 192 168 10 10 Subnet mask 255 255 255 0 3 How to change the EasyIO 30P s IP address a Login to the EasyIO 30P via web browser b Go to Main Network tab c An example of changing the IP address as below Existing IP address 192 168 10 10 Existing subnet mask 255 255 255 0 Existing default gateway null New IP address 192 168 1 10 New subnet ma...

Страница 14: ... it will not allow to change the IP address 4 How to recover the lost IP address for EasyIO 30P Please refer to documents as below a EasyIO Basic 02 Recover Lost IP and Login Crendentials User Guide b EasyIO Basic 03 Terminal Mode User Guide 5 How to check the EasyIO 30P s firmware type and version Go to Main Device info tab ...

Страница 15: ...EasyIO 30P Frequently Asked Questions 15 Model Number IO 30S BM Sedona Firmware version IO 30P BN Bacnet Firmware Version IO 30P ME Modbus Firmware Version Firmware Version ...

Страница 16: ...rmat firmware Then flash it again to the desire firmware Please use the EasyIO30PFormatV1 00 bin file This action will clear all the memory Please back up whatever necessary Please refer to document EasyIO Basic 01 Firmware Flashing User Guide 8 How to perform firmware flashing for EasyIO 30P Please refer to document EasyIO Basic 01 Firmware Flashing User Guide 9 How to get the latest EasyIO 30P f...

Страница 17: ...currently Maximum 5 users can access concurrently Higher than that the performance will be sluggish 12 Can the web server port number default is 80 be changed from EasyIO 30P s web interface The web server port number can be configured with Sedona firmware version Web server port setting was found in Sedona version ...

Страница 18: ...are Flashing User Guide 4 What is the IP address for EasyIO 30P Boot Loader mode The default IP address for EasyIO 30P boot loader mode is 192 168 10 10 This IP address is not the same with the web browser IP address If user has changed the username and password via web browser that username and password cannot be used for boot loader mode 5 For Windows Vista or Windows 7 the third party hyper ter...

Страница 19: ...onverter would be needed if hardware does not support RS 485 communication 3 What are the settings for EasyIO 30P s terminal mode Please refer to document EasyIO Basic 03 Terminal Mode User Guide 4 Why can t get into EasyIO 30P s terminal mode BACnet firmware is using If you are running EasyIO 30P with BACnet firmware most likely the RS 485 COM is broadcasting BACnet MS TP messages This will jamme...

Страница 20: ...via Niagara Workbench equipment with Sedona Workbench 3 EasyIO 30P SF supports what protocols EasyIO 30S BM support BACnet IP BACnet Ethernet BACnet MS TP Modbus TCP Modbus RTU and also Modbus Master and Salve 4 What is the default login credentials for Sedona Web Browser Username admin Password 1234 Web Port 80 5 How to change add edit Sedona Web Browser login credential User can change add edit ...

Страница 21: ...ench login credential Users can change add edit login credentials via Sedona Workbench Open the Sedona Workbench via Niagara Workbench Go to Sedona App Service Users This login credentials can be reset back to factory settings by re installing and restart Sedona VM from the web browser Please refer to item 9 ...

Страница 22: ...EasyIO 30P Frequently Asked Questions 22 8 How to connect into Sedona Workbench a Open Niagara Workbench b Go to File Open Open Sedona c Key in the login credentials as item 6 ...

Страница 23: ...r the installed Sedona applications Login to the EasyIO 30S BM via web browser go to Sedona Sedona Tab Key in the magic number provided This is re install all Sedona VM into the controller to default and will also restart the Sedona VM This step will also clear all the login credentials created previously to default ...

Страница 24: ...to change settings from the web browser except for a Modbus Serial Settings b BACnet serial settings and BACNet device ID c Temperature Table Changing settings via web browser such as AI settings will get overwrite or restore back to default if any power cycle occur 12 How to define the temperature table Please refer to EasyIO Advanced 07 Temperature Table User Guide 13 I cannot connect into Sedon...

Страница 25: ...ch login credential User can change add edit login credentials via Sedona Workbench Open the Sedona Workbench via Niagara Workbench Go to Sedona App Service Users This login credentials can be reset back to factory settings by re installing and restart Sedona VM from the web browser Please refer to item 9 16 Why is the performance slow down after I have complete building my logic inside the contro...

Страница 26: ...be used for too complicated task must be verified first 17 How to create history in the Sedona Controller Please refer to EasyIO Adv 07 Temp Table User Guide 18 How to archive history that is stored in the Sedona Controller into Niagara Fox Please refer to Sedona history document for step by step or click on the link below 19 What is the max memory allocated for history in a Sedona Controller Tota...