After LED flash code analysis and appliance repair are 
complete, turn thermostat below room temperature for 10 
seconds; turn the thermostat above room temperature to 
initiate a new call for heat. 

5. 

Observe the ignition sequence; comparing it to the Sequence 
of Operation shown in fig. 10.  Allow the new ignition 
sequence to proceed until appliance lights or an abnormal or 
unexpected event is observed.  See next section 

 

Troubleshooting Without LED Indicator Assistance 
(Appliance power or thermostat call for heat has cycled 
since appliance failure occurred) 

 

 

1. 

Make sure the appliance power is on and any manually 
operated gas cock on the appliance is open. 

2. 

Remove the appliance burner compartment door.  
Confirm that RW9510/RW9520; RW9610/RW9620 LED 
indicator is flashing in a “bright-dim” sequence. 

3. 

Make sure the ignition system control switch is in the ON 
position. 

4. 

Disconnect the system thermostat leadwires at the  
Terminal Board. 

5. 

Using alligator clips on a short jumper wire, jumper the R 
and W terminals on the EFT or Terminal Board. 

6. 

Observe the appliance operation, comparing it to the 
Sequence of Operation shown in Fig. 10.  Allow the 
ignition sequence to proceed until the appliance lights or 
an abnormal or unexpected event is observed. 

7. 

Check the appliance as shown in the following table. 

 

 

 

If 

And 

Check/Repair 

Combustion air 
blower does not 
energize. 

2 Flash code does not come on 30 
seconds after call for heat starts. 

1. 

Combustion air blower wiring 

2. 

Combustion air blower 

Combustion air 
blower does not 
energize. 

2 Flash code does come on 30 seconds 
after call for heat starts. 

1. 

Airflow proving switch stuck closed 

2. 

Airflow proving switch miswired or jumpered 

Combustion air 
blower energized. 

3 Flash code does not come on after 30 
seconds. 

Wait for the prepurge time to expire 

3 Flash code comes 
on 30 seconds after 
combustion air 
blower is energized. 

Combustion air blower turns off. 

1. 

Ignition system control switch must be in the ON position 

2. 

Airflow proving switch stuck in open position 

3. 

Airflow proving switch tubing and wiring 

4. 

Obstructions or restrictions in appliance air intake or 
exhaust flue system that prevent proper combustion air 
flow 

Prepurge time has 
expired. 

HSI element does not glow red within 10-
15 seconds. 

1. 

Broken or damaged HSI element 

2. 

Broken or damaged HSI element leadwires 

3. 

Failure to power HSI element 

HSI element is 
glowing red. 

No other visible control system action. 

Wait for HSI element warm up time to expire 

 
 
 
 
 
 
 
 
 
 
 
 
 

WARNING 
Line Voltage Power 
Can cause property damage, 
severe injury or death. 

Only a trained, experienced service 
technician 
Should perform this 
troubleshooting. 

Содержание PPRTH-50-15

Страница 1: ...thoroughly before installing or servicing this equipment The installation must comply with local codes and CAN CGA B 149 in Canada or the National Fuel Gas codes ANSI Z83 20 CSA 2 34 2008 and ANSI Z83...

Страница 2: ...GNES DE SECURITE SI VOUS SENTEZ UNE ODEUR DE GAZ 1 OUVREZ LES FENETRES 2 NE TOCHEZ PAS AUX INTERRUPTEURS ELECTRIQUES 3 ETEIGNEZ TOUTE FLAMME NUE 4 CONTACTEZ IMMEDIATEMENT VOTRE COMPANGIE DE GAZ READ T...

Страница 3: ...used If in any doubt contact the factory for proper assessment HEATING As a general rule it is recommended that the burner head be located near the area with the greatest heat loss Also note that ther...

Страница 4: ...must only be performed by a licensed technician trained and educated in the installation of this type of gas appliance INFRARED HEAT The Purple People Heater heaters are effective in heating outdoor s...

Страница 5: ...imum clearances marked on the heater will be maintained from vehicles parked below the heater Minimum clearances inches from combustibles measured from radiant surface Clearances are reduced by 1 3 15...

Страница 6: ...eat anticipator that the heat anticipator is set at maximum When using a 24 Volt thermostat only one heater may be controlled by one thermostat In locations used for storage of combustible materials s...

Страница 7: ...stalling supplemental steel support rail or angle iron can substantially reduce labour and materials Hardware with a minimum 40 lbs workload must be used at each heater suspension point Connect the st...

Страница 8: ...rmal gas supply pipe expansion and radiant tube heater expansion must be provided All piping must conform to local codes Provide a 1 8 in 3 2mm NPT plugged tapping accessible for test gauge connection...

Страница 9: ...N IN COMMERCIAL GARAGES AND PARKING STRUCTURES Low intensity heaters are suitable for use in commercial garages when installed in accordance with the latest edition of the Standard for Parking Structu...

Страница 10: ...ts cranes vehicles lifts overhead doors etc sprinkler systems and other obstructions on the site Consideration must also be given to vent duct placement and the allowable combined lengths of vent and...

Страница 11: ...thorities for approval of the proposed installation GAS SUPPLY 1 Only persons trained and experienced in gas supply piping should be engaged to install the supply piping to the heaters All gas piping...

Страница 12: ......

Страница 13: ......

Страница 14: ...avoid damaging movement under various weather conditions The chain mount is ideal for indoor use when hanging from an overhead structure OUTDOOR PIPE MOUNT INSTALLATION 1 Install post mounting bracke...

Страница 15: ...tube along with other tubes into the hangers joining the lengths of tube together and securing joints IMPROPER HANGER PLACEMENT CAN CAUSE THE RADIANT TUBE TO WARP AND VOID WARRANTY THE BAFFLE MUST BE...

Страница 16: ...NZI Z21 24 CSA 6 10 In Canada a Type 1 hose connector CAN CGA 8 1 Also the flue vent and combustion air intake if used must be installed in such a manner that the normal expansion of the heater will b...

Страница 17: ...Horizontal vent systems shall slope downwards not less than inch per foot from the start of the vent system to the vent terminal 11 When installed in a large and adequately ventilated space agricultu...

Страница 18: ......

Страница 19: ......

Страница 20: ......

Страница 21: ......

Страница 22: ......

Страница 23: ......

Страница 24: ......

Страница 25: ......

Страница 26: ......

Страница 27: ......

Страница 28: ......

Страница 29: ......

Страница 30: ......

Страница 31: ......

Страница 32: ......

Страница 33: ...Gas Connector AC1080 Outside Air Adapter AC1030 Remote Thermostat AC1100 Outside Air Wall Cap AC1110 Combustion Air Flex Duct AC1120 4x4x6 Tee AC1130 90 degree Elbow AC1150 Wall Thimble AC1170 Brooder...

Страница 34: ...LISTED ACCESSORIES...

Страница 35: ...AC1120 Tee 4 x4 x6...

Страница 36: ...a Class 1 or Class 2 explosive environment nor a residence If installation of this equipment is in question consult with local authorities having jurisdiction Fire Marshall labour department insurance...

Страница 37: ...4 in USA B149 1 in Canada and as indicated in the manual WARNING VENTING Inadequate venting of a heater may result in asphyxiation carbon monoxide poisoning injury or death The heater may be directly...

Страница 38: ...re protected to prevent degradation Minimum 24 must be provided at the centre of the appliance for burner servicing When venting through a wall the vent terminal must be located at least 7 0 ft above...

Страница 39: ...SED DURING TRIAL FOR IGNITION CIRCULATING AIR FAN OFF AFTER DELAY MAIN VALVE CLOSES THERMOSTAT CALL FOR HEAT ENDS FLAME SENSE LOST COMBUSTION AIR BLOWER OFF AFTER POST PURGE YES WAIT FOR NEXT CALL FOR...

Страница 40: ...icates Electronic Fan Timer the heat speed circulating air fan will be energized until the limit string resets 1 Open manual reset or auto reset burner rollout switch 2 Open high temperature or auxili...

Страница 41: ...al or unexpected event is observed 7 Check the appliance as shown in the following table If And Check Repair Combustion air blower does not energize 2 Flash code does not come on 30 seconds after call...

Страница 42: ......

Страница 43: ...nt allowable under applicable law Easy Radiant Works liability for consequential or incidental damages is expressly disclaimed Easy Radiant Works liability in all events is limited to and shall not ex...

Страница 44: ...mpleted reports can be faxed to Technical Support Easy Radiant Works at fax no 905 899 2262 or call phone no 905 899 3473 During startup material coatings used in the production of tubes and reflector...

Страница 45: ......

Отзывы: