24
Bias Current, Ammeter Al Multiples of rated
current In
Initial
Settings
Bias
Settings
0
1
1.5
2
2.5
Operate Current, Ammeter A2 Amps
10%
10%
0.10
0.11
0.16
0.21
2.26
20%
20%
0.20
0.21
0.33
0.44
0.56
30%
30%
0.30
0.35
0.53
0.71
0.88
40%
40%
0.40
0.50
0.75
1.00
1.25
50%
50%
0.50
0.67
1.00
1.33
1.67
-
60%
0.5
0.86
1.29
1.71
2.14
-
70%
0.5
1.08
1.62
2.15
2.69
Table 1. Normal Operate Values
Bias Current, Ammeter Al Multiples of rated
current In
Initial
Settings
Bias
Settings
0
1
1.5
2
2.5
Operate Current, Ammeter A2 Amps
10%
10%
20%
20%
30%
30%
40%
40%
50%
50%
-
60%
-
70%
Table 2. Operate values Measured on Ammeter A2