                                        EASTRON SDM630MCT-RJV / SDM630MCT-RJA User Manual V1.1 

                                                                                                                               

 

Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.   
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn 

- 1 - 

1.1

 

Introduction 

This document provides operating, maintenance and installation instructions. The unit measures 
and displays the characteristics of three phase four wires supplies, including voltage, frequency, 
current, power, active and reactive energy, imported or exported. Energy is measured in terms of 
kWh, kVarh. Maximum demand current can be measured over preset periods of up to 60minutes. 
The meter uses self-power supply module, the power is getting from L1.     
 
This meter can be configured to work with a wide range of CTs, giving the unit a wide range of 
operation.  Built-in  interfaces  provide  pulse  and  Modbus  outputs.  Configuration  is  password 
protected. 
 
The meter has RJ-12 terminal for current inputs. And voltage terminals, Pulse outputs and RS485 
terminals are all plug-in types. The plug-in solution is user-friendly and mistake-free. It can also 
save much labor work in wiring.   
 

1.2

 

Unit Characteristics 

The Unit can measure and display: 

 

Line voltage and THD% (total harmonic distortion) of all phases 

 

Line Frequency 

 

Currents, Current demands and current THD% of all phases 

 

Power, maximum power demand and power factor 

 

Active energy imported and exported 

 

Reactive energy imported and exported 

 
The unit has password-protected set-up screens for: 

 

Changing password 

 

Demand Interval time 

 

Reset for demand measurements 

 

Pulse output duration 

 

RS485 Communication 

 

CT and PT setting 

 
Two  pulse  output  indicates  real-time  energy  measurement.  A  Modbus  output  allows  remote 
monitoring from another display or a computer. 
 

  1.3 Current inputs 

The  unit  can  be  configured  to  operate  with  CT  ratio  between  primary  current  and  secondary 
current.  The  secondary  current  is  333mV

SDM630MCT-RJV  only

.  The  secondary  current  is 

100mA

SDM630MCT-RJA only

. 

 

  1.4 Modbus 

This  uses  a  RS485  port  with  Modbus  RTU  protocol  to  provide  a  means  of  remotely  monitoring 
and controlling the Unit. 
Set-up screens are provided for setting up the RS485 port. 

Содержание SDM630MCT-RJA-100mA

Страница 1: ...ron com cn SDM630MCT RJV 333mV SDM630MCT RJA 100mA Three phase multifunction din rail energy meter Plug in solution labor saving wiring mistake free Measures kWh KVarh KW Kvar KVA P F PF Hz dmd V A THD etc Bi directional measurement IMP EXP Plug in RJ 12 CT connection Two pulse outputs RS485 Modbus RTU Din rail mounting 35mm Better than Class 1 B accuracy USER MANUAL 2016 V1 1 ...

Страница 2: ...ls are all plug in types The plug in solution is user friendly and mistake free It can also save much labor work in wiring 1 2 Unit Characteristics The Unit can measure and display Line voltage and THD total harmonic distortion of all phases Line Frequency Currents Current demands and current THD of all phases Power maximum power demand and power factor Active energy imported and exported Reactive...

Страница 3: ...00imp kWh 2 Start Up Screens 1 The first screen lights up all display segments and can be used as a display check 2 The second screen indicates the firmware installed in the unit and its build number 3 The interface performs a self test and indicates The result if the test passes After a short delay the screen will display active energy measurements 2 1 Measurements The buttons operate as follows ...

Страница 4: ...ww eastron com cn 3 3 Select the Power display screens In Set up Mode this is the Down button 4 Select the Energy display screens In Set up mode this is the Enter or Right button Voltage and Current Each successive pressing of the button selects a new range 1 1 Phase to neutral voltages 2 Current on each phase 3 1 Phase to neutral voltage THD 4 Current THD for each phase ...

Страница 5: ... 314001 China Tel 0086 573 83698881 83698882 Fax 0086 573 83698883 Web www eastron com cn 4 Frequency and Power factor and Demand Each successive pressing of the button selects a new range 1 Frequency and Power Factor total 2 Power Factor of each phase 3 Maximum Power Demand 4 Maximum Current Demand ...

Страница 6: ... Zhejiang 314001 China Tel 0086 573 83698881 83698882 Fax 0086 573 83698883 Web www eastron com cn 5 Power Each successive pressing of the button select a new range 1 Instantaneous Active Power in kW 2 Instantaneous Reactive Power in kVar 3 Instantaneous Volt amps in KVA 4 Total kW kVarh kVA ...

Страница 7: ... 573 83698881 83698882 Fax 0086 573 83698883 Web www eastron com cn 6 Energy Measurements Each successive pressing of the button selects a new range 1 1 Imported active energy in kWh 1 2 Exported active energy in kWh 2 1 Imported reactive energy in kVarh 2 2 Exported reactive energy in kVarh 3 1 Total active energy in kWh ...

Страница 8: ... Setting up is password protected so you must enter the correct password default 1000 before processing If an incorrect password is entered the display will show PASS Err To exit setting up mode press repeatedly until the measurement screen is restored Set up Entry Methods Some menu items such as password and CT require a four digit number entry while others such as supply system require selection...

Страница 9: ...ndicator will be removed and you will be able to use the buttons of and for further menu selection 6 On completion of all setting up press repeatedly until the measurement screen is restored Number Entry Procedure When setting up the unit some screens require the entering of a number In particular on entry to the setting up section a password must be entered Digits are set individually from left t...

Страница 10: ...he button to enter the change password routine The new password screen will appear with the first digit flashing 2 2 Use and to set the first digit and press to confirm your selection The next digit will flash 2 3 Repeat the procedure for the remaining three digits 2 4 After setting the last digit SET will show Press to exit the number setting routine and return to the Set up menu SET will be remo...

Страница 11: ...nd power readings are integrated for maximum demand measurement The options are off 5 8 10 15 20 30 60 minutes 1 From the set up menu use and buttons to select the DIT option The screen will show the currently selected integration time 2 1 Press to enter the selection routine The current time interval will flash 2 2 Use and to select the time required 2 3 Press to confirm the selection SET indicat...

Страница 12: ...utes from the last time operation on the meter Notes If it s set as 0 the backlit will always be on 2 Press to enter the selection routine The current time interval will flash The options can be 0 5 10 30 60 120minutes Use and buttons to select the time required Then press to confirm the set up CT For SDM630MCT RJV only The CT option sets the Primary current CT1 of the current transformer CT that ...

Страница 13: ... CT secondary Voltage 0 1A 2 Set CT Ratio value Press to enter the Primary current screen The range is from 0005 to 9999A PT The PT option sets the secondary voltage PT2 100 to 500V of the Voltage transformer PT that wires to the meter 1 From the Set up menu use and buttons to select the PT option The screen will show the voltage PT secondary voltage value The default value is 400V 2 Secondary PT ...

Страница 14: ...is option allows you to configure the pulse output The output can be set to provide a pulse for a defined amount of energy active or reactive Use this section to set up the pulse output 1 Units Total kWh Total kVarh 1 From the Set up menu use and buttons to select the Pulse output option 2 Press to enter the selection routine The unit symbol will flash 3 Use and buttons to choose kWh or kVarh On c...

Страница 15: ...kWh 100 1000kWh It shows 1 impulse 10kWh kVarh 1 From the Set up menu use and buttons to select the Pulse Rate option 2 Press to enter the selection routine The current setting will flash 0 01 0 1 1 10 100 1000kWh kVarh per pulse Use and buttons to choose pulse rate On Completion of the entry procedure press to confirm the setting and press to return to the main set up menu Pulse Duration The ener...

Страница 16: ...ine The current setting will flash Use and buttons to choose pulse width On completion of the entry procedure press to confirm the setting and press to return to the main set up menu Communication There is a Modbus port can be used for communication using Modbus protocol For Modbus communication parameters are selected from Front panel Modbus Address 1 From the Set up menu use and buttons to selec...

Страница 17: ...7 On completion of the entry procedure press button to confirm the setting and press button to return the main set up menu Baud Rate 1 From the Set up menu use and buttons to select the Baud Rate option 2 1 Press to enter the selection routine The current setting will flash 2 2 Use and buttons to choose Baud rate 2 4k 4 8k 9 6k 19 2k 38 4k On completion of the entry procedure press to confirm the ...

Страница 18: ...ty 1 From the Set up menu use and buttons to select the Parity option 2 1 Press to enter the selection routine The current setting will flash 2 2 Use and buttons to choose Parity EVEN ODD NONE Default is NONE On completion of the entry procedure press to confirm the setting and press to return to the main set up menu Stop bits 1 From the Set up menu use and buttons to select the Stop Bit option ...

Страница 19: ...op Bit 2 or 1 On completion of the entry procedure press to confirm the setting and press to return to the main set up menu Note Default is 1 and only when the parity is NONE that the stop bit can be changed to 2 CLR The meter provides a function to reset the maximum demand value of current and power 1 From the Set up menu use and buttons to select the reset option 2 Press to enter the selection r...

Страница 20: ...t inputs correction set up 1 use and buttons to select page SET sys cont 2 1 Press to enter Phase A the default is Frd forward 2 2 use and buttons to Phase B or C setting pages How to operate if phase A is reversely connected 1 Go to phase A setting page 2 Press to enter the selection routine The Frd will flash Use button to change Frd to Rev Press to confirm the setting and press to return to the...

Страница 21: ...Power 0 to 3600 MW Reactive Power 0 to 3600 MVAr Volt amps 0 to 3600 MVA Maximum demanded power since last Demand reset Power factor Maximum neutral demand current since the last Demand reset for three phase supplies only Energy Measurements Imported Exported active energy 0 to 9999999 9 kWh Imported Exported reactive energy 0 to 9999999 9 kVarh Total active energy 0 to 9999999 9 kWh Total reactiv...

Страница 22: ...unit provides two pulse outputs Both pulse outputs are passive type Pulse output 1 is configurable The pulse output can be set to generate pulses to represent total kWh or kVarh The pulse constant can be set to generate 1 pulse per 0 01 10 Wh VArh 0 1 100 Wh VArh 1 1 kWh kVarh 10 10 kWh kVarh 100 100 kWh kVarh 1000 1000 kWh kVarh Pulse width 200 100 default 60ms Pulse output 2 is non configurable ...

Страница 23: ...ply voltage Nominal 1 Auxiliary supply frequency Nominal 1 Auxiliary supply waveform if AC Sinusoidal distortion factor 0 05 Magnetic field of external origin Terrestrial flux Environment Operating temperature 25 C to 55 C Storage temperature 40 C to 70 C Relative humidity 0 to 90 non condensing Altitude Up to 2000m Warm up time 3S Vibration 10Hz to 50Hz IEC 60068 2 6 2g Shock 30g in 3 planes Dime...

Страница 24: ...A User Manual V1 1 Address No 1369 Chengnan Road Jiaxing Zhejiang 314001 China Tel 0086 573 83698881 83698882 Fax 0086 573 83698883 Web www eastron com cn 23 Installation 3 Phase 4 Wire for SDM630MCT RJV 3 Phase 4 Wire for SDM630MCT RJA ...

Отзывы: