15
3.6 Power Cables
3.6.1 Specifications
The UPS power cables are recommended in Table 3.3.
Table 3.3 Recommended cables for power cables
Contents
10kVA
15kVA
20kVA
30kVA
Main Input
Main Input Current(A)
20A
29A
39A
58A
Cable Section
(
mm²
)
A
6
6
10
16
B
6
6
10
16
C
6
6
10
16
N
6
6
10
16
Main Output
Main Output Current(A)
15A
23A
30A
45A
Cable Section
(
mm²
)
A
6
6
10
16
B
6
6
10
16
C
6
6
10
16
N
6
6
10
16
Bypass Input
(
Optional
)
Bypass Input Current(A)
15A
23A
30A
45A
Cable Section
(
mm²
)
A
6
6
10
16
B
6
6
10
16
C
6
6
10
16
N
6
6
10
16
Battery Input
Battery Input current(A)
53A
50A
66A
106A
Cable Section
(
mm²
)
+
10
10
16
25
-
10
10
16
25
N
10
10
16
25
PE
Cable Section
(
mm²
)
PE
6
6
10
16
Note
The recommended cable section for power cables are only for situations described below
:
Ambient temperature
:
30
℃
.
AC loss less than 3%
,
DC loss less than 1%
,
The length of the AC power cables are no longer
than 50 m and the length of the DC power cables are no longer than 30 m.
Currents listed in the table are based on the 208V system (Line-to-line voltage).
The size of neutral lines should be 1.5~1.7 times the value listed above when the predominant
load is non-linear.
3.6.2 Specifications for Power Cables Terminal
Specifications for power cables connector are listed as Table 3.4.
Содержание EA990RT G5 10
Страница 4: ......