background image

 

-16- 

3.  After  selecting  “Confirm”,  press  the  key  “

”  momentarily  to  save  the 

interface (by reference to “save and exit setting”). Press the key “

” or “

” 

momentarily, choose “Yes”, and then press the key “

” momentarily to save 

and exit it. 

5.2    Frequency setting 

         

 

1.  The left figure shows the frequency setting interface of rack UPS, and the right 

figure shows the frequency setting interface of tower UPS. 

2.  Press  the  function  setting  key  “

”  for  more  than  5  seconds  to  enter  the 

setting interface. Press the key “

” momentarily to select the output voltage 

standard setting interface. Press the  key  “

”  or  “

”  momentarily  to  select 

the frequency. Available frequency values are 50Hz and 60Hz the frequency is 

50Hz by default.   

3.  After  selecting  “Confirm”,  press  the  key  “

”  momentarily  to  save  the 

interface (by reference to “save and exit setting”). Press the key “

” or “

” 

momentarily, choose “Yes”, and then press the key “

” momentarily to save 

and exit it. 

5.3    Boost charge voltage 

         

 

 

 

-17- 

1.  The  left  figure  shows  the  boost  charge  voltage  interface  of  rack  UPS,  and 

the right figure shows the boost charge voltage interface of tower UPS. 

2.  Press the function setting key “

”  for  more  than  5  seconds  to  enter  the 

setting  interface.  Press  the  key  “

”  momentarily  to  select  the  equalizing 

charge  voltage  interface.  The  equalizing  charge  voltage  cannot  be  set 

through the panel. It is 14.4V by default. 

5.4    Floating charge voltage 

         

 

1.  The left figure shows the floating charge voltage interface of rack UPS, and the 

right figure shows the floating charge voltage interface of tower UPS. 

2.  Press  the  function  setting  key  “

”  for  more  than  5  seconds  to  enter  the 

setting  interface.  Press  the  key  “

”  momentarily  to  select  the  equalizing 

charge voltage interface. The floating charge voltage cannot be set through the 

panel. It is 13.7V by default. 

5.5    Battery end of discharge voltage setting 

         

 

1.  The left figure shows the battery end  of  discharge  voltage  setting  interface  of 

rack  UPS,  and  the  right  figure  shows  the  battery  end  of  discharge  voltage 

setting interface of tower UPS. 

 

Содержание EA610

Страница 1: ......

Страница 2: ......

Страница 3: ...or low above 40 or below 0 and the humidity is high above 90 4 The place having direct sun exposure or close to heating equipment 5 The place where violent vibration occurs 6 Outdoor 3 In case of fire...

Страница 4: ...ials of the machine for convenience of future handling The series of products are very heavy which shall be handled with care 2 1 2 Check whether UPS is damaged during the transportation If any damage...

Страница 5: ...erature of UPS shall be kept between 0 and 40 7 5 It is recommended to charge the battery for 8 hours before using it UPS will charge the battery automatically as long as the input utility power meeti...

Страница 6: ...ery automatically as long as it is connected to the utility power line 3 Installation of rack UPS 9 Vertical installation Combine the connecting extensions and RT foot pieces among the accessories int...

Страница 7: ...1 Press momentarily to enable inverter mute 2 In the utility power mode press momentarily to enable the battery discharge testing for 15 seconds 1 Press the key for 5 seconds to enter the setting int...

Страница 8: ...ery failure utility power failure 13 3 3 LCD display functions Rack LCD Tower LCD Graphics load and battery capacity display area 1 Each grid of the load and battery capacity display area 25 capacity...

Страница 9: ...el shutdown combination button for 3 seconds UPS will enter standby mode rack or bypass mode tower The yellow bypass indicator goes on Then cut off the utility power supply to shut down UPS Shutdown w...

Страница 10: ...5 3 Boost charge voltage 17 1 The left figure shows the boost charge voltage interface of rack UPS and the right figure shows the boost charge voltage interface of tower UPS 2 Press the function setti...

Страница 11: ...ging current is 1A for standard model and 10A for extended runtime model by default 3 After selecting Confirm press the key momentarily to save the interface by reference to save and exit setting Pres...

Страница 12: ...elect ON or OFF the DC self starting function is off by default 3 After selecting Confirm press the key momentarily to save the interface by reference to save and exit setting Press the key or momenta...

Страница 13: ...to exit the state of automatic page up down 1 Output Display UPS output voltage and output frequency as shown below the left figure shows the display interface of rack UPS and the right figure shows...

Страница 14: ...shutdown It can be set 3 load to shut down after 80s transfer time 10ms THDV resistive load 5 Inductive load Yes Capacitive load Yes Resistive load Yes Protection Overload short circuit battery low v...

Страница 15: ...collected too much dust or not 4 Check whether the input output and battery cables are firm or not and whether the cable insulation is good or not 5 Ensure UPS is well protected against moisture 6 St...

Страница 16: ...battery terminals are firmly fastened 29 9 Exception Handing Carry out the self checking according to the following methods in case of abnormal conditions If the abnormal condition cannot be eliminat...

Отзывы: