background image

®

1

STATIONARY BATTERY INSTALLATION  

AND OPERATING INSTRUCTIONS

SAFETY PRECAUTIONS

    Although all valve regulated batteries have the 

electrolyte immobilized within the battery, the 

electrical hazard associated with batteries still exists. 

Work performed on these batteries should be 

done with the tools and the protective equipment 

listed below.

 VRLA battery installations should be 

supervised by personnel familiar with batteries and 

battery safety precautions.

  

WARNING: Risk of fire, explosion or burns. Do not 

disassemble, heat above 65°C, or incinerate

.

IN REFERENCE TO THIS MANUAL:

– “Battery” is defined as an individual 12-volt unit.

–  “Battery string” is defined as a series connected 

electrical system comprised of batteries 

(individual 12-volt units).

Protective Equipment

  

Although VRLA batteries can vent or leak small 

amounts of electrolyte, electrical safety is the principle 

but not the only concern for safe handling. Per IEEE 

1188 recommendations, the following minimum set 

of equipment for safe handling of the battery and 

protection of personnel shall be available:

1. 

 Safety glasses with side shields, or goggles, or face 

shields as appropriate. (Consult application specific 

requirements)

2.   Electrically insulated gloves, appropriate for  

the installation.

3.   Protective aprons and safety shoes.
4.   Portable or stationary water facilities in the battery  

vicinity for rinsing eyes and skin in case of contact  

with acid electrolyte.

5.   Class C fire extinguisher.
6.   Acid neutralizing agent.

Содержание Deka unigy I Battery 1

Страница 1: ...tring is defined as a series connected electrical system comprised of batteries individual 12 volt units Protective Equipment Although VRLA batteries can vent or leak small amounts of electrolyte elec...

Страница 2: ...d at the time of actual unloading each package should be visually inspected for any possible damage or electrolyte leakage If either the entire shipment should be conducted and noted on the bill of la...

Страница 3: ...ompleted for each refresh charge 8 Batteries shall not be stored beyond 12 months Storing beyond 12 months will affect warranty 9 If the storage refresh requirements cannot be met contact the East Pen...

Страница 4: ...East Penn Mfg Safe installation of any venting equipment is the responsibility of the installer BATTERY ASSEMBLY ALWAYS WEAR EYE PROTECTION 1 Set up the battery string so that the positive post of one...

Страница 5: ...rify that the installer did torque all connections properly to 100 in lb 5 Micro ohm readings should be taken across every connection Refer to meter manufacturer s instructions for proper placement of...

Страница 6: ...an 20 from initial readings taken retorque the connection Retourque value is equal to initial torque value as indicated in BATTERY ASSEMBLY section Recheck the micro ohm reading If the reading remains...

Страница 7: ...tery 2 Battery 3 Battery 4 Battery 5 Battery 6 Battery 7 Battery 8 Battery 9 Battery 10 Battery 11 Battery 12 Battery 13 Battery 14 Battery 15 Battery 16 Battery 17 Battery 18 Battery 19 Battery 20 Ba...

Страница 8: ...84 2 28 13 46 14 36 82 4 27 13 48 14 38 80 6 26 13 49 14 39 78 8 25 13 50 14 40 77 0 24 13 51 14 41 75 2 23 13 52 14 42 73 4 22 13 54 14 44 71 6 21 13 55 14 45 69 8 20 13 56 14 46 68 0 19 13 57 14 47...

Страница 9: ...VR30 5 1 1 5 12AVR40 6 7 2 0 12AVR75 13 4 4 0 12AVR90 15 5 4 7 12AVR100 17 9 5 4 12AVR130 23 6 7 1 12AVR100ET 17 6 5 3 12AVR145ET 26 3 7 9 12AVR150ET 27 1 8 1 12AVR170ET 30 8 9 3 12AVR200ET 38 3 11 5...

Страница 10: ..._______________________________________________ Readings should be taken at installation and annually thereafter _________________________________________________________________________________ 1 41...

Страница 11: ...11 P a g e I n t e n t i o n a l l y B l a n k...

Страница 12: ...duced electronically or mechanically without written permission from the company E P M Form No 0902 02 22 2022 by EPM Printed in U S A East Penn Manufacturing Co Lyon Station PA 19536 0147 Phone 610 6...

Отзывы: