42
9 START-UP AND CONFIGURATION
The unit should be configured by the installer to match the installation environment (outdoor climate, installed options, etc.) and
user expertise.
It is important that all information in this chapter is read sequentially by the installer and that the system is configured as
applicable.
CAUTION
9.1 Climate related curves
The climate related curves can be selected in the user interface. Once the curve is selected, the target water flow temperature
in each mode is calculated by the curve.
It’s possible to select curves even dual room thermostat function is enabled.
The relationship between outdoor temperature (T4/°C) and the target water temperature(T1S/°C) is described in the tables and
pictures. )
Temperature curves for heating mode and ECO heating mode
T4H1
T4H2
T1SETH2
T1SETH1
T4
T1S (T1S2)
The automatic setting curve
The automatic setting curve is the ninth curve,the ninth curve can be set as following:
State:In the setting the wired controller, if T4H2<T4H1, then exchange their value; if T1SETH1<T1SETH2, then
exchange their value.
T4
≤ - 20
- 19
- 18
- 17
- 16
- 15
- 14
- 13
- 12
- 11
- 10
- 9
- 8
- 7
- 6
- 5
- 4
- 3
- 2
- 1
0
1- T1S
38
38
38
38
38
37
37
37
37
37
37
36
36
36
36
36
36
35
35
35
35
2- T1S
37
37
37
37
37
36
36
36
36
36
36
35
35
35
35
35
35
34
34
34
34
3- T1S
36
36
36
35
35
35
35
35
35
34
34
34
34
34
34
33
33
33
33
33
33
4- T1S
35
35
35
34
34
34
34
34
34
33
33
33
33
33
33
32
32
32
32
32
32
5- T1S
34
34
34
33
33
33
33
33
33
32
32
32
32
32
32
31
31
31
31
31
31
6- T1S
32
32
32
32
31
31
31
31
31
31
31
31
30
30
30
30
30
30
30
30
29
7- T1S
31
31
31
31
30
30
30
30
30
30
30
30
29
29
29
29
29
29
29
29
28
8- T1S
29
29
29
29
28
28
28
28
28
28
28
28
27
27
27
27
27
27
27
27
26
T4
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
≥ 20
1- T1S
35
35
34
34
34
34
34
34
33
33
33
33
33
33
32
32
32
32
32
32
32
2- T1S
34
34
33
33
33
33
33
33
32
32
32
32
32
32
31
31
31
31
31
31
31
3- T1S
32
32
32
32
32
32
31
31
31
31
31
31
30
30
30
30
30
30
29
29
29
4- T1S
31
31
31
31
31
31
30
30
30
30
30
30
29
29
29
29
29
29
28
28
28
5- T1S
30
30
30
30
30
30
29
29
29
29
29
29
28
28
28
28
28
28
27
27
27
6- T1S
29
29
29
29
29
29
28
28
28
28
28
28
27
27
27
27
27
27
26
26
26
7- T1S
28
28
28
28
28
28
27
27
27
27
27
27
26
26
26
26
26
26
25
25
25
8- T1S
26
26
26
26
26
26
26
25
25
25
25
25
25
25
25
24
24
24
24
24
24
1. when EVU signal is on, the unit operate as below:
DHW mode turn on, the setting temperature will be changed to 70
ć
automatically, and the TBH operate as below:T5<69. the TBH is on,
T5 ≥ 70, the
TBH is off. The unit operate in cooling/heating mode
as the normal logic.
2. When EVU signal is off, and SG signal is on, the unit operate
normally.
3. When EVU signal is off, SG signal is off, the DHW mode is off, and
the TBH is invalid, disinfect function is invalid. The max running time for
cooling/heating is "SG RUNNIN TIME", then unit will be off.
V.2