AC Wire Assembly and Connection
Danger to Life due to High Voltages in the Inverter
Before connecting any electrical wires and components, please ensure the DC switch & AC circuit
breaker are switched OFF and cannot be reactivated.
DANGER
DC Wire Assembly and Connection
Meeting the following requirements is mandatory. All warranty rights will otherwise be invalid.
3.3.1 Maximum open voltage of each string is less than 1100V.
3.3.2 Maximum short circuit current of each PV input is less than inverter allowable limit.
3.3.3 The string is well insulated to ground in all cases.
3.3.4 Make sure that the DC connectors have the correct polarity.
3.3.5 If the PV connectors are not assembled properly and locked into place, arc or overheat may be
induced.
3.3
Step 1
Step 2
Step 3
1. The inverter and mounting bracket have been correctly installed. 2. The inverter’s exposed metal
surface has a ground connection. 3. The resistance between PV arrays and ground is greater than
1Mohm. 4. For any unused DC terminals, there are DC connectors inserted to the terminal and
sealed with waterproof caps. 5. The grid voltage at the point of connection of the inverter is within
the permitted range. 6. The AC circuit breaker must be correctly rated and wired. 7. The cable
communication connectors have been correctly wired and tightened.
Startup
Switch on the DC switch after finishing the above checks, then switch on the AC circuit breaker.
When there is sufficient DC power applied and the grid conditions are met, the inverter will start to
operate automatically.
4.
Commissioning
Please check if:
RS485/Smart Meter and DRED Connection
NOTICE
For AS/NZS 4777, DRM0 is supported.
Make sure the cover and the communication cable gland has been mounted properly and adequately
Step 1
Step 2
Wi-Fi/GPRS Connection (Optional)
The stick is included in the scope of delivery as an option.
3.4.1 Tighten the stick into the COM1 port.Make sure the stick
is securely connected.
3.4.2 For the connection and configuration of the Wi-Fi stick
please refer to <Wi-Fi stick User manual> .
3.4
Step 3
Step 4
GUIDEWAY
2
3
1
4
Use the right sealing ring
according to the diameter of
the cable
1
2
3
4
Press the cable into the appropriate terminal.
Use a screwdriver to lock the cable to the
corresponding position and tighten the
screws on the box following the indicated
sequence (1~4)
Assemble the box,
threaded sleeve and swivel
nut together
Step 1
Step 3
Step 4
Step 5
Step 6
click
click
7mm
7mm
PV1-F/UL-ZKLA/USE2
PV1-F/UL-ZKLA/USE2
Assemble the connectors
2.6-2.9 N·m
Positive
Negative
Assemble the
D4
cable ends
Positive terminal
Negative terminal
Crimp pliers to cable ends
Note: Don't crimp this part!
Step 2
Assemble the
MC4
cable ends
Positive terminal
Negative terminal
4-6mm
2
16mm
2
6mm
2
Approx. 10 mm
RS485 B1
RS485 A2
RS485 B2
RS485 A1
PIN1
PIN2
PIN3
PIN4
RS485 FOR COM2
Meter or DRED FOR COM3
COMLOAD/0
RS485 A
RS485 B
REF GEN/0
PIN1
PIN2
PIN3
PIN4
Pull out the plastic rivet
and remove the plastic
sheet
Please check if the cables are securely
installed by pulling outwards
Strip off the insulation
Check the polarities of the PV strings
Check the open-circuit voltage is less
than inverter input limit 1100V
Remove the waterproof
caps from PV terminals
If there is an unused terminal,
please seal it with the cap
Insert the connector into the terminal
till you hear an audible click
For more information, please download the user manual and other technical documents at www.easelectric.es
EAS ELECTRIC SMART TECHNOLOGY, S.L.
Address: P.I. Codonyers, C/Principal, 4 46220 Picassent (Valencia, SPAIN)
Insert the wires into suitable ferrules (DIN
46228) and crimp
Insert the crimped conductors accordingly into their corresponding terminals and tighten the screws
Assemble the locking cap, threaded
sleeve and swivel nut together.
Screw the connector into the socket and tighten firmly.
Note: Please ensure that the connector has been correctly installed!