Page 9
SKU 97925, 99676
For technical questions, please call 1-800-444-3353.
ity of the cord. For example, a 14 gauge cord can carry a higher current than a 16
gauge cord.
(see table a.)
When using more than one extension cord to make up the total length, make sure
3.
each cord contains at least the minimum wire size required.
(see table a.)
If you are using one extension cord for more than one tool, add the nameplate
4.
am-
peres and use the sum to determine the required minimum cord size.
(see table
a.)
If you are using an extension cord outdoors, make sure it is marked with the suffix
5.
“W-A” (“W” in Canada) to indicate it is acceptable for outdoor use.
Make sure the extension cord is properly wired and in good electrical condition.
6.
Always replace a damaged extension cord or have it repaired by a qualified electri
-
cian before using it.
Protect the extension cords from sharp objects, excessive heat, and damp or wet
7.
areas.
reCommended minimum wire gauge For eXtension Cords*
(120/240 Volt)
nameplate
amperes
(at full load)
eXtension Cord length
25 Feet
50 Feet
75 Feet
100 Feet
150 Feet
0 – 2.0
18
18
18
18
16
2.1 – 3.4
18
18
18
16
14
3.5 – 5.0
18
18
16
14
12
5.1 – 7.0
18
16
14
12
12
7.1 – 12.0
18
14
12
10
-
12.1 – 16.0
14
12
10
-
-
16.1 – 20.0
12
10
-
-
-
taBle a
* Based on limiting the line voltage drop to five volts at 150% of the rated amperes.
symbology
Double Insulated
V~
Volts Alternating Current
Canadian Standards Association
a
Amperes
Underwriters Laboratories, Inc.
n0 xxxx/min.
No Load Revolutions per Minute
(RPM)