HCM-410CP-IM (12/15)
Page 4
The dimensions data for the Hybrid Cooling Module is shown in Figure 1.
Dimensions,
Inches
Connections
Tube, OD,
inches
Sound,
dB(A)
Net
Weight,
Lbs
Coil
H
W
D
Inlet
Outlet
Rows Fins/inch
Face Area,
Sq Ft
25-7/8
36
17-3/8
7/8
7/8
52.0
95
2
15
7.0
Fan
Electrical
Type
CFM
RPM
Dia., inches
Power
Fan HP
Fan FLA
Min Voltage
Swept
1,800
810
20
230-1-60
1/6
1.0
207
Figure 1. Hybrid Cooling Module Dimensions and Data