2. EarthLinked
®
Commercial Water Heating Applications
Figure 2a illustrates a typical installation of a GSTE storage water heater with a commercial
water heating compressor unit. Location of the tank from the compressor unit is to be no more
than 10 ft. apart. Water piping and connections between the compressor unit and tank are all
1-1/2” Type L copper. Hot water supply to the system is out the top of the tank as shown.
Details for the ports and connections on top of the tank are shown in Figure 2b. The electrical
field wiring for the HHK-1872 temperature controller and the storage water heater electric
element and thermostat are illustrated in Figure 2c.
Figure 2a. Commercial Water Heating Application