Speakers.

  The Model 1241 is designed to drive up to four speakers.  Total speaker impedance must be eight (8)

ohms or greater.  (See section 3.2 for wiring diagram.)  If additional speakers are required, or if additional volume is
desired, the Eagle Model 1402 SPEAKER EXPANSION MODULE must be used.

3.6 COMMUNICATOR PROGRAMMING.

When programming the digital communicator, it is advised to begin the "TELEPHONE NUMBER" with "

∗∗

70

" (tone

dialing) or "

1170

" (pulse dialing).  This will allow uninterrupted communication when the subscriber has call waiting.

4.0 ACTIVATION.

4.1 IMMEDIATE TURN ON.

When 

SW5

 is set in the ON position, the module will activate when a trigger is received at the 

TRIP

 terminal.  This

trigger must correspond with the completion of the communicator's alarm report (kiss off from the Central Station).
When  the Two Way audio module is activated in this mode,  the operator, if listening at that time, will hear a two tone
"beep-bop" acknowledgment generated by the module.  This is the operator’s notification that the module is on and
active.  The red LED will illuminate while active.

The operator can control the operation of the module using a  Touch-Tone

 phone per Paragraph 5.0.

4.2 USING RING DETECTOR.

4.2.1 DESCRIPTION.

FULL TIME CALL BACK.

When the ring detector option is selected for the module (

SW4

 is ON), the module will answer in the programmed

number of rings (

SW2

).  When this feature is programmed ON, it is valid at all times, i.e., anytime the phone rings the

programmed 6 or 10 times, the Model 1241 will pick up the line and the red LED will illuminate while active.

FIVE MINUTE WINDOW.

The Model 1241 has a call back mode which activates upon a trip.  The window is initiated from the trip input.  This
sets up the system to answer an alarm which has just been reported by the digital communicator (

SW5

 is OFF).  The

operator will have 5 minutes in which to call back the system and have it answer within one ring.  This feature allows
call back 

only

 within five minutes of an alarm activation.  While active, the red LED will illuminate.

If the five minute call back timer has elapsed, 

SW4

 has been set to activate the system only on the trigger input (OFF)

and 

SW5

 has been set to activate the five minute call back window (OFF), then the system will no longer pick up the

call; no matter how many rings occur.  If 

SW4

 has been set to activate the system both with the trigger input and the

ring detector (ON), 

SW5

 has been set to answer within five minutes of an alarm activation (OFF) and the five minute

call back timer has elapsed, the module will revert to the number of rings programmed using 

SW2

 after the five

minute time-out has expired.

These two features are independent of each other.  That is, the module can be configured to answer the phone in the
programmable 6/10 rings (valid anytime) and/or answer the phone within one ring after an alarm activation (five
minute window).

4.2.2 CALL ANSWERING.

NOTE: The central station receiver must be capable of a “listen-in” function, i.e., the receiver must hold the

phone line open until an operator can pick up the line.

Содержание 1241

Страница 1: ...Manual P N 119503 Rev 6 0 01 95 MODEL 1241 TWO WAY AUDIO MODULE INSTALLATION INSTRUCTIONS LEADERS IN TWO WAY AUDIO TECHNOLOGY ...

Страница 2: ...ON 9 4 1 IMMEDIATE TURN ON 9 4 2 USING RING DETECTOR 9 4 3 MANUAL ACTIVATION HANDS FREE SPEAKERPHONE 10 5 0 CONTROLLING THE MODULE 10 5 1 INTERNAL CONTROLS 12 6 0 OPTIONAL CONNECTIONS 12 7 0 ADDITIONAL INFORMATION 15 7 1 INSTALLATION TIPS 15 7 2 NOTES 15 8 0 FCC REQUIREMENTS 16 TABLE OF DIAGRAMS AND TABLES TABLE 1 SUMMARY OF SWITCH SETTINGS 6 TABLE 2 TERMINAL BLOCK CONNECTIONS 6 DIAGRAM 1 MULTIPLE...

Страница 3: ...l station calls the premises after an alarm activation to initiate Two Way communications This can be used with or without the LINE HOLD mode VOX Two Way communication which automatically switches the ability to talk to the talking party Works like a speakerphone MANUAL CONTROL The opposite of VOX The central station controls who talks and who listens with commands generated from a Touch Tone phon...

Страница 4: ... is independent of SW2 s setting If SW1 is in the DEMO MODE ON then SW2 ON Fast time out of the shut down timer Shuts down in one minute instead of five minutes OFF Normal time out of the shut down timer Shuts down in five minutes There is no recommended setting for SW2 _________________________________________________________________ SW3 ON Activate in the Two Way VOX mode automatic operation OFF...

Страница 5: ... module is required When SW5 is in the OFF position a trigger input will activate a five 5 minute window The 1241 will answer the phone line as soon as it sees one ring within this window The system will ignore any invalid phone calls see section 4 2 When the five minute window expires the system will ignore any additional phone calls unless programmed for call back mode with SW4 Recommended setti...

Страница 6: ...Positive supply input 12 VDC GND 2 Negative supply input Ground TIP 3 Telco Tip premise side brown on RJ 31X RING 4 Telco Ring premise side gray on RJ 31X TRIP 5 Trigger input ANS HGUP 6 Manual Answer Hang up input N C 7 Normally closed relay contact N C 8 Normally closed relay contact MIC1 9 Electret microphone 4 or amplified microphone input selectable MIC POWR 10 Electret microphone supply volt...

Страница 7: ...er output for all electret microphones or any microphone which use 5 VDC for power MIC2 MIC3 and MIC4 These are the inputs for electret microphones Eagle Model 2101 These inputs are amplified on the module Any combination of inputs may be used including terminal MIC1 SHLD This is the ground for all electret microphones This may also be used for a ground connection for a power microphone SPK and SP...

Страница 8: ...INSTALLATION 3 5 1 LOCATION A microphone and speaker can cover a range of up to 2500 square feet This is dependent on the environment in which they are installed Installation is recommended at or near system keypads with a minimum of one per floor excluding basement 3 5 2 SEPARATION It is required to install the microphone and speaker no less than three 3 feet from one another This will prevent an...

Страница 9: ...imes i e anytime the phone rings the programmed 6 or 10 times the Model 1241 will pick up the line and the red LED will illuminate while active FIVE MINUTE WINDOW The Model 1241 has a call back mode which activates upon a trip The window is initiated from the trip input This sets up the system to answer an alarm which has just been reported by the digital communicator SW5 is OFF The operator will ...

Страница 10: ...release 3 3 To switch to Two Way VOX press and release 2 2 To switch to high volume talk only press and release 1 1 The operator can switch back and forth between these modes as often as one wishes independent of the mode in which the module was in when activated The Model 1241 provides five 5 minutes of Two Way During Two Way the module will generate a beep once every minute Upon the fourth and f...

Страница 11: ...C see NOTE 1 MIICROPHONE 2 optional MICROPHONE 3 optional MICROPHONE 4 optional sound discriminators NOTE 1 Terminal 9 can be used in conjuntion with either a 3 pin electret mic or an amplified microphone such as found on some P3 is used to select which type of mic input is being used ON OFF 1 2 3 4 5 6 SW1 SPEAKER VOLUME MICROPHONE VOLUME ANSWER HANGUP INPUT TRIGGER INPUT THE TRIGGER INPUT IS CON...

Страница 12: ... CONTROLS 5 1 1 CENTRAL STATION DETECTION The model 1241 features Eagle s exclusive central station detection This feature allows the audio module to detect a central station receiver dropping off line before an operator picks up on the Two Way line When detected about 15 to 20 seconds post receiver hang up the module will shut itself down and initiate the five minute call back window This feature...

Страница 13: ...IN 1 PIN 3 PIN 5 PIN 4 PIN 6 N C COMM N O N C COMM N O RED BRN ORN GRN YEL BLU 1 2 3 4 5 6 Relay 1 N O Relay 1 N C Relay 1 COM Relay 2 N O Relay 2 N C Relay 2 COM 10 11 12 13 14 15 16 6 PIN HEADER Orange Blue P1 Q1 1401 MODEL SECURITY EAGLE 3 2 1 SWEP 2 3 YELP 1 2 Brown Yellow SPEAKER s 12 VDC FROM CONTROL PANEL GND FROM CONTROL PANEL Blk Red Wht Red 8 Ohm Green 9 P1 CAUTION DO NOT use both the 6 ...

Страница 14: ...dule is in the high gain listen mode and a 2 2 is sent the module will generate the bop tone and will place the module in a regular gain listen only mode The Brown and Red wires on optional cable assembly P N 117006 provide two inputs which completely inhibit Two Way If either of these inhibits are at 5VDC or above when the module is activated the module will not activate P6 SYSTEM CONNECTIONS Use...

Страница 15: ...ol panel 70 or 1170 7 2 NOTES The operation of the system will be greatly enhanced if amplified phone is used at the Central Station When using multiple microphones at the subscriber end be aware that loud background noise picked up by one microphone will drown out the other microphone s It is unwise to switch to the high gain Listen only mode in the presence of loud background noise as that will ...

Страница 16: ...ce to our Company or to one of our authorized agents Service can be obtained at Eagle Security Products Inc 20 North America Drive West Seneca New York 14224 716 674 9192 TECHNICAL SUPPORT HOTLINE 800 926 TECH 8324 HOURS M F 8 AM 6 PM PAGE CALL BACK 6 PM 8 PM or at your local installation company EAGLE SECURITY PRODUCTS MODEL 1241 Complies with Part 68 FCC Rules FCC Registration 1SYUSA 18688 KX N ...

Отзывы: