34
SLB-Series User Manual
External Test
External discharge test means that the load bank does not discharge batteries. Its main function
is to display the values of current clamp and other loads (including battery string). Except
battery total voltage and cell voltage (if connected with DAC), all the other values displayed on
screen are from outside loads. The goal of this test is to use the SLB-Series load bank as a
battery data logger.
To perform external discharge:
1. Select
[External test]
in the
[Other test]
menu
2.
Set discharge parameters as explained in
section 5.2
3. Press the
ENT
button to start the test
Charge Monitor
Charge monitor is a supplemental function for monitoring data when using an external charger
for a battery string. Similar to external testing the SLB is acting as a battery data logger.
To start the charge monitor:
1. Select
[Charge Monitor]
in the
[Other test]
menu
2. Set the following string parameters:
[Strg type]:
Indicates nominal voltage of the battery string
[Cell type]:
Indicates cell voltage
[Cell No.]:
Indicates number of cells
[Time]:
Indicates time to monitor charge
Parameter Settings
3. Set the following monitor parameters
[Clamp type]:
Indicates current rating of clamp
[Tot warn U]:
Indicates upper limit of total voltage
[Cell warn U]:
Indicates upper limit of cell voltage
[1# cell polar]:
Strg type:
48
V
Cell type: 2V
Cell No.:24
Time: 10H 00M