27
SLB-Series User Manual
Discharge Testing
The following section covers steps for performing a discharge test. For an additional tutorial of
the SLB-Series menu, please visit our tutorial video
SLB Menu Walkthrough
Battery String Discharge
Using the keypad and LCD display, press the arrow keys up/down to highlight
[Discharge]
and
press
ENT
to open the discharge test parameter screen.
Battery DIS
DIS test
Continued DIS
Paral load
Discharge Menu
Discharge Test Parameters
There are four system parameters to set for a discharge test. These settings vary slightly
depending on whether or not the test will include the use of DACs.
Discharge Parameters
Use the
left/right
arrow keys to adjust the following values:
[Strg type]:
Refers to the total voltage of the battery string/system
[Cell type]:
Refers to the nominal cell voltage
[Cell No.]:
Refers to the number of cells in the battery string
,
if not using DAC set this
value to “0”
[DIS I]:
Refers to the working current to be applied to the system
After setting the discharge parameters, press the
down
arrow key to progress to the next
screen.
Strg type: 48V
Cell type: 12V
Cell No.: 4 Cell
DIS I: 000.0 A