background image

Product Manual Rosa Thermostat

EAE KNX Rosa Thermostat

Rosa Thermostat PM R1.0

©

EAE Technology

www.eaetechnology.com

Page66 / 77

Parameter

Setting

Description

Activation Difference

(Away from Setpoint)

10...

40

...255 x 0.1K

Additional stage will be activated depends

on temperature difference between current

temperature and setpoint. Given value will

be multiplied with 0.1

Deactivation Difference

(Close to Setpoint)

1...

10

...255 x 0.1K

Additional stage will be deactivated

depends on temperature difference

between current temperature and setpoint.

Given value will be multiplied with 0.1

Controller Algorithm

Hysteresis Override

checked /

unchecked

The controller algoritm will be disabled

when this parameter is selected. When this

parameter is selected, the control signal of

additional stage will be 100% during

activated.

Table 35

4.4.5.4.2

Communication Objects

No

Object Name

Function

Data Type

Flags

51

Additional Heat

Control Value

Send

1 byte

DPT 5.001

CT

Heating actuator will be controlled through this communication object.

Table 36

4.4.5.5

Split Unit

Figure 18

Split unit controller does not directly control temperature, since temperature control is split unit’s

responsibility “Current Temperature” and “Current Setpoint” communication objects should be linked to split

units “Ambient Temperature” and “Setpoint Temperature” communication objects.

Содержание ROSA

Страница 1: ...Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1 0 EAE Technology www eaetechnology com Page1 77 EAE ROSA THERMOSTAT Product Manual Rosa Thermostat...

Страница 2: ...4 1 2Communication Objects 19 4 2 Rockers and Buttons 19 4 2 1 Rockers 20 4 2 2 Push Buttons 30 4 3 Temperature Sensor 39 4 3 1 Parameters 40 4 3 2Communication Objects 42 4 4 Thermostat 43 4 4 1 Par...

Страница 3: ...om Page3 77 4 4 5 4 Fan Coil 64 4 4 5 5 Split Unit 66 4 4 6Cooling Control Main Stages 67 4 4 7Cooling Control Additional Stages 67 4 4 8 Fan Control 68 4 4 8 1 Parameter 68 4 4 8 2Communication Objec...

Страница 4: ...of functional flexibility with integrated programmable switches Buttons on Rosa thermostats can be programmed to control lighting shutter blind drivers speakers make scene calls and mimic panic button...

Страница 5: ...afety Class II EN 61140 Supply Voltage Range Supply Voltage Power Consumption 21 30V DC Supply from EIB KNX line 20 mA 20 mA x 30V Operation LEDs Programming LED for each fold 1 to 5 RGB LEDs for phys...

Страница 6: ...cker 1 value 32768 32768 Send 16 CWT Rocker 1 value 0 4294967295 Send 32 CWT Rocker 1 value 4 byte float Send 32 CWT Button 1 switch On Off 1 CWT Button 1 shutter Up Down 1 CWT Button 1 value 0 1 On O...

Страница 7: ...op Position 1 CWT Button 1 Status On Off 1 CWT 4 Rocker 1 shutter Bottom Position 1 CWT Button 1 shutter Bottom Position 1 CWT 5 Button 2 switch On Off 1 CWT Button 2 shutter Up Down 1 CWT Button 2 va...

Страница 8: ...er Up Down 1 CWT Rocker 2 shutter Send 1 CWT Rocker 2 value 0 255 Send 8 CWT Rocker 2 value 0 65535 Send 16 CWT Rocker 2 value 32768 32768 Send 16 CWT Rocker 2 value 0 4294967295 Send 32 CWT Rocker 2...

Страница 9: ...float Send 32 CWT 11 Rocker 2 shutter Top Position 1 CWT Rocker 2 Status On Off 1 CWT Button 3 shutter Top Position 1 CWT Button 3 Status On Off 1 CWT 12 Rocker 2 shutter Bottom Position 1 CWT Button...

Страница 10: ...tus On Off 1 CWT 16 Button 4 shutter Bottom Position 1 CWT 17 Rocker 3 switch On Off 1 CWT Rocker 3 shutter Up Down 1 CWT Rocker 3 value 0 1 Send 1 CWT Rocker 3 value 0 255 Send 8 CWT Rocker 3 value 0...

Страница 11: ...T Button 5 value 32768 32768 Send 16 CWT Button 5 value 0 4294967295 Send 32 CWT Button 5 value 4 byte float Send 32 CWT 19 Rocker 3 shutter Top Position 1 CWT Rocker 3 Status On Off 1 CWT Button 5 sh...

Страница 12: ...4967295 Send 32 CWT Button 6 value 4 byte float Send 32 CWT 23 Button 6 shutter Top Position 1 CWT Button 6 Status On Off 1 CWT 24 Button 6 shutter Bottom Position 1 CWT 25 Rocker 4 switch On Off 1 CW...

Страница 13: ...top Lamella Adj 1 CWT Button 7 value 0 1 On Off 1 CWT Button 7 value 0 255 Send 8 CWT Button 7 value 0 65535 Send 16 CWT Button 7 value 32768 32768 Send 16 CWT Button 7 value 0 4294967295 Send 32 CWT...

Страница 14: ...65535 Send 16 CWT Button 8 value 32768 32768 Send 16 CWT Button 8 value 0 4294967295 Send 32 CWT Button 8 value 4 byte float Send 32 CWT 31 Button 8 shutter Top Position 1 CWT Button 8 Status On Off 1...

Страница 15: ...nable 1 CW 61 Heat Control Value On Off 1 CT Heat Control Value 0 100 Send 8 CT Heat Cool Control Value On Off 1 CT Heat Cool Control Value 0 100 Send 8 CT 62 Cool Control Value On Off 1 CT Cool Contr...

Страница 16: ...True False 1 76 Away Status True False 1 77 Protect Status True False 1 78 Regulation Status On Off 1 79 Setpoint Comfort C F Temperature 16 CW Setpoint Heating Comfort C F 80 Setpoint Night C F Temp...

Страница 17: ...Away Status C F 88 Setpoint Cooling Comfort Status C F Temperature 16 CRT 89 Setpoint Cooling Night Status C F Temperature 16 CRT 90 Setpoint Cooling Away Status C F Temperature 16 CRT Table 1 4 Param...

Страница 18: ...2 25s 3 25s LEDs on duration when status LEDs used as operation indication with rocker or buttons Touch Feedback Light Duration after button release 0 3000 ms LED indication duration after releasing...

Страница 19: ...ed to this communication object 49 Window Status Open Close 1 bit DPT 1 009 CW If window status enabled this communication object will be used to detect window status If window detected as open thermo...

Страница 20: ...es different parameters and communication objects that will be explained in the following chapters Parameter Setting Description Rocker Operation Rocker 2 Push Button Selects the function of rocker Ro...

Страница 21: ...ED is always On Status Indication Status LED of last pressed rocker button is on other rocker button is off If Separate Comm Object parameter selected as Enable status LEDs will wait for confirmation...

Страница 22: ...tton pressed shorter than time period specified in Long Press Duration parameter rocker button will act as a switch In switch mode rocker buttons will behave as normal switches as explained in Chapter...

Страница 23: ...e time interval to send dimming increase decrease values Function of LED LED Permanently Off LED always off LED Permanently On LED always on Status Indication Status LED of last pressed rocker button...

Страница 24: ...object 3 Rocker 1 Status Comm Obj On Off 1 bit DPT 1 002 CWT Confirmation for On Off switch telegrams will be received from this communication object If these communication object visible it must link...

Страница 25: ...shutter will start moving upwards until it reaches Top Position or STOP telegram transmittedusing Rocker1 STOP LamellaAdj communicationobjectbyshortpressing Up Button or Down Button When Down Button l...

Страница 26: ...buttons 5 Operation Indication StatusLEDofthepressed rocker button will be on for the time period selected at Light Duration of LED parameter at General tab Long Press Duration 300ms 400ms 500ms 600ms...

Страница 27: ...Control Type parameteris Blind Roller Awning only used for stopping blind movement 3 Rocker1 Top Position True False 1 bit DPT 1 002 CWT This communication object should be linked to an appropriate gr...

Страница 28: ...0 65535 4 byte float value 4 byte value 0 4294967295 Select data type Left Button of Rocker Value 0 1 Visiblewhen DataType selected as 1 bit value Value 0 255 Visiblewhen DataType selected as 1 byte...

Страница 29: ...n Data Type selected as 2 byte value 0 65535 Button 1 value 4 byte float Send 4 byte DPT 14 068 CWT Enabled when Data Type selected as 4 byte value floating point Button 1 value 0 4294967295 Send 4 by...

Страница 30: ...erentoperations and 1 function to disable push button NoFunction Operation selection can be configured from Push Button N N Push button number tab visible when Rocker Operation selected as 2 Push Butt...

Страница 31: ...ction of LED LED permanently Off LED always Off LED permanently On LED always On Status Indication Last transmitted command on LED on Last transmitted command off LED off If Separate Comm Object enabl...

Страница 32: ...t parameter Table 17 4 2 2 2 Switch andDim Figure 9 When push button function selected as Switch and Dim push button can be configured in three different ways to control brightness value Short Press L...

Страница 33: ...5 12 5 6 25 3 13 1 56 VisiblewhendimmingtypeisStepWise Selects the dimming resolution that will be sending at every Step Send Interval Step Send Interval 300ms 400ms 500ms 600ms 800ms 1s 1 2s 1 5s 2s...

Страница 34: ...ddress Otherwise status LEDs will not function correctly If status confirmation not to be used the communication object should be disabled by Separate Comm Object parameter Table 20 4 2 2 3 Shutter Fi...

Страница 35: ...ressed it will toggle its last state If push button short pressed while the blind is moving upward or downward Short Press will stop the blind if the blind is not moving Short Press will adjust the la...

Страница 36: ...be on for the time period selected at Light Duration of LED parameter at General tab Long Press Duration 300ms 400ms 500ms 600ms 800ms 1s 1 2s 1 5s 2s 3s 4s 5s 6s 7s 8s 9s 10s Timeintervaltoswitchfrom...

Страница 37: ...etting Description Function of Led LED Permanently Off LED always off LED Permanently On LED always on Operation Indication Status LED of the pressed rocker button will be on for the time period selec...

Страница 38: ...Data Type selected as 4 byte value float value Value 0 4294967295 Visible when Data Type selected as 4 byte value 0 4294967295 Long Press Request No Yes Enable Disable long press duration Long Press D...

Страница 39: ...Long Press Data Type selected as 2 byte value 0 65535 Integer Part 128 0 127 Visible when Long Press Data Type selected as 4 byte value float value Fractional Part 0 99 Visible when Long Press Data Ty...

Страница 40: ...ure selected as Cyclic and Change Selects minimum change in temperature that will trigger transmission of temperature Temperature Measurement Internal Sensor Temperature info can be taken from interna...

Страница 41: ...elsius Spot sensor temp unit can be set as desired If the Same is selected the temp unit will be the same as well as Main Temperature Unit Fahrenheit Same Heat Limit Temperature 0 28 255 K Heat Protec...

Страница 42: ...s DPT should be decided according to the selected temperature unit Temperature telegrams will be sent when a temperature change defined at Minimum Difference parameter occurs or cyclic time period ove...

Страница 43: ...ould be entered here 4 4 1 Parameters Parameter Setting Description Control Mode Heat Cool Heat Cool Heat with Additional Stage Cool with Additional Stage Heat Cool with Heat Additional Stage Heat Coo...

Страница 44: ...e switchover is automatic or Heating or Cooling control will be shut down until the Control Mode change manually DPT Switchover Object 1 Bit DPT_Heat Cool 1 Byte DPT_HVAC_Control_Mode Selects the cont...

Страница 45: ...T 64 Switchover Status Control Mode 0 Cooling 1 Heating 1 bit DPT 1 100 CRT When Switchover Type is Automatic acts as a status communication object and sends current control mode telegram from this co...

Страница 46: ...he system smaller KI value should be Note finding optimum values for a specific room might require some trial and error Using default values as a referencepointandincreaseanddecreasingthesevaluesaccor...

Страница 47: ...s Additional stages can be combined with 5 different ways which are heating with additional heating cooling with additional cooling heat cool with additional heating heating cooling with additional co...

Страница 48: ...g Control Main Stages Selection of the heating control type parameters of the selected control type should be configured here 5 Heating Control types are available which are PI Continuous PI PWM On Of...

Страница 49: ...trol Signal 0 100 Maximum control signal value Minimum Control Signal 0 100 Minimum control signal value Spot Heat Protection checked unchecked This parameter enables the Heat Protection via using Spo...

Страница 50: ...troller Algorithm is selected as Alternative PI Reverse Differential Action Band given value multiplied by 0 1 Table 29 4 4 4 1 2 Communication Objects No Object Name Function Data Type Flags 61 Heat...

Страница 51: ...t Temperature sensor must be enabled in Temperature Sensor page to show this parameter Controller Algorithm PID Alternative PI Controller algorithm can be selected via using this parameter Proportiona...

Страница 52: ...s Chapter 4 4 3 1 2 Minimum Control Signal should be bigger than 120 100 10 60 20 PWM cycle configured as 20 minutes Minimum Control Signal should be bigger than 120 100 20 60 10 4 4 4 2 2 Communicati...

Страница 53: ...10 K 1 10 255 Hysteresis value Chapter 4 4 3 1 3 Spot Heat Protection checked unchecked This parameter enables the Heat Protection via using Spot Temperature Sensor Spot Temperature sensor must be ena...

Страница 54: ...trol Signal 0 100 Maximum control signal value Minimum Control Signal 0 100 Minimum control signal value Spot Heat Protection checked unchecked This parameter enables the Heat Protection via using Spo...

Страница 55: ...mperature since temperature control is split unit s responsibility CurrentTemperature and CurrentSetpoint communicationobjectsshouldbelinkedtosplit units Ambient Temperature and Setpoint Temperature c...

Страница 56: ...3 Split Heat Error True False 1 bit DPT 1 002 CW Visible if Communication Error Object parameter enabled True telegram causes the thermostat to enter Protect Mode wit Error and thermostat stay in this...

Страница 57: ...Control Signal 0 100 Maximum control signal value Minimum Control Signal 0 100 Minimum control signal value Spot Heat Protection checked unchecked This parameter enables the Heat Protection via using...

Страница 58: ...e activated depends on temperature difference between current temperature and setpoint Given value will be multiplied with 0 1 Deactivation Difference Close to Setpoint 1 10 255 x 0 1K Additional stag...

Страница 59: ...iption Control Value Normal Inverse Invert the output of the controller For example if normal output is 1 then inverted output is 0 PWM period 1 10 255 min This parameter determines PWM period Signal...

Страница 60: ...the Controller Algorithm is selected as PID Proportional Gain KP 1 66 255 This parameter shown when the Controller Algorithm is selected as Alternative PI Proportional gain of PI algorithm Integral Ga...

Страница 61: ...parameter is selected the control signal of additional stage will be 1 during activated Table 31 4 PWM Cycle and Minimum Control Signal parameters should be configured considering the limitations of...

Страница 62: ...Additional Heating Control Value communication object Hysteresis 1 10 K 1 10 255 x 0 1K Hysteresis value Chapter 4 4 3 1 3 This parameter will be enabled If the Additional Stage Activation is selected...

Страница 63: ...tpoint 1 10 255 x 0 1K Additional stage will be deactivated depends on temperature difference between current temperature and setpoint Given value will be multiplied with 0 1 Table 33 4 4 5 3 2 Commun...

Страница 64: ...r read Chapter 4 4 3 1 4 4 4 5 4 1 Parameters Parameter Setting Description Control Value Normal Inverse Invert the output of the controller For example if normal output is 80 then inverted output is...

Страница 65: ...hm PID Alternative PI Disabled Controller algorithm can be selected via using this parameter Proportional Band 1 30 255 x 0 1 C This parameter shown when the Controller Algorithm is selected as PID Ti...

Страница 66: ...ith 0 1 Controller Algorithm Hysteresis Override checked unchecked The controller algoritm will be disabled when this parameter is selected When this parameter is selected the control signal of additi...

Страница 67: ...etpoint 10 40 255 x 0 1K Additional stage will be activated depends on temperature difference between current temperature and setpoint Given value will be multiplied with 0 1 Deactivation Difference C...

Страница 68: ..._Enable 0 Enable 1 Disable Telegram value to enable automatic fan speed might differ between different actuators use this parameter to change the telegram value for enabling automatic fan speed DPT Fa...

Страница 69: ...peed 1 Enable 1 bit CWT DPT 1 002 Fan Speed communication object visible when Fan Speed Object Type is 1 byte and fan speed controlled and status received with given values 0 Fan Speed 0 1 Fan Speed 1...

Страница 70: ...Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1 0 EAE Technology www eaetechnology com Page70 77 4 5 Setpoints Figure 25...

Страница 71: ...ed unchecked This parameter is limitting the Setpoint changes Allowed Range 1 5 30 K This parameter is shown when the Setpoint Range Limiting is selected Given value will be applied plus and minus sid...

Страница 72: ...Fan Speed Auto Fan Speed 1 2 3 Fan speed value can be set for Night Mode AWAY MODE Setpoint 0 21 99 C F This parameter allows to set default Setpoint Temperature of Comfort Mode Setpoint Heating 0 21...

Страница 73: ...nication object when the room temperature has changed or cyclically configured Temperature Sensor tab 56 Current Setpoint C Temperature 2 byte DPT 9 001 CRT Current Setpoint F Temperature 2 byte DPT 9...

Страница 74: ...etpoint Night communication object If Multi Setpoint is enabled Setpoint will be changed by Setpoint Heating Night group object 81 Setpoint Away C Temperature 2 byte DPT 9 001 CW Setpoint Away F 2 byt...

Страница 75: ...001 Setpoint Heating Comfort Status F 2 byte DPT 9 027 Setpoint temperature for Comfort mode can be transmitted read using the Setpoint Comfort Status communication object If Multi Setpoint is enabled...

Страница 76: ...ject 88 Setpoint Cooling Comfort Status C Temperature 2 byte DPT 9 001 CRT Setpoint Cooling Comfort Status F 2 byte DPT 9 027 If Multi Setpoint is enabled Setpoint will be transmitted read by Setpoint...

Страница 77: ...uttons on thermostat Fan Speed Button Enable Disable Enable Disable fan speed button on thermostat Operating Mode Button Enable Disable Enable Disable operating mode button on thermostat Table 53 When...

Отзывы: