1-Standards & Certification:

2- General Structure of Products:

Electrical Characteristics:

2.2- Housing and Structure:

- Busbar system shall be designed and manufactured as per IEC 60439-2 standard.
Each individual rated busbar shall have separate type test certificate from an
independent internationally accredited laboratory.
-

- Busbar system shall have CE marking.
- Each product shall have a “Type Label”, which indicates the brand, type of the unit,
conductor number and electrical details

- Busbar system shall be Air-Insulated and Plug-in type. Aluminium or Copper conductors
shall be tin plated along the entire length. Housing shall be galvanized steel or if required
RAL 7038-Electrostatic painted.

- Busbar systems nominal insulation voltage shall be 1000V.
- As per ampere rates, minimum short circuit values shall be like below;

Temperature rise shall be maximum 50K over 40°C ambient temperature

for both tin plated Aluminium and Copper conductor busbars.

160A

:

250 and 315A :
400 and 500A :
600A and above:

- Busbar system shall be of air insulated type. The bars shall be supported by insulators
installed into the housing at every 25 cm.
- On a three meter standard length busbar the distance between the plug-in points on
one side shall be 50cms. The points shall be on both sides of the busbar making the
average distance of plug-in points 25cm.

.

2.1-

-

Manufacturing facility of busbar systems shall have ISO 9001 and ISO 14001

certification.

- To prevent wrong alignment of the phase sequence during installation there shall be
mechanical barriers on the joint that shall ensure correct mounting.
- IP Plug-in covers of the busbar system should be hinged.Plug-in windows shall have
automatic shutter system. This shutter shall open automatically when the earth contact of
tap-off box is inserted.
- Busbar system shall have all necessary accessories (elbows, offsets, panel-transformer
connections, reductions, etc). Manufacturer shall supply special dimensioned units in
short time, if the project conditions requires.
- For horizontal runs, a horizontal expansion unit shall be used at every 40m and expansion
points of the building.
- For vertical applications, a vertical expansion unit shall be used at every floor. Busbar
system shall be rigidly fixed by supports at every floor.

- Busbar system shall have Nickel and Tin-plated 6101 class aluminium conductors (160-

600A). / Busbar system shall have Tin-plated Electrolytic copper conductors (250-800A).
- Busbar system shall have below number of conductors and phase configuration;

a) 4 Conductors:(4 full size cond Housing ( earthing )
b)

(4 full size cond ½ earth con Housing)

c)

( 5 full size cond Housing (earthing) )

d)

( 5 full size conductors, 5th bar shall be used as clean earth + Housing).

- Neutral conductor shall have the same cross-section (100%) of phase conductors.

2.3-

Conductors:

4 ½ Conductors  :

5 Conductors :

5 Conductors :

160A...800A Busbar System Product Overview  (E-LINE KO-   )

KO-II

MANUAL

Product Overview

1sec/rms-10kA, Peak-17kA
1sec/rms-15kA, Peak-30kA
1sec/rms-30kA, Peak-63kA
1sec/rms-35kA, Peak-73,5kA

ENGLISH

21

Содержание KO-II

Страница 1: ...Fire Barriers 1 2 3 4 5 6 7 7 1 7 2 7 3 7 4 2 3 4 5 6 7 8 9 11 Points To Be Taken Into Consideration After Installation KOP 40 80A Plastic Tap Off Boxes Installation KOP 160 250 400A Tap Off Boxes In...

Страница 2: ...ivery of equipment on site Handling installation and operation of busbar systems should be carried out only by skilled trained and authorized personnel using all associated equipment such as rubber gl...

Страница 3: ...0 164 0 235 11 0 12 5 25 52 5 603 0 144 0 207 12 5 14 0 35 73 5 643 0 078 0 144 16 0 19 0 35 73 5 693 0 068 0 110 18 0 21 0 Rated Current Conductor Type Aluminium KOA Copper KOC Busbar Code KO IIMANUA...

Страница 4: ...ck jointed end and a non block jointed end See as shown Figure 2 1 1 Busbar 2 2 Busbar 3 Block Joint 3 1 Locker Piece 3 2 Insulators 3 3 Double Headed Nut 3 4 Plastic Seperator Piece 4 Conductors 5 Fr...

Страница 5: ...nsurance Company must be informed immediately for proper reporting with all required documents for further action 2 3 4 5 6 All busbar straight lengths and modules should be handled with care to avoid...

Страница 6: ...r Storage area should be free of vehicle traffic to prevent physical damage to the products 2 When busbar straight lengths and modules are to be stored for a certain time before installation restore t...

Страница 7: ...e measure the lengths of these modules as shown below 2 Length A is measured between housing of 2 busbars in cm A The special length is calculated by deducting 25cm from this measured length X A 12 cm...

Страница 8: ...project drawings 3 The recommended distance between supports is 2m Make sure that support positions do not block either joint covers or tap off points usbar system should be handled with care either b...

Страница 9: ...arked as shall be thrown away 1a 2 Introduce bolted and non bolted ends of the busbar into each other carefully till joint side cover plate screws can be put on 3 Fix the joint side cover of the block...

Страница 10: ...KO IIMANUAL 6 II Install top and bottom joint cover plates Check the joint before fitting the last joint side cover plate Fit the joint cover side plate and tighten and screws Check the position of t...

Страница 11: ...nts 8 55 Nm 40lbft Installation of End Closer KO IIMANUAL 8 If removal is required for any reason tighten nut by calibrated torque wrench adjusted to 55 Nm 40 lbft after re fixing block joint set 11 E...

Страница 12: ...Barrier KO Fire barriers are used to prevent the transition of flame and smoke from one zone to another in case of fire Chimney effect of air insulated busbars are diminished While placing an order f...

Страница 13: ...tall five conductor units to four conductor units or vice versa 4 Do not apply any kind of oil or chemical at the joints or to the contacts of tap off boxes KG O il 4 8 KO IIMANUAL 5 Do not use any ot...

Страница 14: ...Consideration After Installation 12 Take care when handling the system components Do not drop the units 13 Ensure the selected degree of protection IP rating of the system is suitable for the working...

Страница 15: ...arth contact 3 Carefully align the tap off box contacts and push the box towards the busbar 4 When the box is secured to the busbar housing closed the box cover and tighten the screws Attention Check...

Страница 16: ...ps Push left side of tap off box towards busbar and lock fixing clamps to the busbar Tight back the plastic headed bolt to hold busbar rigidly 3 Carefully align the tap off box contacts and push right...

Страница 17: ...e should be checked in order to match the busbar phases sequence before reconnecting all connections to transformers switchboards meters etc 1 When installing the feeder boxes B10 B11 make sure that t...

Страница 18: ...in sequence by starting at the source to end of the system 5 After all overcurrent protection devices have been turned on loads such as lighting circuits contactors heaters and motors may be turned ON...

Страница 19: ...nce 1 An external inspection of the system should be carried out once a year 2 Any dripping or other source of moisture onto the busbar modules should be eliminated from installed area Contact EAE for...

Страница 20: ...e responsibility that the aforementioned products conforms with the regulations and guidelines of the following standards According to EC Directive 2006 95 EEC Low Voltage Directive Tests KO IIMANUAL...

Страница 21: ...ation To prevent wrong alignment of the phase sequence during installation there shall be mechanical barriers on the joint that shall ensure correct mounting IP Plug in covers of the busbar system sho...

Страница 22: ...om the busbar when the switch is at ON position Mechanical interlock mechanism shall prevent the cover of the box fromopening whentheswitchisat ON position When the switch is at OFF position and the c...

Отзывы: