Product Overview

KX III 400A – 6000A COMPACT BUSWAY PRODUCT FEATURES

KX III–UL 

busway system allows users to distribute electrical energy safely with 46 years of 

experience in design and manufacturing of busway systems. 

KX III–UL

, features flexible power 

supply, short installation time, superior heat dissipation and electrical characteristics. Where 

shown on plans, furnish and install a totally enclosed, low-impedance busway system of the 

indicated ratings with all necessary fittings, power takeoffs, hanging devices and accessories.

1- Standards & Certification

-

 KX III–UL

 Busway system has been designed and manufactured as per UL  857 standard, 

which requires below listed tests. Each busway rating has been type tested individually and 

comply with recent UL  857 standards for all type tests and certified by independent authorized 

testing laboratory as UL including below test:

- Compliant for: CUL Listing

- Compliant for: National Electric Code (NEC)Article 364 – Busways 19

- Compliant: NEMA AB1, Molded Case Circuit Breakers and Molded Case Switches 

- Compliant: NFPA 70 – National Fire Protection Agency 

- EAE has ISO 9001, ISO 14001, OSHAH 18001, ISO 27001 and ISO 17025 certifications.

- All the required type tests for each rating according to IEC 61439-6 and certified with 3rd 

Party. 

- Compliant: IEC 60364-1 Low-voltage electrical installations

-  KX  III–UL  Busway  has  high  flame  resistance  and  circuit  integrity  properties  under  fire 

conditions according to IEC 60331, BS 6387, BS 8491 standards including joints and tap-off 

boxes.

2- Electrical Characteristics

- KX III–UL  Busway systems nominal voltage is 600 V.

- Operating Frequency: 50/60 Hz

- 6 Cycle RMS Symmetrical Short Curcuit Rating shall be:

For Aluminium Conductors;

400-630A : 50kA

800-1300A : 65kA

1600-2000A : 100kA

2500A : 125kA

3200A : 200kA

4000A : 150kA

5000A : 200kA

For Copper Conductors;

630-1000A : 65kA

1250-2000A: 125kA

2000-6000A: 200kA

- Position: 100% rating for any horizontal or vertical orientation. 

- The maximum hot-spot temperature rise at any point in the busway at continuous rated load 

shall not exceed 122°F

3- Components

3.1- Housing

KX III–UL

 Busway system has “Sandwich-Compact” structure. Conductors are packed and 

placed into the housing without leaving air gap in order to provide low reactance. 

- The housing shall be RAL7038-Electrostatic painted  extruded aluminum to provide maximum 

protection against corrosion from water  and other contaminants normally encountered during 

construction. 

- The busway housing shall be of 100% aluminum construction to reduce hysteresis and eddy 

current losses.

- Busway housing shall have optional powder coating finish if required per project design,

- “Compact structure of the housing has been provided by M6 screws applied at every 7.48 in 

along the entire length.

- The sandwich-compact structure continues at the plug-in points too. There isn't any air gap 

between conductors at the plug-in points.

- The housing material and paint are selected with non-propagating properties.

3.2- Conductors

-  Conductors:  Individual  isolated  and  insulated.  Aluminum  or  Copper  conductors  are  epoxy 

coated. All phase and neutral conductors joints and contact surfaces are plated tin (optinal 

Silver). 

- Straight sections of feeder busway can be supplied in any length, from a 12.00-inch (350 mm) 

minimum to a 10-feet (3048 mm) maximum

- Bus bars shall be suitably plated at all joints and contact surfaces. 

- KX III–UL busway system has aluminum conductors between 400A – 5000A,

- KX III–UL busway system has copper conductors between 630A – 6000A,

- KX III–UL busway system has the following number of conductors and wire configuration;

  A, 4½ Conductors: (4 full size cond PE (50% earth con housing)).

  b. 5 Conductors: (4 full size cond PE (100% earth con housing)).

  c. 6 Conductors: (5 full size conductors ( + PE (100% earth con housing)).

3.3- Insulation

- Insulation system is suitable for 600 V continuous operation.

- Specially formulated Class B epoxy insulation has been applied as insulation 

material  which  provides  high  insulation  resistance  and  high  peak  temperature 

resistance. 

-The insulation process apply is the spray insulation process which produces 

uniform application of the epoxy powder over the entire conductor bar. It is further 

enhanced by inline filter process and magnetic separator that help to eliminates 

contaminants common to fluidized bed systems.

- Epoxy is UL V0 class and halogen and toxic free properties.

- All insulators must be UL recognized.

3.4- Joint Structure

-  Electrical  and  mechanical  connection  is  making  by  placing  conductor  joints 

into the joint blocks of the connected conductors and followed by tightening and 

fastening of the joint bolts. 

- KX III–UL Busway also includes special EAE belleville spring washer be provided 

to  give  positive  pressure  over  complete  contact  area,  that  retains  its  original 

contact pressure ensuring proper 

electrical  contact.  Offers  securer,  more  reliable  and  virtually  maintenance-free 

joint.  

- All parts of the joint structure are plated with tin against contact losses due to 

corrosion in order to get safe and reliable earth connections and have very low 

resistance values entire length. 

- It shall be possible to make up a joint from one side in the event the busway 

is installed against a wall or ceiling. The joint shall be so designed as to allow 

removal of any length without disturbing 

adjacent lengths.

3.5- Accessories and Components

- All conductive fittings including Tees, flanges, Reducers, Expansion joints and 

Elbows etc. shall be of the same material from the same manufacturer.

- End pieces and end caps will be provided to install at the ends of each line.

- KX III–UL  Busway system has all necessary accessories (elbows, offsets, panel-

transformer connections, reductions, etc.) EAE supply special dimensioned units 

in short time, if the project conditions require.

- For horizontal runs, a horizontal expansion unit has been used at every 40m and 

expansion points of the building.

- For vertical applications, a vertical expansion unit has been used at every floor. 

Busway system must be rigidly fixed by supports at every floor.

-  Horizontal  runs  of  busway  shall  be  UL  Listed  for  hanging  on  10-foot  (3.05 

meters) centers in any position. Vertical riser runs of busway shall be supported 

with rigid and/or spring hangers in positions indicated on plans (max 16'/4.88 

meters) centers.

4- Tap-Off Boxes

- Tap off points shall be easily modifiable for phase configuration and be safe for 

installation and decommissioning while the busway is in its live state. All tap off 

distribution points shall have safety 

features prohibiting their installation while under load

- Plug-In busways have minimum 2 and maximum 5 plug-in points on each 10 

inch length. 

- Plug-in tap off boxes are suitable to install or removed from busways without 

switching off the power on the busway.

- Contacts of plug-in tap off box are plated by silver.

- Tap off boxes are manufactured of sheet steel and epoxy painted.

- Plug-in  tap off  boxes have electromechanical safety interlock system.  Which 

means;

-  Electromechanical  interlock  mechanism  ensures  that  the  tap  off  box  cannot 

be removed mechanically from the busway, when the switch is at “ON” position. 

- Electromechanical interlock mechanism ensures that, cover of the box can be 

opened, when the switch is at “OFF” position.  It is possible to open the cover to a 

special pin when the switch “on” 

position, it is depending on customer requests 

- While inserting the contacts of plug-in tap off box, earth contact makes the first 

touch. While removing, it is disconnected last.

Final  field  measurements  shall  be  made  by  the  contractor  prior  to  release  for 

manufacture to assure coordination with other trades.

The installer will follow all manufacturers' installation details. 

Содержание E-LINEKX-III

Страница 1: ...www eaeusa us E LINEKX III MANUAL...

Страница 2: ...E LINEKX III...

Страница 3: ...Of Special Lengths Offset Sizing Mounting Instructions For Joints Bolt on Plug in Points To Be Taken Into Consideration After Installation Standard Application Precautions Plug in Busplug Busplug Cabl...

Страница 4: ...nts in Istanbul The components that you have purchased are manufactured by a completely environment conscious with the relevant Environmental management Standards and accordance with the principles of...

Страница 5: ...which will result in personal injury if the instructions are not followed This is the safety alert symbol It is used to alert you to personal injury hazards Obey all safety messages that follow this...

Страница 6: ...ed only by qualified electrical personnel Handle this equipment carefully and install operate and maintain it correctly in order for it to function properly Neglecting fundamental installation and mai...

Страница 7: ...rized to test energize clean ground label and lock the system and equipment suitable for occupational safety applications Be trained in the use and maintenance of personal protective equipment such as...

Страница 8: ...rement Rain Drops Please use canopy for outdoor applications Please use porch for outdoor Please use porch for outdoor Please use canopy for building expension points Chemicals Urine Water CLOSE INDIR...

Страница 9: ...ng List or any piece is damaged during transportation Insurance Company must be informed immediately for proper reporting with all required documents for further action 4 All busway straight lengths a...

Страница 10: ...he load is stable and safely secured Then adequate sling and slinging method can be used for shifting from one place to another 6 The removal of the products from one floor to the other floor must be...

Страница 11: ...for weight specifications If using a forklift position the plug in unit on the forks to distribute the weight properlyTake care not to damage the metal housing Avoid using objects with sharp edges to...

Страница 12: ...ansition of building dilatations appropriate dilatation module should be chosen Please contact our company for support 6 Busway system should be handled with care either by forklift crane or any other...

Страница 13: ...e installation Micrometer type adjustable calibrated torque spanner 9 a inch square drive size 10mm 13mm and 9 b 19mm socket 9 c Drilling Machine 9 d Size 10mm Spanner Socket 9 e Screwdriver 9 f Hoist...

Страница 14: ...Washer 7 Alignment Pin removable 8 Conductors 9 IP55 Nut Locking Piece 10 Protection Plastics 11 IP55 Joint Cover Gasket 12 Alignment Pin Slot NB Protective covers 10 are discarded KX busway are manu...

Страница 15: ...KX IIIMANUAL www eaeusa us 13 Installation General Overview Of The Joint Bolt on Box Fixing Point Plug in Box Fixing Point Use special hand clamps if it is difficult to move...

Страница 16: ...ses please contact our company for technical support and technical information Note Please send a drawing for combined offsets when ordering Indicate bolted and non bolted ends on the drawing 325 A X...

Страница 17: ...ock joints 3 Remove the nut locking piece on the busway joint and loosen the joint Remove the protective covers after loosening the joint 4 Ensure that the insulation plates of the joint are not crack...

Страница 18: ...e bolt per phase the bolts should be tightened by hand to approximately 20 30 Nm as per the sequence shown above Then finally torque to 83Nm using the same sequence 12 Remove the joint covers and reve...

Страница 19: ...Joints have been done according to manual and applied related Nm value to the main bolts Tarih Date Ad Soyad First Last mza Signature Ek montaj talimat na uygun yap lm t r ve yanda yaz l Nm de erinde...

Страница 20: ...e insulation test is completed successfully 2 3 After the busway system is energized loads must be switched in sequence main and sub feed 2 4 When the busway is used properly it will have a moderate h...

Страница 21: ...ns than original tap off boxes to supply energy from the busway 6 Current rating of the busway run should be equal to the rating of the breaker Do not exceed busway nominal current during operation 7...

Страница 22: ...DARD IP55 IP65 Vertical Shaft Application Pressure Water 3 Min 1 The neutral bar of KX busway shall be at the bottom for horizontal busway lines and on the left for vertical busway lines Figure 1 2 In...

Страница 23: ...confirm that the power is off Do not install plug in unit without circuit breaker installed Do not install plug in unit with cover open or removed Failure to follow these instructions will result in...

Страница 24: ...Frequency Protection Degree Wire 1000 V 50 60 Hz IP55 Ui f IP 3P N PE Housing E L E K T R K 1 EAE tap off boxes are not equipped with any protective device unless they are required by customer Any typ...

Страница 25: ...e fixing screw of plug in tap off point cover using cross recessed screw driver 3 Throw the contact protection cover to the recycling waste bin 4 Place the KXP Plug in tap off box to the holes on the...

Страница 26: ...way 6 Push the box to the busway housing click sound will be heard from the locking parts on the box ensure the interlock betwe en the box and the housing then tighten the screw 6 a 6 a 6 b 6 b CLICK...

Страница 27: ...IDENTAL RESPONSE TO BE CONTACTED BY PARTS UNDER ELECTRICALLY FOLLOW ALL MANUFACTURER S WARNINGS AND INSTRUCTIONS 4 Resistance testing is to be carried out with a resistance tester of 1000 volts per pa...

Страница 28: ...l parts 13 All busway ratings routings and supporting systems should be checked as per final isometric drawings 14 All busway ratings routings and supporting systems should be checked as per final iso...

Страница 29: ...such as lighting circuits contactors heaters and motors may be turned ON 6 EAE busway system is particularly quiet when operating normally In some installations however there may be a moderate hum Exc...

Страница 30: ...erly rated voltage sensing device at all line and load side fuse clips to confirm that the plug in unit is off Never operate the plug in unit with the door open Failure to follow these instructions wi...

Страница 31: ...A 70E NOM 029 STPS 2011 or CSA Z462 Turn off the plug in unit Always use a properly rated voltage sensing device at all line and load side fuse clips to confirm that the plug in unit is off Never oper...

Страница 32: ...pairs it may be desirable to perform an infrared temperature test on all electrical connections Do this after the busway has been re energized and has reached a stable operating temperature 7 Refer to...

Страница 33: ...cleaner or clean lint free rag Do not use a blower or compressed air 1 An external inspection of the system should be carried out once a year 2 Any dripping or other source of moisture onto the buswa...

Страница 34: ...tors 5 full size conductors PE 100 earth conductor housing 3 3 Insulation Insulation system is suitable for 600 V continuous operation Specially formulated Class B epoxy insulation has been applied as...

Страница 35: ......