PF
-
03
~
PF-40
Edit definition
by user
-
0F03H
~
0F28H
-
PF macro
parameter
selection
0: According to the user programming mode
1-100: Call the application macro defined by
the manufacturer
0F01H
0
PF
-
02
PF parameter
group length
3
~
66
0F02H
18
A0
-
00
Function
Code
PV Water Supply
control mode
Parameter Name
1000H
Address
A0
Constant pressure water supply parameters
0x0000
~
0x0021
LED BIT0: MPPT Control mode
0: A0-03 Set value control
1: Automatic searching MPPT voltage for control
LED BIT1: Automatic start-stop control logic
0: A0-01
~
02 control start-stop
1: Liquid level sensor and A0-01
~
02 control
start-stop
2: Running by liquid level sensor
3: Running by terminal and liquid level sensor
LED BIT2: Reserved
LED BIT3: Reserved
Setting Range
1
Default
A0
-
01
Auto Start
Voltage
1001H
300.0/550.0
0
~
800
.
0Vdc
The minimum PV input value allowed to start,
below which the run command in invalid.
1002H
1003H
1004H
1005H
1006H
A0-02
Auto Stop
Voltage
0
~
800
.
0Vdc
The minimum PV voltage value in operation, below
which the AC drive enters the shutdown state.
A0-03
A0-04
A0-05
A0-06
Upper limit of
output power
MPPT maximum
voltage value
MPPT Downtest
Step
MPPT Uptest
Step
0.10
~
100.00kW
The maximum output power in operation, if the
value is exceeded, the AC drive will reduce
the power operation.
0.1
~
750.0
When BIT A0-00 is set to 0, follow the voltage
to control the water pump.
The higher the value is, the faster the search
speed is. When the parameter is set too large,
it is easy to cause vibration near the maximum
power point.
200.0/300.0
Model
dependent
250.0/480.0
1.5
0.6
1007H
A0-07
MPPT control
cycle
0.01
~
60.00S
Set the interval time of each tracking step,
the shorter the tracking time is, the faster
the speed is; too short the tracking speed may
also lead to vibration.
0
.
20
PF
-
01
1008H
A0-08
MPPT control
starting voltage
100.0
~
800.0Vdc
By setting local parameters to prevent: when
it is cloudy or in the evening(morning), the
output voltage of the solar panel is very low,
so the normal MPPT tracking method will make
the DC bus voltage too low, which may cause
the system under voltage shutdown.
240.0/440.0
-
4 3
-
-
4 4
-
F u n c t i o n C o d e T a b l e
EC620
EC620
F u n c t i o n C o d e T a b l e
100AH
100BH
100CH
A0-10
A0-11
A0-12
0.12
100.00
2.00
100DH
A0-13
Reserved
-
-
1009H
A0-09
Minimum Error
KP1
It determines the regulation intensity of the
whole PID regulator. The greater the P value
is, the greater the regulation intensity is,
and the smaller the I value is, the greater
the regulation intensity is. A0-07
~
A0-10
these two groups of parameters set the upper
and lower limits of PID parameters, which are
automatically given according to the linear
proportional relationship between the error
value of the feedback value and the given
value.
20.0
100EH
A0-14
PID control
deviation limit
0.0
~
100.0%
When the deviation value of actual voltage
and reference voltage is the ratio percentage
of reference voltage, i.e. ABS (actual voltage
reference voltage)* 100.0%/ reference voltage,
and the value is greater than the deviation
limit value of A0-03, PI regulation will be
carried out, otherwise PI treatment will not
be carried out. The default is 0.0%. ABS:
absolute value.
0.0%
100FH
A0-15
PID output
upper frequency
limit
A0-05
~
100.0%
A0-15 is used to limit the maximum value of
the target frequency, 100% Corresponding to
P0-10 Maximum frequency. After PI adjustment,
the final target frequency is limited to the
set upper limit.
100.0%
1010H
A0-16
Sleep
frequency
0.00Hz
~
Maximum frequency
This function can realize sleep and wake-up
functions. After the start command is issued,
if it is in sleep state, when the set
frequency exceeds A0-18 (wake-up voltage)
and the duration exceeds A0-19 (wake-up delay
time), the system will wake up and run. When
the system is
, if the set frequency
running
is less than A0-16 (sleep frequency), the
system will enter the sleep state (shutdown)
if the duration exceeds A0-17 (sleep delay
time). If set to A0-16 (sleep frequency)
and A0-18 (wake-up voltage) to 0, the sleep
and wake-up functions will be invalid.
0.00
1011H
A0-17
Sleep
delay
time
20.00
1012H
A0-18
Wake-up
voltage
0.00
1013H
A0-19
Wake-up delay time
20.00
1014H
A0-20
Under load detection
time of water pump
0
.
00
~
1000.0s
Setting of under load detection time of water
pump. Under the condition of continuous under
load, the under load alarm ERR60 will be given
when the operation time reaches.
60.0s
1015H
A0-21
Detection value of
under load current
0
.
00
~
100.0%
When it is 0.0%, it is determined by the under
load detection of the pump inverter itself.
When it is not 0.0%, it is determined by the
set value.
0.0%
Minimum Error
KI1
Maximum Error
KP2
Maximum Error
KI2