39
40
Region
Default Value
Vw
1
Vw
2
Australia A Voltage
253 V
260 V
Inverter maximum active power
output level (P)% of
S
rated
100%
20%
Australia B Voltage
250 V
260 V
Inverter maximum active power
output level (P)% of
S
rated
100%
20%
Australia C Voltage
253 V
260 V
Inverter maximum active power
output level (P)% of
S
rated
100%
20%
New
Zealand
Voltage
242 V
250 V
Inverter maximum active power
output level (P)% of
S
rated
100%
20%
Procedures to enable or disable the Volt-watt Response Mode:
Step1: go to ‘All Set Enable’ in the menu of ‘TECHNICAL SET’ and turn the
status to ‘ON’.
Step2: go to ‘Special Func’ and then go to ‘PU Curve’
Step3: enable or disable the ‘Volt-watt Response Mode’ by changing the
status to ‘ON’ or ‘OFF’.
6.2.5.8.4 Fixed Power Factor Mode or the Reactive Power Mode
Those modes are disabled by default. The fixed power factor mode or the
reactive power mode may be enabled in some situations by the electrical
distributor to meet local grid requirements, one of these modes shall be
enabled if the volt-var mode is disabled.
Procedures to set up the Reactive Power Mode:
Step1: go to ‘All Set Enable’ in the menu of ‘TECHNICAL SET’ and turn the
status to ‘ON’.
Step2: go to ‘Special Func’, then go to ‘Q Curve’ and enable the Q Curve by
change the status to ‘ON’
Step3: go to ‘Power Control’ and then go to ‘Q Set’.
Step 4: Set up the Reactive Power Mode manually.
Procedures to set up the Fixed Power Factor Mode:
Step1: go to ‘All Set Enable’ in the menu of ‘TECHNICAL SET’ and turn the
status to ‘ON’.
Step2: go to ‘Special Func’, then go to ‘PF Curve’ and enable the PF Curve by
change the status to ‘ON’
Step3: go to ‘Power Control’ and then go to ‘PF Set’.
Step 4: Set up the Fixed Power Factor manually.
PF CURVE
OFF
Q CURVE
OFF
NOTE
: This operation is for maintenance personnel only. Password
is required to access this part!
NOTE
: This operation is for maintenance personnel only. Password
is required to access this part!