WP6-BG 

Weatherproof Break Glass 
Manual Call Point 

 
 
 
 

 

 
 
 
 

 

1) 

Introduction 

The  WP6-BG  is  a  break  glass  manual  call  point 
designed  to  withstand  harsh  environments.  It  has 
the following ratings:  
 
 
CE Marking: 
 
 
UKCA Marking:  
 
 
IP Rating:  
IP66 
 
Ambient Temperature Range: 
-40°C to +75°C 
 
Input Voltage: 
AC voltage 250V Max. Current 5.0A Max. 
DC voltage 48V Max. Current 1.0A Max. 
DC voltage 24V Max. Current 3.0A Max. 
 
The  enclosure  is  made  from  Red  GRP  (Glass 
reinforced  Polyester).  If  alternative  colours  are 
ordered,  these  will  be  painted  with  an  epoxy 
powder coat. 
 

2) 

Call Point Location and Mounting 

The location of the call point should enable ease of 
access  for  operation  and  testing.  The  unit  should 
be  mounted  using  the  4  off  fixing  holes  which  will 
accept up to M4 sized fixings. 

72

.0

 [

2.

83

]

90.0 [3.54]

 

 

View of base unit showing fixing centres in mm [in] 

 
To  gain  access  to  the  mounting  holes  in  the  base 
the front cover must be removed.  
This  is  achieved  by  removing  the  4  off  M4  cap 
head bolts holding on the cover. 
 

 

 
Once the screws are  removed the cover  will hang 
down  out  of  the  way  to  gain  access  to  the  Ex  e 
terminal  block,  the  internal  earth  terminal  and 
mounting hole recesses. 
 
 
 
 
 

3) 

Earthing 

The unit has an internal earth terminal. 
It  is  recommended  that  a  cable  crimp  lug  is  used 
on the earth wires. 
The  internal  earth  wire  is  placed  under  a  earth 
clamp  which  will  stop  the  cable  twisting.  This  is 
secured by an M4 screw and spring washer. 
 

 

 
 
Internal Earth 

     DIN Rail terminals 

terminal 

 

 

 

 

4) 

Cable connections 

There  are  3  off  cable  entries  for  M20x1.5  cable 
glands  or  stopping  plugs  with  a  minimum  ingress 
protection of IP66. 
 
The unit can be wired in a number of different ways 
depending  whether  normally  open  or  normally 
closed contacts are required. 

 

Wire sizes allowable are 0.5mm² 

 

to 

 

4.0mm² 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

5) 

Testing unit operation 

The  break  glass  unit  can  be  tested  without  the 
need to break/replace the frangible glass element.  
A test key (7mm Allen key) is used to mechanically 
drop the glass down activating the switch.  
 

 

 

The test key is inserted in the test cam and rotated 
clockwise by an angle of 60º the glass element will 
visibly drop down in the viewable window.  
The  call  point  switch  will  now  change  over  its 
contacts to operate the alarm. 
 
Once  testing  is  complete  the  unit  needs  to  be 
reset, the test key is rotated back anticlockwise by 
an  angle  of  60º  back  to  its  original  position.  The 
glass  element  should  now  raise  up  so  it  is  level 
again in the viewable window. 
 

 

 
1. 

               2.                      3. 

Insert test                 Hold in               Rotate back  
Key rotate                 position              anticlockwise  
clockwise                  during                 to reset 
60º                            test 
 
 
 
 
 
 
 
 
 
 
 
 

INSTRUCTION MANUAL  

WP6-BG Weatherproof Break Glass Manual Call Point 

 

 