Terminal Block Options Available 

 
The STExJ2 can have two pre-fitted wire connectors: Terminal 
Block Version or DIN Rail Version. 

 

Figure 5: Terminal Block Version 

 STExJ2T01.

 

 

 

Figure 6: Terminal Block Version 

 STExJ2D01.

 

 
When connecting wires to the terminals great care should be 
taken to dress the wires so that when the cover is inserted into 
the  chamber  the  wires  do  not  exert  excess  pressure  on  the 
terminal  blocks.  This  is  particularly  important  when  using 
cables with large cross-sectional areas such as 2.5mm². 

 

Earthing

 

 
Junction box units must be connected to an earth according to 
EN/IEC  60079/14.  The  units  are  provided  with  internal  and 
external earth terminals which are both located on the terminal 
chamber section of the unit (see figures 5 or 6). 

 

Internal earthing connections should be made to the Internal 
Earth terminal in the base of the housing using a ring crimp 
terminal to secure the earth conductor under the earth clamp,  
or to the bonded Earth terminals of DIN rail (see figure 6). The 
earth conductor should be at least equal in size and rating to 
the incoming power conductors. 
 
External earthing connections should be made to the M5 earth 
stud, using a ring crimp terminal to secure the earth 
conductor  to  the  earth  stud.  The  external  earth  conductor 
should be at least 4mm2 in size. 
 
 
 

6.3. Cable Glands, Blanking Elements & Adapters

 

 
For high ambient temperatures, the cable entry and the cable 
branching  point  temperatures  may  exceed  the  following 
temperatures: 
 

  For ATEX / IECEx: 70ºC at entry or 80ºC at branching point. 

  For NEC / CEC: 60ºC at entry or 60ºC at branching point. 

 
Therefore,  suitable  heat  resisting  cables  and  cable  glands 
must  be  used  with  a  rated  service  temperature  at  least  as 
stated in the Instructions document of the product being used. 
Refer to STExB2 Xenon (D199-00-201-IS) and STExB2 LED 
(D199-00-401-IS) Instructions. 

 

Cable Glands 

 
The cable gland entries have an M20 x 1.5 entry thread. Only 
use  suitably  rated  and  certified  cable  glands,  as  per  type  of 
approval,  which  must  be  suitable  for  the  type  of  cable  being 
used and also meet the requirements of the current flameproof 
installation standards (see section 6.1). 

 

Blanking Plugs 
 

When only one cable entry is used the other entries must be 
closed with suitably rated and certified blanking plugs as per 
type of approval. 
 
Any unused cable entries must be closed with suitably rated 
and certified blanking plugs. 
 

Ingress Protection 

 
If  a  high  IP  (Ingress  Protection)  rating  is  required,  then  a 
suitable sealing washer must be fitted under the cable glands 
or blanking plugs. 
 
A  minimum  ingress  protection  rating  of  IP6X  must  be 
maintained for installations in explosive dust atmospheres. 
 
For combustible dust applications, the cable entry device and 
blanking elements shall be in type of explosion protection and 
shall have an IP 6X rating. 
 
For use in Class I Division II locations, in order to maintain the 
db  type  protection,  flameproof  conduit  seals  and/or  cable 
glands must be used. 
 

Adapters 

 
The  STExJ2  can  be  supplied  with  the  following  types  of 
adapters: 
 

M20 to ½” NPT

 

M20 to ¾” NPT

 

M20 to M25 

 
It is important to note that stopping plugs cannot be fitted onto 
adapters, only directly onto the M20 entries. 
 
Any other adapters used must be suitably rated as per the 
applicable standards. 
 
If the installation is made using conduit, openings must have a 
sealing fitting connected as close as practical to the wall of the 
enclosure, but in no case more than the size of the conduit or 
50mm, whichever is the lesser. 
 
 
 

Содержание STExJ2

Страница 1: ...EC60079 0 2011 Ed 6 Explosive Atmospheres Equipment General requirements EN60079 1 2014 IEC60079 1 2014 Ed 7 Explosive Atmospheres Equipment protection by flameproof enclosures d BS EN 60079 31 2014 I...

Страница 2: ...likely to occur in normal operation Zone 22 ATEX IECEx only Explosive dust air mixture not likely to occur in normal operation and if it does it will only exist for a short time Gas Groupings Group I...

Страница 3: ...ve atmospheres Classification of areas Explosive gas atmospheres EN60079 10 2 IEC60079 10 2 Explosive atmospheres Classification of areas Explosive dust atmospheres NEC Class Zone CEC Class Zone and N...

Страница 4: ...y or 60 C at branching point Therefore suitable heat resisting cables and cable glands must be used with a rated service temperature at least as stated in the Instructions document of the product bein...

Страница 5: ...el in accordance with the current relevant standards EN60079 19 IEC60079 19 Explosive atmospheres Equipment repair overhaul and reclamation EN 60079 17 IEC60079 17 Explosive atmospheres Electrical ins...

Страница 6: ...Netherlands B V Utrechtseweg 310 6812 AR Arnhem Netherlands Quality Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 2G Ex db IIC T6 T3 Gb II 2D Ex tb IIIC T...

Страница 7: ...e and Place of Issue London 03 12 2021 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the m...

Отзывы: