background image

 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH

 

www.e2s.com

 

Tel: +44 (0)208 743 8880

 

Document No. D199-00-501-IS

 

Issue 4

 

04-01-21

 

 

Sheet 2 of 5

 

 

CEC Class / Zone Ratings Canada Codes 

 

Standards 

CAN/CSA C22.2 No. 60079-0 (Ed. 4) 02/2019 

Explosive Atmospheres - Part 0: Equipment - General 
Requirements 

CAN/CSA C22.2 No. 60079-1 (Ed. 3) 2016 

Electrical Apparatus for Explosive Gas Atmospheres - Part 
1: Flameproof Enclosures 'd' 

Ratings 

STExJ2 

Ex db IIC T5 Gb Ta -50°C to +70°C 
Ex db IIC T6 Gb Ta -50°C to +65°C 

 
Installation  must  be  carried  out  in  compliance  with  the 
Canadian Electric Code. 
 

NEC & CEC Class / Division Ratings for US / Canada, 
USL CNL 

 

Standards 

UL1638A (Ed. 1) 2016 

Standard for Visual Signal Appliances for General 
Signalling Use 

CSA C22.2 No. 205-17 (Ed. 3) 2017 

Signal Equipment 

Ratings 

STExJ2 
 

Class I Div 2 Group ABCD T5 Ta -50°C to +70°C 
Class I Div 2 Group ABCD T6 Ta -50°C to +65°C 

 
Installation must be carried out in compliance with the National 
Electric Code / Canadian Electric Code. 
 

3)  Zones, Gas Group, Category and 

Temperature Classification 

 

The  units  can  be  installed  in  locations  with  the  following 
conditions: 
 

Area Classification 

Zone 1 

Explosive gas air mixture likely to occur in 
normal operation. 

Zone 2 

Explosive gas air mixture not likely to occur in 
normal operation, and if it does, it will only 
exist for a short time. 

Zone 21 

(ATEX / IECEx only)

 

Explosive dust air mixture likely to occur in 
normal operation. 

Zone 22 

(ATEX / IECEx only)

 

Explosive dust air mixture not likely to occur 
in normal operation, and if it does, it will only 
exist for a short time. 

Gas Groupings 

Group IIA 

Propane 

Group IIB 

Ethylene 

Group IIC 

Hydrogen and Acetylene 

Temperature Classification for Gas Applications 

T1 

450ºC  

T2 

300ºC 

T3 

200ºC 

T4 

135ºC 

T5 

100ºC 

T6 

85ºC 

Dust Groupings 

(ATEX / IECEx only) 

Group IIIA 

Combustible Flyings 

Group IIIB 

Non-conductive Dust 

Group IIIC 

Conductive Dust 

Maximum Surface Temperature for Dust Applications 

(ATEX / IECEx only)

 

STExJ2 

80ºC 

Equipment Category 

2G / 2D  

Equipment Level Protection

 

Gb, Gc, Db, Dc 

Ambient Temperature Range 

-50°C to +70°C 

IP Rating 

IP6X to EN/IEC60079-0 
IP66 to EN60529 

 

4)  Special Conditions of safe use 

 

Repair of the flame path / flameproof joints is not permitted. 
 

 

Figure 1: Flame Path.

 

 
The  metallic  enclosure has a non-conductive coating.  These 
may generate an ignition-capable level of electrostatic charges 
under certain extreme conditions. The user should ensure that 
the  equipment  is  not  installed  in  a  location  where  it  may  be 
subjected to external conditions that might cause a build-up of 
electrostatic charges on non-conducting surfaces. 

 

5)  Product Mounting and Access 

 

5.1. Location and Mounting 

 

The  location  of  the  junction  boxs  should  be  made  with  due 
regard  to  the  area  over  which  the  warning  signal  must  be 
visible. They should only be fixed to services that can carry the 
weight of the unit.

 

 
The  STEx  junction  boxes  should  be  securely  bolted  to  a  flat 
surface  using  9.0mm  diameter  bolt  holes  in  the  base  of  the 
unit. See figure 2.  

Содержание STExJ2

Страница 1: ...EC60079 0 2011 Ed 6 Explosive Atmospheres Equipment General requirements EN60079 1 2014 IEC60079 1 2014 Ed 7 Explosive Atmospheres Equipment protection by flameproof enclosures d BS EN 60079 31 2014 I...

Страница 2: ...likely to occur in normal operation Zone 22 ATEX IECEx only Explosive dust air mixture not likely to occur in normal operation and if it does it will only exist for a short time Gas Groupings Group I...

Страница 3: ...ve atmospheres Classification of areas Explosive gas atmospheres EN60079 10 2 IEC60079 10 2 Explosive atmospheres Classification of areas Explosive dust atmospheres NEC Class Zone CEC Class Zone and N...

Страница 4: ...y or 60 C at branching point Therefore suitable heat resisting cables and cable glands must be used with a rated service temperature at least as stated in the Instructions document of the product bein...

Страница 5: ...el in accordance with the current relevant standards EN60079 19 IEC60079 19 Explosive atmospheres Equipment repair overhaul and reclamation EN 60079 17 IEC60079 17 Explosive atmospheres Electrical ins...

Страница 6: ...Netherlands B V Utrechtseweg 310 6812 AR Arnhem Netherlands Quality Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 2G Ex db IIC T6 T3 Gb II 2D Ex tb IIIC T...

Страница 7: ...e and Place of Issue London 03 12 2021 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the m...

Отзывы: