If an input and output wire is required the 2-off Live/Neutral or 
+/- terminals can be used. If fitting 2-off wires to one terminal 
way  the  sum  of  the  2-off  wires  must  be  a  maximum  cross 
sectional area of 2.5mm². Strip wires to 8mm. Wires may also 
be fitted using ferrules. Terminal screws need to be tightened 
down  with  a  tightening  torque  of  0.45  Nm  /  5  Lb-in.  When 
connecting wires to the terminals great care should be taken 
to dress the wires so that when the cover is inserted into the 
chamber  the  wires  do  not  exert  excess  pressure  on  the 
terminal  blocks.  This  is  particularly  important  when  using 
cables with large cross sectional areas such as 2.5mm². 

 

12) Wiring Unit 

 

The units come with two options for the terminal block. 
A DIN rail version which has 8-way connection and allows for 
limited wiring of EOL devices. 
The  PCB  Terminal  Version  has  a  6-way  connector  but  is 
designed  to  allow  for  full  configuration  with  Series  and  EOL 
devices in a number of wiring configurations. 
 
For EOL and Series device limitations and configurations see 
Section 15. 
For wiring schematic see document D204-06-001 

 
Wiring Diagram For 8-Way DIN Rail 
 

 

 

Fig. 4 DIN Rail in Base 
 

Wiring Diagram For 6-Way PCB Terminal Board 
 
 
 
 
 
 

 

  

 
 
 
 

Fig. 5 PCB Terminal Block in Base

 

 

See  section  15  and  page  7  for  details  of  adding  Series  and 
EOL  devices  on  the  PCB.  This  can  either  be  done  at  the 
order stage or added to the correct terminal blocks afterward 
(see example  on  sheet 7).  All  devices must comply  with  the 
requirements stipulated in section 15. 

 

13) Testing unit operation 

 

The  break  glass  unit  can  be  tested  without  the  need  to 
break/replace the frangible glass element.  
A  test  key  (Plastic  Key  Supplied  with  unit)  is  used  to 
mechanically drop the glass down activating the switch.  
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
The test key is inserted in the test cam and rotated clockwise 
by an angle of 90º the glass element will visibly drop down in 
the viewable window.  
The  call  point  switch  will  now  change  over  its  contacts  to 
operate the alarm. 
Once testing is complete the unit needs to be reset, the test 
key  is  rotated  back  anticlockwise  90º  to  its  original  vertical 
position. The glass element should now raise up so it is level 
again (horizontal) in the viewable window. 
 

 

1.                                        2.                          3. 
Insert test 

 

Hold in                 Rotate back  

Key rotate              

position                anticlockwise  

clockwise               

during                   to reset 

60º                         

test 

 

 

14) Replacement of glass element 

 
If  the  break  glass  unit  has  been  operated  the  broken  glass 
element can be quickly replaced. 
 
The break glass cover plate is removed by unscrewing the 4 
off M4 cap head screws attaching it.  

 

M/S 1        M/S 2 
+    -           +    - 
1   3           4    6 

SERIES 1     

 

SERIES 2 

          EOL 1    EOL 2

 

Содержание STExCP8-BG-D

Страница 1: ...tified Body No The units can be installed in locations with the following conditions Area Classification Gas Zone 1 Explosive gas air mixture likely to occur in normal operation Zone 2 Explosive gas a...

Страница 2: ...the base Insert the M6 x 40 cover bolts and fully tighten down tightening torque 8 8Nm ensuring no gap is visible between the cover and base of the enclosure The metallic enclosure has a non conductiv...

Страница 3: ...max 5 0A max 48Vdc max 1 0A max 24Vdc max 3 0A max A supply voltage variation of 10 outside the voltage range is permissible Electrical connections are to be made into the terminal blocks DIN rail pro...

Страница 4: ...s see Section 15 For wiring schematic see document D204 06 001 Wiring Diagram For 8 Way DIN Rail Fig 4 DIN Rail in Base Wiring Diagram For 6 Way PCB Terminal Board Fig 5 PCB Terminal Block in Base See...

Страница 5: ...e observed depending on supply voltage and type of components fitted If a combination of resistors diodes zener diodes is used values for all components must be observed and lowest current limit for e...

Страница 6: ...nit must only be cleaned with a damp cloth Units must not be opened while an explosive atmosphere is present 17 SIL 2 Reliability Data Reliability and Functional safety IEC EN61508 which has been asse...

Страница 7: ...DOS PARAFUSOS DA TAMPA A4 70 N O ABRA QUANDO HOUVER GASES OU P S EXPLOSIVOS NO AMBIENTE POTENCIAL PERIGO DE DESCARGA ELETROST TICA TODAS AS ENTRADAS M20 X 1 5 SE A TEMPERATURA EXCEDER 70 C NA ENTRADA...

Страница 8: ...ente se tornar o limite geral A limita o de corrente para unidades equipadas com resistores de fim de linha diodos ou diodos zener deve ser garantida usando uma fonte de alimenta o limitada de corrent...

Страница 9: ...to M5 usando um terminal de crimpagem para fixar o condutor de aterramento ao terminal de aterramento O condutor de terra externo deve ter pelo menos 4 mm de tamanho Ao concluir a instala o das jun es...

Страница 10: ...e can be fitted either by customer or pre installed by E2S at point of order When fitting diodes or zener diodes polarity across devices must be observed Resistor polarity is unimportant SERIES EOL Wi...

Страница 11: ...07 2019 D204 06 001 FOR PERMITTED MIN MAX VALUES OF EOL SERIES DEVICES PLEASE REFER TO INSTRUCTIONS Standard Unit showing positions of optional Series and EOL Devices 1 2 3 4 5 6 M S 1 M S 2 7 8 N O...

Страница 12: ...open 1 2 3 4 5 6 M S 1 M S 2 7 8 N O COM 4A Circuit as shown in Unoperated condition Terminals 1 4 M S 1 and 5 8 M S 2 open Terminals 1 3 M S 1 and 5 7 M S 2 closed N C N O COM N C 1 2 3 4 5 6 M S 1 M...

Страница 13: ...shown in Operated condition Terminals 1 2 M S 1 and 4 5 M S 2 open Terminals 1 3 M S 1 and 4 6 M S 2 closed STExCP8 R N POTTS R S RAIT 03 07 2019 B ISARD Optional Single or Double Microswitch Circuit...

Страница 14: ...ion Service Notified BodyNo 2813 CSAGroup Netherlands B V Utrechtseweg 310 6812AR Arnhem Netherlands Quality Assurance Notification ModuleD SIRA 05 ATEX M342 Provisions fulfilledby theequipment II 2G...

Страница 15: ...er Date andPlace of Issue London 23 12 2020 EU Declaration of Conformity On behalf of European SafetySystems Ltd I declarethat on the date the equipment accompanied by this declaration is placed onthe...

Страница 16: ...n Module D CSAE 22UKQAN0046 Provisions fulfilled by the equipment II 2G Ex db IIC T5 Gb II 2G Ex db IIC T6 Gb Standards applied EN IEC 60079 0 2018 EN 60079 1 2014 Directive 2014 30 EU Electromagnetic...

Отзывы: