Ingress Protection 

 
If  a  high  IP  (Ingress  Protection)  rating  is  required,  then  a 
suitable sealing washer must be fitted under the cable glands 
or blanking plugs. A minimum ingress protection rating of IP6X 
must  be  maintained  for  installations  in  explosive  dust 
atmospheres. 
 
For combustible dust applications, the cable entry device and 
blanking elements shall be in type of explosion protection and 
shall have an IP 6X rating. 
 

Adapters 

 
The  STEx  sounder  range  can  be  supplied  with  the  following 
types of adapters: 

 

M20 to ½” NPT

 

M20 to ¾” NPT

 

M20 to M25 

 

It is important to note that stopping plugs cannot be fitted onto 
adapters, only directly onto the M20 entries. 

 
 

Any  other  adapters  used  must  be  suitably  rated  and  ATEX / 
IECEx certified adapters. 
 
If the installation is made using conduit, openings must have a 
sealing fitting connected as close as practical to the wall of the 
enclosure, but in no case more than the size of the conduit or 
50mm, whichever is the lesser. 
 

8)  Settings 

 
Following illustrations show the different settings available for 
STExS1  Alarm  Horn  Sounders.  See  schematic  diagrams 
D190-06-201 for DC units and D190-06-205 for AC units. 
 

8.1. SPL Configuration 

 
See  Table  1  for  product  power  supply  and  Sound  Pressure 
Levels (SPL). 
 

Configuration for DC Units 

 

 

Figure 7: DC PCBA SPL Configuration.

 

 
 
 
 
 
 
 
 
 
 
 

Configuration for AC Units 
 

 

Figure 8: AC PCBA SPL Configuration.

 

 

8.2. Stage Switching Polarity (DC Units) 

 
Switching  from  positive  switching  (default)  to  negative 
switching - DC Only. 
 

NOTE:

  Max  supply  is  33V  DC 

  if  higher  DC  voltage  is 

required, use Negative switching. 
 

 

Figure 9: Stage Switching Polarity.

 

 

8.3. Wiring into the Sounder and Beacon separately 

 
The sounder PCBA and beacon PCBA are linked as a default 
setting. They can be wired in separately by removing the link 
wires.  See  D190-06-201  (DC)  and  D190-06-205  (AC)  for 
wiring details. 

 

Figure 10: STExC1 Sounder Terminal and 

Beacon Terminal Linked.

 

Содержание STExC1

Страница 1: ...Vac 50 60Hz 127mA 149mA 109 101 STExC1X05FDC012 12Vdc 11 5 14Vdc 885mA 1 002mA 115 109 STExC1X05FDC024 24Vdc 20 28Vdc 508mA 555mA STExC1X05FDC048 48Vdc 42 54Vdc 325mA 427mA STExC1X05FAC230 230Vac 220 240Vac 50 60Hz 127mA 149mA 115 109 Max Tone 4 Nom Tone 44 x Average over 64 tones The table shows the input current taken by the various sounders Supply voltage variation of 10 outside the voltage ran...

Страница 2: ...b Ta 50 C to 70 C STExC1X05AC230 Ex db IIC T5 Gb Ta 50 C to 45 C Ex db IIC T4 Gb Ta 50 C to 70 C Ex db IIIC T117 C Db Ta 50 C to 70 C Certificate No DEMKO 16 ATEX 1466X IECEx ULD 16 0017X Epsilon x Equipment Group and Category II 2G II 2D CE Marking and Notified Body No 2813 Certificate No DEMKO 16 ATEX 1466X IECEx ULD 16 0017X 4 Zones Gas Group Category and Temperature Classification The units ca...

Страница 3: ...ct the electrical supply cables to the sounder it is necessary to remove the flameproof cover to gain access to the flameproof chamber To access the Ex d chamber loosen the M4 grub screw on the sounder cover Open the enclosure by turning the sounder cover counterclockwise and remove the cover taking extreme care not to damage the flameproof threads in the process See figure 3 Figure 3 Accessing th...

Страница 4: ...th located on the terminal chamber section of the unit see figure 6 Internal earthing connections should be made to the PCB terminal block or to the Internal Earth terminal in the base of the housing using a ring crimp terminal to secure the earth conductor under the earth clamp The earth conductor should be at least equal in size and rating to the incoming power conductors External earthing conne...

Страница 5: ...n is made using conduit openings must have a sealing fitting connected as close as practical to the wall of the enclosure but in no case more than the size of the conduit or 50mm whichever is the lesser 8 Settings Following illustrations show the different settings available for STExS1 Alarm Horn Sounders See schematic diagrams D190 06 201 for DC units and D190 06 205 for AC units 8 1 SPL Configur...

Страница 6: ...nd stage 2 respectively Default S2 Tone 1 Default S1 Tone 44 ON 1 OFF 0 Figure 11 DIP switch configuration The sounder can also be switched to sound the third and fourth stage alarm tones The tone table D221 95 001 IS shows the switch positions for the 64 tones on first and second stages and which tones are available for the third and fourth stages dependent on the Stage 1 DIP switch setting Table...

Страница 7: ... polarity monitoring Custom DC Independent Sounder Beacon Activation Remove Link Wires Fig 10 See document D190 06 201 5a DC Single Stage Configuration Line monitoring Positive Switching 5b DC Two Stage Configuration Common Negative Positive Switching 5c DC Three Four Stage Configuration Common Negative Positive Switching 6 DC Three Four Voltage Free 2nd 3rd 4th Stage Activation Configuration Comm...

Страница 8: ...disassembled To change the lens unscrew the M5 socket head screws and remove the M5 screws M5 spring flat washers Figure 11 Removal of Lens Remove the guard and replace the old lens with the new lens Figure 12 Changing of Lens Fit the guard back on to the lens and casting align the holes of the guard lens and casting To reattach the lens the fixings MUST be in the order shown in figure 13 Figure 1...

Страница 9: ...e 1 ve IN Stage 1 ve OUT Common ve IN Common ve OUT Stage 2 ve Stage 3 ve WIRING LINKING BEACON SOUNDER FACTORY FITTED 6 R1 R1 S2 S3 R1 S2 OPTIONAL LINE MONITORING RESISTOR CUSTOMER SUPPLIED 14V MAX SYSTEM 120Ω MIN 2W MIN OR 1KΩ MIN 0 5W MIN 28V MAX SYSTEM 470Ω MIN 2W MIN OR 2 4KΩ MIN 0 5W MIN RECOMMENDED MINIMUM VALUES R1 Stage 1 ve IN Stage 1 ve OUT Stage 1 ve IN Stage 1 ve OUT Single Stage Conf...

Страница 10: ... D190 06 201 6 S2 S3 R1 S2 R2 OPTIONAL LINE MONITORING RESISTOR CUSTOMER SUPPLIED 14V MAX SYSTEM 120Ω MIN 2W MIN OR 1KΩ MIN 0 5W MIN 28V MAX SYSTEM 470Ω MIN 2W MIN OR 2 4KΩ MIN 0 5W MIN RECOMMENDED MINIMUM VALUES R1 Three Four Stages Voltage Free 2nd 3rd 4th Stage Activation Configuration Config 2 Common Positive Customer Set H1 H2 to Negative Switching See Below Stage 1 Apply Power to Common ve S...

Страница 11: ...SIONS IN MM DRAWING NUMBER A B C D E F G 10 9 G F E 7 8 6 5 D C 1 3 4 2 A B R S RAIT B ISARD R N POTTS NTS OF 3 SWITCHES FOR STAGE OPERATION CUSTOMER SUPPLIED D190 06 201 6 WIRING LINKING BEACON SOUNDER FACTORY FITTED OPTIONAL LINE MONITORING RESISTOR CUSTOMER SUPPLIED 14V MAX SYSTEM 120Ω MIN 2W MIN OR 1KΩ MIN 0 5W MIN 28V MAX SYSTEM 470Ω MIN 2W MIN OR 2 4KΩ MIN 0 5W MIN RECOMMENDED MINIMUM VALUES...

Страница 12: ... Stage 2 ve Stage 1 ve IN Stage 1 ve OUT Common ve IN Common ve OUT Stage 2 ve Stage 3 ve ve IN ve IN D190 06 201 6 4 R2 ve OUT ve OUT R1 R1 S2 R1 S2 S3 OPTIONAL LINE MONITORING RESISTOR CUSTOMER SUPPLIED 14V MAX SYSTEM 120Ω MIN 2W MIN OR 1KΩ MIN 0 5W MIN 28V MAX SYSTEM 470Ω MIN 2W MIN OR 2 4KΩ MIN 0 5W MIN RECOMMENDED MINIMUM VALUES R1 Single Stage Configuration Config 5a Line Monitoring Set to p...

Страница 13: ...2 R1 OPTIONAL LINE MONITORING RESISTOR CUSTOMER SUPPLIED 14V MAX SYSTEM 120Ω MIN 2W MIN OR 1KΩ MIN 0 5W MIN 28V MAX SYSTEM 470Ω MIN 2W MIN OR 2 4KΩ MIN 0 5W MIN RECOMMENDED MINIMUM VALUES R1 Three Four Stages Voltage Free 2nd 3rd 4th Stage Activation Configuration Config 6 Common Positive Customer Set H1 H2 to Negative Switching See Below Stage 1 Apply Power to Common ve Stage 1 ve Stage 2 Apply P...

Страница 14: ...SIONS IN MM DRAWING NUMBER A B C D E F G 10 9 G F E 7 8 6 5 D C 1 3 4 2 A B R S RAIT B ISARD R N POTTS NTS OF SWITCHES FOR STAGE OPERATION CUSTOMER SUPPLIED D190 06 201 6 6 OPTIONAL LINE MONITORING RESISTOR CUSTOMER SUPPLIED 14V MAX SYSTEM 120Ω MIN 2W MIN OR 1KΩ MIN 0 5W MIN 28V MAX SYSTEM 470Ω MIN 2W MIN OR 2 4KΩ MIN 0 5W MIN RECOMMENDED MINIMUM VALUES R1 Independent Sounder Beacon Activation Rem...

Страница 15: ...L SHEET SCALE TITLE A3 IF IN DOUBT ASK DO NOT SCALE ALL DIMENSIONS IN MM DRAWING NUMBER A B C D E F G 10 9 G F E 7 8 6 5 D C 1 3 4 2 A B D190 06 205 R S RAIT B ISARD R N POTTS OF NTS 1 SWITCHES FOR STAGE OPERATION CUSTOMER SUPPLIED WIRING LINKING BEACON SOUNDER FACTORY FITTED 2 Earth Earth Stage 2 Stage 3 Common L N L N N N L L E N N L L E C S2 S3 Live IN Live OUT Neutral IN Neutral OUT Stage 1 Li...

Страница 16: ...CALE ALL DIMENSIONS IN MM DRAWING NUMBER A B C D E F G 10 9 G F E 7 8 6 5 D C 1 3 4 2 A B D190 06 205 R S RAIT B ISARD R N POTTS OF NTS 2 SWITCHES FOR STAGE OPERATION CUSTOMER SUPPLIED 2 Stage 1 Live IN Stage 1 Live OUT Stage 1 Neutral IN Stage 1 Neutral OUT Earth Live IN Live OUT Neutral IN Neutral OUT Earth Stage 2 Stage 3 Common N N L L E N N L L E C S2 S3 Single Stage Configuration Config 2a S...

Страница 17: ... 0 0 0 1 0 1 0 0 0 0 1 1 0 0 0 1 1 1 0 0 0 0 0 0 1 0 0 1 0 0 1 0 0 0 1 0 1 0 0 1 1 0 1 0 0 0 0 1 1 0 0 1 0 1 1 0 0 0 1 1 1 0 0 1 1 1 1 0 0 0 0 0 0 1 0 1 0 0 0 1 0 0 1 0 0 1 0 1 1 0 0 1 0 0 0 1 0 1 0 1 0 1 0 1 0 0 1 1 0 1 0 1 1 1 0 1 0 1 1 0 1 1 0 0 0 1 1 1 0 0 1 1 1 1 0 0 0 0 0 0 1 0 1 0 0 0 1 1 1 0 0 0 1 0 0 1 0 0 1 1 0 1 0 0 1 0 1 1 0 0 1 1 1 1 0 0 1 0 0 0 1 0 1 0 1 0 1 0 1 1 0 1 1 0 1 0 1 1 1 0...

Страница 18: ...p Netherlands B V Utrechtseweg 310 6812 AR Arnhem Netherlands Quality Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 2G Ex db IIC T6 T3 Gb II 2D Ex tb IIIC T82 C T137 C Db IP6X Dust Protection to EN60079 0 EN60079 31 Standards applied EN IEC 60079 0 2018 EN 60079 1 2014 EN 60079 31 2014 Directive 2014 30 EU Electromagnetic Compatibility Directive EMC Sta...

Страница 19: ...te and Place of Issue London 03 12 2021 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the market the equipment conforms with all technical and regulatory requirements of the above listed directives regulations and standards This Declaration is issued under the sole responsibility of the ma...

Отзывы: