DC-011_Issue_J (IS-Mini) - Page 1 of 2 - QAF_252_Issue_5

 

EU Declaration of Conformity 

Manufacturer: 

 

 

European Safety Systems Ltd. 

 

 

 

Impress House, Mansell Road, Acton 

 

 

 

London, W3 7QH 

 

 

 

United Kingdom 

 
Authorised Representative: 

E2S Warnsignaltechnik UG 

 

 

 

Charlottenstrasse 45-51 

 

 

 

72764 Reutlingen 

 

 

 

Germany 

 
Equipment Type:  

 

IS-mA1, IS-mA2, IS-mA3, IS-mB1, IS-mC1, IS-mA1M 

 

Directive 2014/34/EU: Equipment and Protective Systems for use in Potentially Explosive Atmospheres (ATEX) 

Notified Body for EU type Examination (Module B): 

Sira Certification Service 
Notified Body No.: 2813 
CSA Group Netherlands B.V, Utrechtseweg 310, 6812 AR, Arnhem, Netherlands 

EU-type Examination Certificate (Module B): 

SIRA 05ATEX2084X 

Notified Body for Quality Assurance Notification / Conformity to EU-type 
based on 
quality assurance of the production process (Module D): 

Sira Certification Service 
Notified Body No.: 2813 
CSA Group Netherlands B.V, Utrechtseweg 310, 6812 AR, Arnhem, Netherlands 

Quality Assurance Notification (Module D): 

SIRA 05 ATEX M342 

Provisions fulfilled by the equipment: 

II 1 G Ex ia IIC T4 Ga (-

40 °C ≤ Ta ≤ +60 °C) or

 

I M1 Ex ia I Ma (-

40 °C ≤ Ta ≤ +60 °C)

 

Standards applied: 

EN IEC 60079-0:2018 
EN 60079-11:2012 
IEC 60079-26:2014 

Regulation EU No. 305/2011: Construction Products Regulation (CPR) 

 IS-mA1 (tones 2, 3, 9, 15, 16, 17) only 

Notified Product Certification Body for Certificate of Constancy of 
Performance or EC Type Examination Certificate and continuous 
surveillance, assessment and evaluation of factory production control: 

VdS Schadensverhütung GmbH 
Notified Body No.: 0786 
Amsterdamer Str 172-174, 50735 Köln, Germany 

Certificate of Constancy of Performance or EC Type Examination 
Certificate: 

0786-CPD-20338 

Standards applied: 

EN 54-3:2001 + A1:2002 + A2:2006 

Directive 2014/30/EU: Electromagnetic Compatibility Directive (EMC)  

Standards applied: 

EN 61000-6-1:2007 
EN 61000-6-2:2005 
EN 61000-6-3:2007 / A1:2011 / AC: 2012 
EN 61000-6-4:2007 / A1: 2011 

Directive 2011/65/EU: Restriction of the use of certain hazardous substances in electrical and electronic equipment (RoHS) 

The product and all the components contained within it are in accordance with the restriction of the use of hazardous substances in electrical and electronic 
equipment, including amendment by Directive 2015/863/EU.

 

Regulation (EC) 1907/2006: Registration, Evaluation, Authorisation and Restriction of Chemicals (REACH) 

The product and all the components contained within it are free from substances of very high concern. 

Other Standards and Regulations 

EN 60529:1992+A2:2013 - Degrees of protection provided by enclosures (IP code) 

 enclosure rated IP65 

 

 

Содержание Minialert IS-mC1

Страница 1: ...but at supply voltages above 16V the internal current limit will function and therefore it is recommended that they are not operated continuously with a direct supply greater than 16V IS mC1 Sounder S...

Страница 2: ...e that the equipment is not installed in a location where it may be subjected to external conditions that might cause a build up of electrostatic charges on non conducting surfaces additionally cleani...

Страница 3: ...nd remove the sounder beacon section from the base by turning it anti clockwise Ensure that the O ring seal remains in place b Remove the required 20mm knockout section s depending on system wiring an...

Страница 4: ...meet the requirements for the sounder section see section 4 3 Hazardous Area IS mC1 Beacon IS mC1 Sounder 0V Power Supply Safe Area Barrier On Off 28V 93mA Positive Fig 7 Combined Unit wired for simu...

Страница 5: ...Intermittent 800Hz 0 25s ON 1s OFF Alternating 544Hz 100ms 440Hz 400ms NFS 32 001 Motor Siren Slow rise to 1200Hz Motor Siren Slow rise to 800Hz Continuous 1200Hz Motor Siren Slow rise to 2400Hz Inte...

Страница 6: ...rictive but care should be taken not to exceed a capacitive limit of 83nF for installations when very long cables are used 9 Volume Control The output level of the IS mC1 Combined Sounder Beacon can b...

Страница 7: ...ounder Terminal w r t Sounder Terminal from a barrier having a maximum open circuit voltage Uo that is 28V and a maximum short circuit current Io that is 93mA where Io is resistively limited If not al...

Страница 8: ...uoted and for which the output is non ignition capable for the Class Division or Zone and Group of use 7 The IS mC1 Combined Unit enclosure has an ingress protection rating of IP 65 If supplied withou...

Страница 9: ...ospheres disconnect power before servicing 8 Substitution of components may impair safety 9 The total capacitance connected to terminals of the sounder i e Ccable plus any other capacitance shall not...

Страница 10: ...2018 EN 60079 11 2012 IEC 60079 26 2014 Regulation EU No 305 2011 Construction Products Regulation CPR IS mA1 tones 2 3 9 15 16 17 only Notified Product Certification Body for Certificate of Constanc...

Страница 11: ...and Place of Issue London 23 12 2020 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the ma...

Страница 12: ...EU No 305 2011 Construction Products Regulation CPR IS mA1 tones 2 3 9 15 16 17 only Notified Product Certification Body for Certificate of Constancy of Performance or EC Type Examination Certificate...

Страница 13: ...and Place of Issue London 04 02 2022 UKCA Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the m...

Отзывы: