background image

 

 

European Safety Systems Ltd.

  Impress House, Mansell Road, Acton, London W3 7QH 

 

 

 

 

 

[email protected]  Tel: +44 (0)208 743 8880 

Document D150-00-651-IS   Issue 2  06-08-15 

 

 

Sheet 2 of 3 

 

 

 

www.e2s.com  Fax +44 (0)208 740 4200 

6) Earthing 

The unit has both internal and external earth 
terminals. 
It is recommended that a cable crimp lug is used 
on the earth wires. 
The internal earth wire is placed under a earth 
clamp which will stop the cable twisting. This 
secured by an M4 screw and spring washer. 
The external earth lug should be located between 
the two M5 washers provided and securely locked 
down with the M5 spring washer and two locknuts. 
 

 

Internal Earth 
terminals  

 

External 

 

 

               Earth Stud 

 Terminal 

block 

 

7) Cable 

connections 

 
There are 3 off cable entries for M20x1.5 cable 
glands or stopping plugs. 
 
Cable glands or stopping plugs must be rated IP66. 
 
The unit can be wired in a number of different ways 
depending on the resistor combination selected. 
 
Option 1 – EOL (End of line) Resistor 
Option 2 – Series (In line) resistor  
Option 3 – Series and EOL resistors 
 
 
The equipment needs to be installed with ATEX 
and/or IECEx certified Zener Barriers or Galvanic 
Isolators. 
 
 
 
 

8) 

Testing unit operation 

The push button unit can be tested without the 
need to replace any element.  
 
To test, lift the cover lift flap to reveal the push 
button. The button should be pressed into the body 
to activate the unit and place it into the operated 
condition. 
 

 

 
 
The call point switch will now change over it’s 
contacts to operate the alarm. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Once testing is complete the unit needs to be reset 
from the operated condition.  
 
Rotate the push button anticlockwise by an angle 
of 55º, see guide alignment marks on button and 
cover, shown below (1). The push button should 
pop back up to its original position. 
Ensure that the push button has also twisted back 
clockwise by 55º to its original position see guide 
marks on button and cover, shown below (2). 
The unit is now reset. 
  
 

 

 
 

1. On operated unit 

         2. Button should pop 

Twist push button 

         up and twist back to 

Anticlockwise 55º 

         original position 

to reset 

 

          

 
 
 

 
Note: use alignment 
marks circled to 
indicate the push 
button’s status 
/position.  
 
Unit currently shown 
as ‘standby 
condition’ 
 

 
Resetting an operated unit is the same as resetting 
a tested unit. 

Отзывы:

Похожие инструкции для IS-CP4B-PB