IS-CP4B-PB 

Manual Call Point – Push Button 
With resistor Modules 

For use in Flammable Gas and 
Combustible Dust Atmospheres 
 

 

1) Introduction 

The IS-CP4B-PB is a push button manual call point 
which is certified intrinsically safe to the European 
and International Gas standards. The unit meets 
the requirements of the ATEX directive 94/9/EC 
and IECEx scheme. 
 
The call point can be used in hazardous areas 
where potentially flammable gas atmospheres may 
be present. 
 
The IS-CP4B-PB has up to two monitoring 
resistors. The units are Group II, EPL (equipment 
protection level) Ga. The equipment is certified ‘Ex 
ia IIC T4 Ga’ and as such may be used in Zones 0, 
1 and 2 with flammable gases and vapours with 
gas groups IIA, IIB & IIC and temperature classes 
T1, T2, T3 and T4. 
 
The equipment needs to be installed with ATEX 
and/or IECEx certified Zener Barriers or Galvanic 
Isolators. 
 

 
 

2) Marking 

All units have a rating label, which carries the 
following important information:- 
 
Unit Type No.: 
IS-CP4B-PB Manual Call Point 
 
Code: 
Ex ia IIC T4 Ga 
IP66 
 
Ui=30V Ii=500mA Pi=1.1W Ci=0 Li=0 
 
–40ºC <= Ta <= +50ºC 
 
Certificate No.: 
SIRA 09ATEX2287X 
IECEx SIR 09.0122X 
 
Epsilon x:                           II 1G 
 
 
CE Marking 
Notified body No.               0518 
 
Year/Serial No. i.e. 10/1CP4BPB000001   
 
WARNING - DO NOT OPEN WHEN AN 
EXPLOSIVE ATMOSPHERE MAY BE PRESENT 

 
3) Type 

Approval 

Standards 

The beacon has an EC Type examination 
certificate issued by SIRA and have been approved 
to the following standards:- 
 
EN 60079-0:2012 / IEC 60079-0:2011 
EN 60079-11:2012 / IEC 60079-11:2011 
IEC 60079-26:2014 
 
The equipment is certified for use in ambient 
temperatures in the range -40

o

C to +50

o

C and shall 

not be used outside this range. 
 

4) Installation 

Requirements 

 Installation of this equipment shall only be carried 
out by suitably trained personnel in accordance 
with the applicable code of practice e.g. IEC 
60079-14/EN 60079-14. 
 
 
 
 

 
Repair of this equipment shall only be carried out 
by the manufacturer or in accordance with the 
applicable code of practice e.g. IEC 60079-19/EN 
60079-19. 

 

The certification of this equipment relies on the 
following materials used in its construction: 
 
Enclosure:

 

Aluminium Pressure Die Cast Body 

LM6 
 
Through enclosure mechanism: Plastic Nylon Zytel 
Injection Moulded 
 
Sealing of enclosure and mechanism: O-ring 
Acrylonitrile-Butadiene Rubber  
 
If the equipment is likely to come into contact with 
aggressive substances, then it is the responsibility 
of the user to take suitable precautions that prevent 
it from being adversely affected, thus ensuring that 
the type of protection is not compromised. 
 
“Aggressive substances” - e.g. acidic liquids or 
gases that may attack metals, or solvents that may 
affect polymeric materials. 
 
“Suitable precautions” - e.g. regular checks as part 
of routine inspections or establishing from the 
material’s data sheet that it is resistant to specific 
chemicals. 
 
Refer to certificates SIRA 09ATEX2287X and 
IECEx SIR 09.0122X for special conditions of safe 
use. 
 
 

5) 

Call Point Location and Mounting 

The location of the call point should enable ease of 
access for operation and testing. The unit should 
be mounted using the 4 off fixing holes which will 
accept up to M4 sized fixings. 
 
When installing in Zone 0 applications, ensure that 
the equipment enclosure is protected from impact. 
 

 

 
View of base unit showing fixing centres. 
 
 
To gain access to the mounting holes in the base 
the front cover must be removed.  
 
This is achieved by removing the 4 off M4 cap 
head bolts holding on the cover. 
 

 

 
Once the screws are removed the cover will hang 
down out of the way to gain access to the Ex e 
terminal block, the internal earth terminal and 
mounting hole recesses. 
 
 
 
 

INSTRUCTION MANUAL  

IS-CP4B-PB Push Button Manual Call Point 

For use in Flammable Gas and Dust Atmospheres 