background image

 

 

_______________________________________________________________________________________________________________________________ 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH           [email protected]              Tel: +44 (0)20 8743 8880 

                                                                                                                                                             www.e2s.com             Fax: +44 (0)20 8740 4200 
Document No. IS 4501      Issue E                 27-11-09                       

Sheet 1 of  6

 

INSTRUCTION MANUAL 

IS-A105N 

Intrinsically Safe Sounder

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

1)  Introduction 

 
The  IS-A105N  is  an  ATEX  and  IECEx  certified  intrinsically 
safe  sounder  which  produces  a  loud  warning  signal  in  a 
hazardous  area.  Forty-nine  first  stage  alarm  sounds can  be 
selected by internal switches and each one can be externally 
changed  to  a  second  or  third  stage  alarm  sound.  The 
sounder may be used in all gas groups IIA, IIB and IIC. The 
IS-A105N  sounder  may  be  used  in  conjunction  with  an  IS-
L101L intrinsically safe beacon, allowing a combined audible 
and visual alarm to be constructed. 
 

2)  Description 

 
Fig  1  shows  a  simplified  block  diagram  of  an  IS-A105N 
sounder. The device operates  immediately  power  is  applied 
to  the  +  and  –  terminals  which  are  duplicated  to  allow  a 
second sounder to be connected in parallel, or for an end of 
line  monitoring  resistor  to  be  installed.  The  output  tone  is 
defined by the positions of the six internal switches and this 
tone can be changed to a second or third stage alarm tone by 
connecting  terminals  S2 or S3  to 0V.  The  tone  generator  is 
crystal  controlled  to  ensure  that  when  two  sounders  are 
started  at  the  same  time  the  output  tones  remain 
synchronised. 

 

3) 

Supply Voltage

 

 
The  IS-A105N  sounder  has  been  designed  to  operate  in  a 
hazardous area from a 24V dc supply via 28V 93mA resistive 
ATEX  and  IECEx  certified  Zener  Barriers  or  Galvanic 
Isolators. The sounders may be tested or used in safe areas 
without  a  Zener  barrier  or  galvanic  isolator,  but  at  supply 
voltages above 16V the internal current limit will function and 
therefore  it  is  recommended  that  they  are  not  operated 
continuously with a direct supply greater than 16V. 
 
 

 

-
-

IS-A105N Sounder

Volume Control

Tone Selection Switches

Tone Generator

+
+

S2

S3

 

 

Fig 1 Simplified block diagram 

 

4) 

Intrinsic Safety Certification

 

 

4.1 ATEX certificate 

The  IS-A105N  sounder  complies  with  the  following 
standards:-  
 
EN60079-0:2006  
EN60079-11:2007 
EN60079-26:2007 
IEC60079-0:2007 

(used for guidance in respect of marking)

 

 

 

 
The  EC-Type  Examination  Certificate  SIRA  04ATEX2301X 
has  been  issued  by  the  Notified  Body  Sira.  This  confirms 
compliance  with  the  European  ATEX  Directive  94/9/EC  for 
Group II, Category  1G equipment.   The sounder carries  the 
Community Mark and subject to local codes of practice, may 
be  installed  in  any  of  the  EEA  member  countries.  This 
instruction  sheet  describes  installations  which  conform  to 
EN60079:Part14:2008  Electrical  Installation  in  Hazardous 
Areas.   When  designing systems  for  installation  outside  the 
UK, the local Code of Practice should be consulted. 
 
 

1) 

The certification marking is as follows:  

 

e

2S

european safety systems ltd. 

SIRA 04ATEX2301X

0518

IS-A105N Sounder

London W3 7QH UK
www.e2s.com

Year / Serial No.  
   09 / 1S000001

WARNINGS:

 

IECEx SIR 04.0038X

Term. + w.r.t. Term. -  Ui = 28V  Ii = 93mA  

                                    Pi = 660mW   Ci = 0   Li = 0

Term. S2&S3 w.r.t. Term. -   Ui = 28V  Ii = 0mA

FM

APPRO VED

To a void a  possible electrostatic
charge on ly cle an with a damp cloth 

To prevent ignitio n of flammable or combustible
 atmosph eres, disconnect power before servicing

 

Su bstitution of componen ts may impair safe ty 

IS C lass I, Zone 0, AEx ia IIC T4
IS C lass l, Division 1, Groups A, B, C, D

II 1G   Ex ia IIC  T4 Ga  (-40ºC <=Ta<= +60° C)

Con trol Drawing No. D 4528

 

The IS-A105N sounder is CE marked for 

compliance with the European 

Explosive Atmospheres Directive 

94/9/EC and the European EMC 

Directive 89/336/EEC 

II 1G      Ex ia IIC T4 Ga (-40ºC <= Ta <= +60ºC) 

Отзывы: