8)  AC Wiring 

 

A  6-way  terminal  block  is  provided  on  the  AC  Sounder  for 

power.  There  are  2-off  Live,  2-off  Neutral  and  2-off  Earth 

terminals  in  total.  A  3-way  terminal  is  provided  for  stage 

switching with a stage 2, a stage 3 and a common terminal.  

 

8.1 

Wiring Diagrams 

 

 
 

Fig 3. E2xS1 AC Simplified Block Diagram 

 

8.2 

Stage Switching 

 

8.2.1 

Units First Stage Tones 

 

Stage one (S1) Operation 

 

Simply connect the supply 

voltage  to  the  L  and  N 
supply  terminals,  (see  fig. 

4). 

 

 

8.2.2 

 AC  Units  Second  &  Third  Stage  Tone 
Selection 

 

To select the second and third stage tones on the E2xS1 AC 

sounder. 

 

Stage two (S2) Operation 

 

Power L and N. 
Link the Common-C and 

S2 terminal.  

Dip switch alters stage 2 

tone.

 

Stage three (S3) Operation 

 

Power L and N. 
Link the Common-C and 

S3 terminals.  

Dip switch alters stage 3 

tone. 

 
 

 
 

 
 

 

 

 

Fig. 4 AC Terminals 

 

9)  DC Wiring 

 

A  10-way  terminal  block  is  provided  on  the  DC  Sounder. 

There are 2-off +ve, 2-off -ve, 2-off stage 2, 2-off stage 3 and 

2-off Earth terminals in total. 

 

9.1 

Wiring Diagrams 

 

 
 

 

 
 

Fig. 5 DC Simplified Block Diagram  

 

9.2  

Stage Switching 

 

9.2.1 Units First Stage Tones 

 

Stage one (S1) Operation 

 

Simply  connect  the  supply 
voltage  to  the  +  and  - 

supply  terminals,  (see  fig. 

6). 

 

9.2.2  

DC  Units  Second  &  Third  Stage  Tone 

Selection 

 

Stage two (S2) Operation

 

 

Power +ve and –ve. 

Link a -ve supply line to the 
S2 terminal.  

Dip  switch  alters  stage  2 

tone. 

 

 

 

 

 

 