Document No. D209-00-511-IS

 

Issue 1

 

20-08-22

 

 

Sheet 5 of 7

 

 

       

--   

     ++      S2   S3 

 
 

 

 

Fig. 6a DC Sounder Terminals 

 
 

 

Fig. 6b beacon DC Terminals 

 
11.2    Line Monitoring 

 

On  E2xC1LD2  DC  units,  DC reverse  line  monitoring  can  be 
used  if  required.  All  DC  sounders  and  beacons  have  a 
blocking diode fitted in their supply input lines. An end of line 
monitoring resistor can be connected across the +ve and –ve 
terminals.  If  an  end  of  line  resistor  is  used  it  must  have  the 
following values: 
 

 

Min. Resistance 

Min. Power 

24V DC 

3.9KΩ 

0.5W 

1KΩ 

2W 

48V DC 

15KΩ 

0.5W 

3.9KΩ 

2W 

 
11.2.1  Sounder Line Monitoring

 

 
The resistor must be connected directly across the +ve and  
-ve terminals as shown in the following drawing. Whilst 
keeping its leads as short as possible, a spacing of at least 
1/16” (1.58mm) must be provided through air and over 
surfaces between uninsulated live parts. 

 

 

Fig. 8 End of Line Resistor Placement 

 
11.2.2  Beacon Line Monitoring 
 
(Independent Beacon and Sounder Operation Only) 

 
The resistor must be connected directly across the +ve and  
-ve terminals as shown in the following drawing. Form the 
resistor legs as shown in Fig. 9a, remove the +ve and –ve 
terminal plugs and fit the resistor across the two terminal 
plugs before refitting them to the PCBA as shown in Fig. 9b. 
A spacing of at least 1/16” (1.58mm) must be provided 
through air and over surfaces between uninsulated live parts. 

 

 

 

Fig. 9a End of Line Resistor Forming 

 

 

 

Fig. 9b End of Line Resistor Placement 

 

12. Settings 
 

12.1  Tone Selection 

 

The sounders have 45 different tones that can be selected for 
the first stage  alarm.  The  sounders  can  then be  switched  to 
sound  second  and  third  stage  alarm  tones.  The  tones  are 
selected by operation of a DIP switch on the PCB for both DC 
and  AC  units.  The  tone  table  on  page  six  shows  the  switch 
positions  for  the  45  tones  and  which  tones  are  available  for 
the  second  and  third  stages.  To  operate  the  sounder  on 
stage  1  simply  connect  the  supply  voltage  to  the  normal 
supply  terminals  (+ve  and  –ve  for  DC units, L  and  N for AC 
units). 

 
 
 
 
 

End of Line Resistor 

48V DC 
Volume 
Control 

DIP Switch 

S3
S2


E

 

24V DC 
Volume 
Control 

End of Line Resistor 

Содержание E2xC1LD2F

Страница 1: ...ating Marking Information 3 1 ATEX IECEx UKEx certification The E2xC1LD2 combined alarm horn and LED beacon complies with the following standards Standards EN IEC 60079 0 2018 IEC60079 0 2017 Ed 7 Exp...

Страница 2: ...IC Dc T105 C Ta 20 C to 55 C Ex tc IIIC Dc T90 C Ta 20 C to 40 C Installation must be carried out in compliance with the Canadian Electric Code 4 Zones Gas Groups Category and Temperature Classificati...

Страница 3: ...e E2x combined sounder beacon should be secured to any flat surface using the three 7mm fixing holes on the stainless steel U shaped mounting bracket See Figure 1 The required angle can be achieved by...

Страница 4: ...tional area of 2 5mm Strip wires to 8mm Wires may also be fitted using ferrules Terminal screws on the sounder PCBA need to be tightened down with a tightening torque of 0 45 Nm 4 Lb in Terminal screw...

Страница 5: ...ing Independent Beacon and Sounder Operation Only The resistor must be connected directly across the ve and ve terminals as shown in the following drawing Form the resistor legs as shown in Fig 9a rem...

Страница 6: ...he equipment should only be carried out by suitably qualified personnel in accordance with the current relevant standards EN60079 19 IEC60079 19 Explosive atmospheres Equipment repair overhaul and rec...

Страница 7: ...400 2900Hz 50Hz Sweeping 25 Tone 5 Tone 29 1 1 1 0 1 0 800 1000Hz 50Hz Sweeping 24 Tone 5 Tone 6 0 1 1 0 1 0 800Hz 2Hz Intermittent 23 Tone 5 Tone 2 1 0 1 0 1 0 544Hz 0 875 sec Intermittent 22 Tone 5...

Страница 8: ...HOWN ABOVE DRAWING TO BS8888 2000 GEOMETRIC TOLERANCES TO ISO1101 1983 LINEAR DIMENSIONAL TOLS ANGULAR DIMENSIONAL TOLS 05 08 2020 05 08 2020 DC E2XC1LD2 UNITS Line Monitoring Stage 1 Apply power to S...

Страница 9: ...Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 3G Ex ec IIC T4 T3 T2 Gc II 3D Ex tc IIIC 85 C 120 C Dc IP6X Dust Protection to EN60079 0 EN60079 31 Standar...

Страница 10: ...e and Place of Issue London 22 08 2022 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the m...

Страница 11: ...on Module D CSAE 22UKQAN0046 Provisions fulfilled by the equipment II 3G Ex ec IIC T4 T3 T2 Gc II 3D Ex tc IIIC 85 C 120 C Dc IP6X Dust Protection to EN60079 0 EN60079 31 Standards applied EN IEC 6007...

Страница 12: ...Place of Issue London 22 08 2022 UKCA Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the marke...

Отзывы: