European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH           [email protected]              Tel: +44 (0)20 8743 8880 

                                                                                                                                                             www.e2s.com             Fax: +44 (0)20 8740 4200 
Document No. IS4202     Issue:  H                 26-03-13                         Sheet 2 of 3 

a suitable cable gland. Follow the markings for the terminals 
on the PCB and install wiring as shown in the diagram below. 
 
Cable glands need to be UL certified to ANSI/UL 2225 or 
C22.2 NO. 174-M1984. and to UL514B / CSA-C22.2 No. 18.3-
12, ratings for hazardous locations must be equal to or better 
than the rating of the sounder used. 
If a high IP (Ingress Protection) rating is required then a 
suitable sealing washer must be fitted under the cable gland. 

 

WARNING - ALL ELECTRICAL WIRING MUST BE 

       INSTALLED IN ACCORDANCE TO THE 
       NATIONAL ELECTRICAL CODE 

 

AC SOUNDERS 

Black 

 Live 

 Violet 

 C 

White 

 Neutral 

 Orange 

 S2 

Green/Yellow 

 

Ground 

 Yellow 

 S3 

S3

S2 

 

Stage 3

Stage 2

L
N

C

C

N

L

L

N

C S2 

 

S3

S3

S2 

 

C

N

L

NOTE if the second and third stage wires are not used they must be 
individually insulated to ensure that cannot make contact to any other wires.

DC SOUNDERS

 

Red 

 Positive 

 Orange 

 S2 

Black 

 Negative 

 Yellow 

 

 S3 

Green/Yellow  

Ground

 

S3

S2 

 

Stage 3

Stage 2

+

-

-

+

S2 

 

S3

S3

S2 

 

NOTE if the second and third stage wires are not used they must be 
individually insulated to ensure that cannot make contact to any other wires.

-

+

-

+

 

POWER SUPPLY SELECTION 

It is important that a suitable power supply is used to run the 
sounders. The power supply selected must have the 
necessary capacity to provide the input current to all of the 
sounders connected to the system. 
  

Unit Type 

Input  

 

Input @ 1kHz 

Max. 

 

 

Voltage   

Current                I/P Volts

 

E2xS121UL 

24V 

DC 

 280mA 

 30V 

E2xS121UL 

48V 

DC 

 215mA 

 58V 

E2xS121UL 

230V 50/60Hz AC  76mA 

 

253V 

E2xS121UL 

120V 50/60Hz AC  142mA 

 

132V 

 

 
 
 
TONE SELECTION

 

The E2xS121UL sounders have 45 different tones that can be 
selected for the first stage alarm. The sounders can then be 
switched to sound second and third stage alarm tones. The 
tones are selected by operation of a DIP switch on the pcb for 
both DC and AC units. The tone table opposite shows the 
switch positions for the 45 tones and which tones are 
available for the second and third stages. To operate the 

sounder on stage one simply connect the supply voltage to the 
flying leads (Red and Black for DC units, Black, White and 
Green/Yellow for AC units).  
 
The operation of the second and third stages is different for DC 
and AC units. 
 
DC Units Second and Third Stage Tone Selection 
To activate the second stage, remotely switch the S2 orange 
wire to the negative supply.  To activate the third stage, 
remotely switch the S3 orange wire to the negative supply.  
NOTE the DC power supply to the Red and Black wires must be 
maintained for 2

nd

 and 3

rd

 stages. 

 
AC Units Second and Third Stage Tone Selection 
To select the second and third stages on the E2xS121UL AC 
sounders the Common (C) Violet wire must be remotely 
connected to the S2 orange wire for the second stage and to 
the S3 yellow wire for third stage. NOTE the AC power supply to 
the Black and White lead must be maintained for 2

nd

 and 3

rd

 

stages. 
 

VOLUME CONTROL 

The volume on the E2xS121UL sounder can be set using the 
volume control (see figures 2 and 3). For maximum output level 
the potentiometer should be set to the fully clockwise position. 
 
 

WARNING – HIGH VOLUME MAY CAUSE HARM TO 
  

       PERSONNEL IN CLOSE PROXIMITY 

 
 

END OF LINE MONITORING 

On E2xS121UL DC units, dc reverse line monitoring can be 
used if required. All DC sounders have a blocking diode fitted in 
their supply input lines. An end of line monitoring resistor can be 
connected across the +ve and –ve terminals. If an end of line 
resistor is used it must have the following values:- 
 

24V DC Sounders 

 
Minimum Resistance 3k9 ohms 

Minimum wattage 0.5W 

Minimum Resistance 1k ohms 

Minimum wattage 2.0W 

 

48V DC Sounders 

 
Minimum Resistance 15k ohms 

Minimum wattage 0.5W 

Minimum Resistance 3k9 ohms 

Minimum wattage 2.0W 

 
The resistor must be connected directly across the +ve and –ve 
terminals as shown in the following drawing. Whilst keeping its 
leads as short as possible, a spacing of at least 1/16 inch 
(1.58mm) must be provided through air and over surfaces 
between uninsulated live parts.  

S3

  S3

  S2

  

S2 

  

 

-  

 -  

 +  

  +

   

    

 

E2xS121UL DC Sounder 
End of Line Resistor

G   

 G

  

  

   

 

End of Line Resistor

 

 