10) Earthing
The unit has both internal and external earth terminals,
(please see fig 3).
Internal earthing connections should be made to the internal
earth terminal on the PCBA, (please see fig 5 for AC, fig 8 for
DC). The earth conductor should be at least equal in size and
rating to the incoming power conductors. The internal earth
bonding wire connects the PCBA earth terminal to the
internal earth terminal in the enclosure back box.
External earth connections should be made to the M5 earth
stud, using a ring crimp terminal to secure the earth
conductor to the earth stud. The external earth conductor
should be at least 4mm2 in size. The external earth crimp
ring should be located between the two M5 plain washers
provided and securely locked down with the M5 spring
washer and M5 nut.
11) Settings
11.1 Flash Rate Setting
The D2xB1LD2 beacons can produce different flash patterns
as shown in Table 1. The flash patterns are selected by
operation of the flash setting DIP switch on the PCB, Fig 6.
Fig. 9: DIP Switch Location
(
*
setting permitted for use as public mode fire alarm device)
Table 1: Switch Positions for Flash Patterns
Fig. 10 Dip Switch
1=ON; 0=OFF
Example shown: 100000 = Flashing 1Hz (Default setting)
12) Interchangeable & Spare Parts (General
Signaling and Private Mode Alarm
Versions only)
The Beacon lens cover is interchangeable, contact E2S Ltd for a
replacement lens cover available in various colours. Please note that
Private Mode Fire Alarm units can only be used with either clear or
red lenses, Public Mode Fire Alarm units cannot be used with a lens
or a guard.
To change the lens cover, unscrew the 4-off M5 posi pan head
screws, spring and flat washers using a screwdriver. Remove the
wire guard and replace the old lens cover with the new lens cover.
Fig. 11 Replacement of beacon lens cover
Fit the wire guard back onto the housing, over the new lens cover
aligning the fixing holes of the guard, lens cover and housing. Refit
the fixings to hold into place, the fixings MUST be fitted in the order
shown above.
Switch
Setting
S1 Mode
S2 Mode
S3 Mode
(123456)
(DC & AC)
(DC Only)
(DC Only)
000000
Steady High
Power
Flashing 1Hz
*
Flashing Triple
Strike
000001
Steady Low
Power
Flashing 1Hz
*
Flashing Triple
Strike
100000
Flashing
1Hz
*
Flashing
Double Strike
Flashing Triple
Strike
101000
Flashing
1.5Hz
*
Flashing 2Hz
*
Flashing
Double Strike
010000
Flashing
2Hz
*
Flashing Triple
Strike
Flashing Triple
Strike
110000
Flashing
Double Strike
Steady High
Power
Flashing Triple
Strike
001000
Flashing
Triple Strike
Flashing 2Hz
*
Flashing
Double Strike
Warning –
Hot surfaces. External surfaces
and internal components may be hot after
operation, take care when handling the
equipment.
Warning – high-intensity light source. Avoid
looking directly at the light source for
extended periods of time.
M5 screw
M5 spring washer
M5 flat washer