European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH           [email protected]              Tel: +44 (0)208 743 8880 

                                                                                                                                                             www.e2s.com             Fax: +44 (0)208 740 4200 
Document No. D211-00-401-IS-SC           Issue E          02-03-2020                         Sheet 4 of 10

 

N      L          

       

--   

     ++      S2   S3 

(Customer 

supplied 

switches) 

N
L

N N L L

N N L L

N N L L

-

+

- - + +

- - + +

- - + +

S2 S3

S2 S3

S2 S3

S2

S3

Wires having a cross sectional area between 0.5 mm² to 
2.5mm² can be connected to each terminal way. If an input 
and output wire is required the 2-off Live/Neutral or +/- 
terminals can be used. If fitting 2-off wires to one terminal 
way the sum of the 2-off wires must be a maximum cross 
sectional area of 2.5mm². Strip wires to 8mm. Wires may also 
be fitted using ferrules. Terminal screws need to be tightened 
down with a tightening torque of 0.56 Nm / 5 Lb-in. When 
connecting wires to the terminals great care should be taken 
to dress the wires so that when the cover is inserted into the 
chamber the wires do not exert excess pressure on the 
terminal blocks. This is particularly important when using 
cables with large cross sectional areas such as 2.5mm². 
 

8) AC 

Wiring 

 

3-off 2-way terminal blocks are provided on the AC beacon 
for power. There are 2-off Live, 2-off Neutral and 2-off Earth 
terminals in total. 

 

8.1 Wiring 

Diagrams 

 
 
 
 
 
 
 

 

Fig 3. D2XB1LD2 AC Simplified Block Diagram 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Fig. 4 D2XB1LD2 AC Terminals 

 

9) DC 

Wiring 

 

3-off 2-way terminal blocks are provided on the AC beacon 
for power. There are 2-off +ve, 2-off –ve, 1-off Stage 2 and 1-
-off stage 3 terminals in total. 
 

9.1 Wiring 

Diagrams 

 
 

 
 
 
 
 
 
 

Fig. 5 D2XB1LD2 DC Simplified Block Diagram  

 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Fig. 6 D2XB1LD2 DC Terminals 

 
9.2 Line 

Monitoring 

 

On D2xB1LD2 DC units, DC reverse line monitoring can be 
used if required. All DC beacons have a blocking diode fitted 
in their supply input lines. An end of line monitoring resistor 
can be connected across the +ve and –ve terminals. If an 
end of line resistor is used it must have the following values: 
 
24V DC applications 
 
Minimum resistance 3K9 Ohms 

Minimum Power 0.5W 

Minimum resistance 1K Ohms 

Minimum Power 2.0W 

 
48V DC applications 
 
Minimum resistance 15K Ohms 

Minimum Power 0.5W 

Minimum resistance 3K9 Ohms 

Minimum Power 2.0W 

 
The resistor must be connected directly across the +ve and  
-ve terminals as shown in the following drawing. Form the 
resistor legs as shown in Fig. 8a, remove the +ve and –ve 
terminal plugs and fit the resistor across the two terminal 
plugs before refitting them to the PCBA as shown in Fig. 8b. 
A spacing of at least 1/16” (1.58mm)

 

must be provided 

through air and over surfaces between uninsulated live parts. 
 

 

 

Fig. 7 End of Line Resistor Forming 

 

 
 
 

 
 
 

 
 
 
 

 

 

Fig. 8 End of Line Resistor Placement 

 

 

End of Line Resistor 

-

 

             

+

 

Содержание D2xB1LD2AC230

Страница 1: ...971 UL1638 CAN ULC S526 2 2 Private Mode Fire Alarm Ratings All models are approved for use as Visual Appliance for use in Fire Alarm Systems Private Mode For private mode fire alarm use the beacons m...

Страница 2: ...0079 10 2 Explosive atmospheres Classification of areas Explosive dust atmospheres 2 7 Ingress Protection Ratings The product is rated for ingress Protection as follows IP rating IP66 Type rating per...

Страница 3: ...t to all of the sounders connected to the line When selecting the cable size consideration must be given to the voltage drop over the length of the cable run to ensure the min input voltage at the poi...

Страница 4: ...r There are 2 off Live 2 off Neutral and 2 off Earth terminals in total 8 1 Wiring Diagrams Fig 3 D2XB1LD2 AC Simplified Block Diagram Fig 4 D2XB1LD2 AC Terminals 9 DC Wiring 3 off 2 way terminal bloc...

Страница 5: ...itch 1 ON 0 OFF Example shown 100000 Flashing 1Hz Default setting 12 Interchangeable Spare Parts General Signaling and Private Mode Alarm Versions only The Beacon lens cover is interchangeable contact...

Страница 6: ...e equipment should only be carried out by suitably qualified personnel in accordance with the current relevant standards EN60079 19 IEC60079 19 Explosive atmospheres Equipment repair overhaul and recl...

Страница 7: ...rried out to the correct NFPA standards and guidelines 14 1 Horizontal Light Output Dispersion for wall mounting public mode 0 15 15 30 45 60 75 90 90 30 45 60 75 Fig 12 Horizontal dispersion angles f...

Страница 8: ...Dispersion for wall mounting public mode 75 60 45 30 15 0 90 Fig 13 Vertical dispersion angles for wall mounting Table 4 Vertical Light Output Dispersion for Wall Mounting Viewing Angle Of Rating Inte...

Страница 9: ...in values as per UL 1971 UL1638 CAN ULC S526 at worst case min input voltage 14 4 On axis light output rating private mode Table 5 Vertical Light Output Dispersion for Ceiling Mounting Viewing Angle O...

Страница 10: ...4mA 180mA Flashing Triple Strike 144 8mA 211 2mA D2xB1LD2AC115 115Vac 60Hz 115 120Vac 50 60Hz Steady High Power 83mA 102 4mA Steady Low Power 53mA 88 1mA Flashing 1Hz 68mA 99 7mA Flashing 1 5Hz 64 1m...

Отзывы: