10) End of Line Monitoring (DC Units) 

 

10.1 

Standard DC End Of Line Monitoring 

  

All DC units have a blocking diode fitted in their supply input lines. An 
end of line monitoring diode or an end of line monitoring resistor can 
be  connected  across  the  +ve  and 

–ve  terminals  in  the  flameproof 

chamber.  If  an  end  of  line  resistor  is  used  it  must  have  a  minimum 
resistance value  of  3k3  ohms  and  a  minimum  wattage  of  0.5W  or a 
minimum resistance value of 500 ohms and a minimum wattage of 2W. 

 

The  resistor  must  be  connected  directly  across  the  +ve  and  -ve 
terminals as shown in the following drawing. The resistor leads should 
be kept as short as possible. See D190-06-001 for details. 

Figure 9: End of Line Resistor placement. 

 

10.2       Custom DC Multi-Stage End Of Line Monitoring 

  

An optional 12-way terminal module is available to enable up to four 
alarm stages to be activated from three DC voltage output channels. 
The three alarm stage activation inputs can be independently 
monitored. 
  
Refer to Schematic D190-06-001, Config. 6. 
Specify Product option ‘V’ when ordering. 
Spare part code for field installation: SP78-0001 

 

 

11) Maintenance, Overhaul and Repair 

 

Maintenance,  repair  and  overhaul  of  the  equipment  should  only  be 
carried  out  by  suitably  qualified  personnel  in  accordance  with  the 
current relevant standards: 
 

For ATEx/IECEx or UKEx: 

 

EN60079-19/IEC60079-19  

 

Explosive  atmospheres 

–  Equipment  repair,  overhaul  and 

reclamation 

 

EN 60079-17/IEC60079-17    
Explosive  atmospheres 

– Electrical installations inspection 

and maintenance 

 
Units must not be opened while an explosive atmosphere is present. 
 
If opening the unit during maintenance operations, a clean 
environment must be maintained and any dust layer removed prior to 
opening the unit. 
 
Potential electrostatic charging hazard 

– Clean only with a damp 

cloth. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Figure 10: End of Line Resistor placement 

– 

Optional 12-Way Terminal Module. 

 
 
 
 
 
 

 

 
 
 
 
 
 
 
 
 
 
 
 
 

Содержание D1xS2FAC230-A

Страница 1: ...S ATMOSPHERES DISCONNECT FROM SUPPLY BEFORE OPENING KEEP TIGHTLY CLOSED WHEN IN OPERATION WARNING FIT SEALING FITTING IN CONDUIT RUNS WITHIN 18 INCHES FROM ENCLOSURE EQUIPMENT MUST NOT BE INSTALLED WI...

Страница 2: ...C Ex tb IIIC T95 C Db Ta 55 C to 75 C D1xS2 AC230 A Ex db IIC T5 Gb Ta 55 C to 75 C Ex db IIC T6 Gb Ta 55 C to 60 C Ex tb IIIC T93 C Db Ta 55 C to 75 C See Product table for electrical ratings of eac...

Страница 3: ...arges on non conducting surfaces Only the explosionproof cover is to be used for access to the enclosure for installation service and maintenance 6 Specific Conditions for Safe Use Flameproof threaded...

Страница 4: ...nd the length of the cable runs The cable size selected must have the necessary capacity to provide the input current to all the sounders connected to the line AC 1 0 2 5mm2 AWG18 AWG12 DC 0 2 2 5mm2...

Страница 5: ...ders See schematic diagram D190 06 001 for details 9 1 Configuration See Table 1 for product power supply and Sound Pressure Levels SPL Configuration for DC Units Fig 5 DC PCBA Configuration for AC Un...

Страница 6: ...iring options Config Voltage Configuration Description Features Product Option Identifier 1a DC Single Stage Configuration Line monitoring Positive Switching 1 1b DC Two Stage Configuration Common Neg...

Страница 7: ...f Line Monitoring An optional 12 way terminal module is available to enable up to four alarm stages to be activated from three DC voltage output channels The three alarm stage activation inputs can be...

Страница 8: ...ces may be fitted between the ve ve terminals of the PCBA Please ensure that the device legs meet the wire size range stated for the connection terminals and are fitted correctly in order to avoid a s...

Страница 9: ...0 0 0 1 0 1 0 0 0 0 1 1 0 0 0 1 1 1 0 0 0 0 0 0 1 0 0 1 0 0 1 0 0 0 1 0 1 0 0 1 1 0 1 0 0 0 0 1 1 0 0 1 0 1 1 0 0 0 1 1 1 0 0 1 1 1 1 0 0 0 0 0 0 1 0 1 0 0 0 1 0 0 1 0 0 1 0 1 1 0 0 1 0 0 0 1 0 1 0 1...

Страница 10: ...US 100 2dB A CA 108 5dB A P3 US 103 5dB A CA 111 6dB A at 10 feet 24Vdc For Fire Alarm applications the Sounder Volume must be at the highest setting see volume control section For fire alarm use Ton...

Страница 11: ...al Axis 3dB A 39 41 38 41 6dB A 45 47 64 69 D1xS2FDC024 A D1xS2FDC024 S Sounder Directional Characteristics for Canadian Fire CAN ULC S525 P3 OSPL Horizontal Axis Vertical Axis 3dB A 46 48 46 47 6dB A...

Страница 12: ...INE MONITORING RESISTOR CUSTOMER SUPPLIED 14V MAX SYSTEM 120 MIN 2W MIN OR 1K MIN 0 5W MIN 28V MAX SYSTEM 470 MIN 2W MIN OR 2 4K MIN 0 5W MIN RECOMMENDED MINIMUM VALUES R1 Stage 1 ve IN Stage 1 ve OUT...

Страница 13: ...n ve OUT Stage 1 ve OUT Stage 3 ve Stage 1 ve IN H2 H1 Stage 1 ve Stage 1 ve Stage 2 ve Stage 2 ve OF 2 3 R1 S2 S3 R1 S2 R2 OPTIONAL LINE MONITORING RESISTOR CUSTOMER SUPPLIED 14V MAX SYSTEM 120 MIN 2...

Страница 14: ...er to Stage 2 ve Stage 2 ve Two Three Stage Voltage Free Activation Configuration Config 5 Customer Set H1 H2 to Negative Switching See Below Power ve ve Stage 1 Connect Stage 1 ve to Common ve Stage...

Страница 15: ...5 R S RAIT B ISARD R N POTTS OF NTS 1 SWITCHES FOR STAGE OPERATION CUSTOMER SUPPLIED 1 Earth Earth Stage 2 Stage 3 Common Live IN Live OUT Neutral IN Neutral OUT Earth Stage 1 Stage 2 Common N N L L E...

Страница 16: ...warden Industrial Park Hawarden Deeside CH5 3US UK Quality Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 2G Ex db IIC T6 T3 GB II 2D Ex tb IIIC T82 C 145 C...

Страница 17: ...e and Place of Issue London 10 02 2022 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the m...

Страница 18: ...CH4 9JN UK Quality Assurance Notification Module D CSAE 22UKQAN0046 Provisions fulfilled by the equipment II 2G Ex db IIC T6 T3 GB II 2D Ex tb IIIC T82 C 145 C Db Standards applied EN 60079 0 2018 EN...

Страница 19: ...ate and Place of Issue London 24 02 2022 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the...

Страница 20: ...Page left Intentionally blank...

Отзывы: